background image

5

English (US)

voltage and phase of the motors. Verify that the starters are 
suitable to operate the pump motors on voltage and phase that is 
available.

4. Operation

4.1 Priming

The Grundfos Type EB pump is not self-priming, and must be 
completely primed (filled with liquid) before starting. If the pump 
will operate with a positive suction head, prime by opening the 
suction valve and allowing liquid to enter the pump casing. Open 
the air vent at this time and make sure all air is forced from the 
pump by liquid before closing. If the pump has suction lift, priming 
must be accomplished by other methods. The use of foot valves, 
ejectors or vacuum pumps, or by manual filling of the pump 
casing and suction line with liquid are possible methods 
suggested for this purpose. 

4.2 Pre-start checklist

Make the following inspections before starting your Grundfos EB 
pump:

1. Make sure all wiring connections to the motor (and starting 

device) match the wiring diagram and produce clockwise 
rotation as viewed from the back of the motor.

2. Double check rotation. Rotation must be clockwise. Operating 

in reverse will destroy the impeller and shaft.

3. If the motor has been in storage for an extended length of 

time, either before or after installation, refer to motor 
instructions before starting.

4. Check the voltage, phase, and line circuit frequency with the 

motor nameplate. 

5. Tighten plugs in gauge and drain taps. If the pump is fitted 

with pressure gauges, keep gauge clocks closed when not in 
use.

6. Check suction and discharge piping for leaks, and make sure 

all flange bolts are securely tightened.

4.3 Motor rotation

After the unit has been wired and checked to insure that all 
components in the system (disconnect device, magnetic starters, 
pilot devices and motors) are properly connected, check motor 
rotation as follows: For 3 phase units only—momentarily energize 
the motors to ensure that the rotation is correct as indicated by 
the arrow cast into the pump volute. If rotation is incorrect, 
interchange two wires at the motor starter terminals T1 and T2. 
IMPORTANT: The pumps must not be operated while dry. Use 
extreme caution that motors are energized only momentarily to 
determine proper rotation.

4.4 Starting the pump

1. Fully open gate valve (if any) in suction line, and close gate 

valve in discharge line.

2. Fill suction line with liquid and completely prime pump.

3. Start the motor (pump).

4. Immediately make a visual check of pump and suction piping 

for pressure leaks.

5. Immediately after pump reaches full operating speed, slowly 

open the discharge gate valve until complete system flow is 
achieved.

6. Check discharge piping for pressure leaks.

7. If pump is fitted with pressure gauges, open gauge cocks and 

record pressure reading for future reference. Verify that the 
pump is performing in accordance with parameters specified 
on performance curve.

8. Check and record voltage, amperage per phase, and 

kilowatts, if a wattmeter is available.

4.5 Voltage regulation

The motor will operate satisfactorily under the following 
conditions for voltage and frequency variation, but not necessarily 
in accordance with the standards established for operation under 
rated conditions: The voltage variation may not exceed 10% 
above or below rating specified on the motor data plate. The 
frequency variation may not exceed 5% above or below motor 
rating. The sum of the voltage and frequency variations may not 
exceed 10% above or below motor rating, provided the frequency 
variation does not exceed 5%.

4.6 Pump shutdown

The following shutdown procedures will apply in most normal 
shutdowns for the Grundfos Type EB pumps. If the pump will be 
inoperative for an extended length of time, follow storage 
procedures in Extended Period Shutdown. Always close the 
discharge valve before stopping the pump. Close the valve slowly 
to prevent hydraulic shock. Cut and lock off power to the motor.

4.7 Short duration shutdown

For overnight or temporary shutdown periods under non-freezing 
conditions, the pump may remain filled with liquid. Make sure the 
pump is fully primed before restarting.

For short or frequent shutdown periods under freezing conditions, 
keep fluid moving within the pump casing and insulate or heat the 
pump exterior to prevent freezing.

4.8 Extended period shutdown

For long shutdown periods, or to isolate the pump for 
maintenance, close suction gate valve. If no suction valve is used 
and the pump has positive suction head, drain all liquid from 
suction line to terminate liquid flow into pump suction nozzle. 
Remove plugs in pump drain and vent taps, as required, and 
drain all liquid from the pump volute casing. If freezing conditions 
will exist during long shutdown periods, completely drain the 
pump and blow out all liquid passages and pockets with 
compressed air. Freezing of pump liquid can also be prevented 
by filling the pump with antifreeze solution. 

5. Maintenance

Before attempting any inspection or repair on the pump, the driver 
controls must be in the "OFF" position, locked and tagged to 
prevent injury to personnel performing service on the pump.

5.1 Motor lubrication

To lubricate the motor while running or at rest, remove grease 
drain plug (if any) and filler plug on grease fitting. Grease with 
clean lubricant until grease appears at drain hole or along motor 
shaft.

One-half to one cubic inch of grease is sufficient for motors 5 HP 
and under, with proportionately more grease for greater HP 
motors.

Caution

Never run the pump dry in the hope that it will 
prime itself! Serious damage to the shaft seals, 
pump wear rings and shaft sleeves will result.

Warning

In the interest of operator safety, the unit must 
not be operated above the nameplate conditions. 
Such operation could result in unit failure 
causing injury to operating personnel. Consult 
instruction book for proper operation and 
maintenance of the pump and its supporting 
components.

Summary of Contents for EB 20501-5

Page 1: ...GRUNDFOS INSTRUCTIONS End gun booster Installation and operating instructions...

Page 2: ...2...

Page 3: ...ILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES LOSSES OR EXPENSES ARISING FROM INSTALLATION USE OR ANY OTHER CAUSES THERE ARE NO EXPRESS OR IMPLIED WARRANTIES INCLUDING MERCHANTABILITY...

Page 4: ...f installations are threaded straight onto the nipple where the suction must be the same size no decrease in pipe size at suction allowed Discharge pipe size will be the same at the pump or may be one...

Page 5: ...on performance curve 8 Check and record voltage amperage per phase and kilowatts if a wattmeter is available 4 5 Voltage regulation The motor will operate satisfactorily under the following conditions...

Page 6: ...ion normal or light loading clean air 100 F maximum ambient temperature Severe conditions Continuous 24 hour operation shock loading or vibration poor ventilation 100 150 F ambient temperature Extreme...

Page 7: ...ent items Specify pump serial or catalog number when ordering parts 3 Reassembly is the reverse of disassembly 4 Observe the following when reassembling the liquid end All mechanical seal components m...

Page 8: ...8...

Page 9: ...9...

Page 10: ...10...

Page 11: ...Grundfos companies U S A Grundfos CBS Inc 902 Koomey Road Brookshire TX 77423 USA Phone 281 994 2700 Toll Free 1 800 955 5847 Fax 1 800 945 4777...

Page 12: ...ing ahead makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S D...

Reviews: