12. Technical data
12.1 Supply voltage
3 x 380-415 V ±10%, 50/60 Hz, PE.
Cable: Max. 10 mm².
See nameplate.
Recommended fuse sizes
Standard as well as quick-blow or slow-blow fuses may be used.
12.2 Leakage current
Earth leakage current > 30 mA.
The leakage currents are measured in accordance with
EN 60 355-1.
12.3 Inputs/output
Start/stop
External potential-free switch.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 0.5 - 1.5 mm².
Digital
External potential-free switch.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 0.5 - 1.5 mm².
Setpoint signals
•
Potentiometer
0-5 VDC, 10 k
Ω
(via internal voltage supply).
Screened cable: 0.5 - 1.5 mm².
Maximum cable length: 100 m.
•
Voltage signal
0-5 VDC/0-10 VDC, R
i
>
50 k
Ω.
Tolerance: +0%/–3% at maximum voltage signal.
Screened cable: 0.5 - 1.5 mm².
Maximum cable length: 500 m.
•
Current signal
DC 0-20 mA/4-20 mA, R
i
= 250
Ω.
Tolerance: +0%/–3% at maximum current signal.
Screened cable: 0.5 - 1.5 mm².
Maximum cable length: 500 m.
Sensor signals
•
Voltage signal
0-5 VDC/0-10 VDC, R
i
>
50 k
Ω
(via internal voltage supply).
Tolerance: +0%/–3% at maximum voltage signal.
Screened cable: 0.5 - 1.5 mm².
Maximum cable length: 500 m.
•
Current signal
DC 0-20 mA/4-20 mA, R
i
= 250
Ω
.
Tolerance: +0%/–3% at maximum current signal.
Screened cable: 0.5 - 1.5 mm².
Maximum cable length: 500 m.
•
Electricity supply to sensor:
+24 VDC, max. 40 mA.
+5 VDC, max. 5 mA.
Signal relay output
Potential-free changeover contact.
Maximum contact load: 250 VAC, 2 A.
Minimum contact load: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm².
Maximum cable length: 500 m.
Bus input
Grundfos bus protocol, GENIbus protocol, RS-485.
Screened 3-core cable: 0.5 - 1.5 mm².
Maximum cable length: 500 m.
12.4 Other technical data
EMC (electromagnetic compatibility)
EN 61 800-3.
Immunity to electromagnetic disturbance - second environment
(industrial areas).
Contact Grundfos for further information.
Enclosure class
Standard: IP 54 (IEC 34-5).
Insulation class
F (IEC 85).
Ambient temperature
•
During operation: –20
°
C to +40
°
C.
•
During storage/transport: –30
°
C to +60
°
C.
Relative air humidity
Maximum 95%.
Sound pressure level
13. Re-lubrication of motor motor bearings
The motor bearings are pre-lubricated on delivery. After approx.
3000 operating hours, the bearings must be re-lubricated.
Note:
Before re-lubrication, the bottom plug in the motor flange
and the plug in the bearing cover must be removed to ensure that
old and excess grease can run out.
When lubricating the first time, use the double quantity of lubricat-
ing grease as the lubricating channel is still empty.
The recommended grease type is Asonic GHY 72, which is a
polycarbamide-based lubricating grease.
14. Disposal
Disposal of this product or parts of it must be carried out accord-
ing to the following guidelines:
1. Use the local public or private waste collection service.
2. In case such waste collection service does not exist or cannot
handle the materials used in the product, please deliver the
product or any hazardous materials from it to your nearest
Grundfos company or service workshop.
Motor size [kW]
Max. [A]
11
25
15
35
18.5
50
22
50
Motor
[kW]
Speed stated
on nameplate
[min
-1
]
Sound pressure level
[dB(A)]
2-pole
4-pole
11
2800-3000
69
63
15
2800-3000
70
65
18.5
2800-3000
70
65
22
2800-3000
73
67
Frame size
Quantity of
lubricating grease
[ml]
Lubricating
intervals
[hours]
Drive end
(DE)
Non-drive
end (NDE)
MMGE 160
23
20
3000
MMGE 180
23
23
Subject to alterations.