8.8.10 Input addresses (SCADA to Polydos)
Data block DB100: Register 16 … 19 (40017 - 40020) =
Db100.DBW32 … DBW38
DBW32 - Register 16 / 40017 input word 1
•
Format: BOOL
•
Type of signal: impulse
Address
Description
State
DB100.DBX32.0
Activate control mode "Remote"
TRUE
DB100.DBX32.1
Activate operation mode "Automatic" TRUE
DB100.DBX32.2
Deactivate operation mode
"Automatic"
TRUE
DB100.DBX32.3
Activate dry-material dosing mode
TRUE
DB100.DBX32.4
Activate liquid-concentrate dosing
mode
TRUE
DB100.DBX32.5
Write setpoint of solution
concentration
TRUE
DB100.DBX32.6
Reset fault
TRUE
DB100.DBX32.7
RESERVE
DB100.DBX33.0
RESERVE
DB100.DBX33.1
RESERVE
DB100.DBX33.2
RESERVE
DB100.DBX33.3
RESERVE
DB100.DBX33.4
RESERVE
DB100.DBX33.5
RESERVE
DB100.DBX33.6
RESERVE
DB100.DBX33.7
RESERVE
DBW34 - Register 17 / 40018 input word 2
•
Format: BOOL
Address
Description
State
DB100.DBX34.0
RESERVE
DB100.DBX34.1
RESERVE
DB100.DBX34.2
RESERVE
DB100.DBX34.3
RESERVE
DB100.DBX34.4
RESERVE
DB100.DBX34.5
RESERVE
DB100.DBX34.6
RESERVE
DB100.DBX34.7
RESERVE
DB100.DBX35.0
RESERVE
DB100.DBX35.1
RESERVE
DB100.DBX35.2
RESERVE
DB100.DBX35.3
RESERVE
DB100.DBX35.4
RESERVE
DB100.DBX35.5
RESERVE
DB100.DBX35.6
RESERVE
DB100.DBX35.7
RESERVE
DBD36 - Register 18, 19 / 40019, 40020 input double word 3
Address
Description
Format Type of signal
DB100.DBD36
Setpoint of
solution
concentration
REAL
Value for
concentration [%]