Furthermore, the LC 221 has six digital inputs for the following
functions:
– connecting an analogue sensor (4-20 mA or 0-5 V)
– connecting up to four level switches or pressure switches
instead of analogue sensors. An additional float switch can
be connected to the alarm input as backup for the analogue
sensors
– connecting a separate level switch to be used for flood
detection outside the Multilift MOG or MDG. Lifting stations
are often installed in a sump inside the basement - the
lowest point in the building. In case of e.g. groundwater
inflow or water pipe burst, an alarm will be indicated by the
controller.
– connecting a piezoresistive pressure sensor PCB
(pre-assembled)
– connecting an external alarm reset
– connecting the thermal switch of the motor.
For updates and further adjustments, a PC Tool can be
connected. See service instructions.
To allow for the situation that the normal power supply should fail,
a battery (accessory) can be installed which activates an acoustic
alarm (buzzer). The buzzer is activated as long as the fault exists.
It cannot be reset.
In case of sectional power failure, the common alarm output
which is a potential-free changeover contact can be used to
forward the alarm signal to a control room by means of an
external power source.
Type key, LC 221 controller
Nameplate, LC 221 controller
The controller type, voltage variant, etc. are stated in the type
designation on the nameplate situated on the side of the
controller cabinet.
Fig. 9
Example of an LC 221 nameplate
Example
LC 221 .1 .230 .1 .10 .30
LC 221 = controller type
1 = one-pump controller
2 = two-pump controller
Voltage [V]
1 = single-phase
3 = three-phase
Max. operating current [A]
Capacitors [
μ
F]
Starting method:
[ ] = DOL
SD = Star-delta
T
M
05
18
70
33
11
Pos.
Description
1
Type designation
2
Product number
3
Production code, year and week
4
Number of phases
5
Maximum pump input current
6
Maximum voltage at potential-free contact
7
Maximum backup fuse
8
Minimum ambient temperature
9
Version
10
Serial number
11
Rated voltage
12
Power consumption
13
Maximum current at potential-free contact
14
Weight
15
Maximum ambient temperature
16
Frequency
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Type
Prod.-No.
P.c.
f
Phases
U
G
Serial no.
P
max
T
Amb
max
I
Pump max
V
A
Hz
C
O
kg
98189707
LC 221.1.230.1.10.30/150 MPU
98189707
1221
1
10
250
16
0
V01
0012
220-240
3
2
5.2
40
50
U
contact max
I
Fuse max
T
Amb min
A
C
O
I
contact max
V
W
A
I
c < 10 kA
IP55
Made in Germany