2. Installation - mechanical

All installations should be performed by personnel experienced 
with the placement, connection, and alignment of pumping 
equipment. The following instructions are general in nature, and 
may not deal with the specifics of your installation. Read these 
instructions thoroughly before installing and operating your 
Grundfos type EB centrifugal pump. Keep these instructions 
handy for future use.

2.1 Pump identification

All Grundfos Pumps are identified by Catalog and Serial 
Numbers. These are stamped on the pump nameplate Fig. 1 
affixed to each pump casing and should be referred to in all 
correspondence with the Company.

Fig. 1

Nameplate

2.2 Receiving

Check pumping unit for shortages and damages immediately 
upon arrival. Pump accessories, when required, are packaged in 
a separate container and shipped with the unit. If equipment is 
damaged in transit, immediately report the damage to the truck 
line’s agent. Make a complete report on the freight bill to speed 
satisfactory adjustment by the carrier. Unload and handle the 
equipment with a sling or tow motor. 

2.3 Temporary storage

If pump is not to be installed and operated soon after arrival, store 
it in a clean, dry area of moderate ambient temperature. Rotate 
the shaft by hand periodically to coat bearing with lubricant to 
retard oxidation and corrosion. Follow motor manufacturer’s 
storage recommendations where applicable.

2.4 Location

Locate the pump as close to the suction supply as possible. Use 
the shortest and most direct suction piping practical. Locate the 
pump below system level wherever possible. This will facilitate 
priming, assure a steady liquid flow, and provide a positive 
suction head. Make sure sufficient NPSH (Net Positive Suction 
Head) is provided at the suction end by considering the pump’s 
location in relation to the entire system. Available NPSH must 
always equal or exceed required NPSH specified on the pump 
performance curve. Always allow sufficient accessibility for 
maintenance and inspection. Provide a clear space with ample 
head room for use of a hoist strong enough to lift the unit. Make 
sure a suitable power source is available for the pump motor. 
Electrical characteristics should match those specified on the 
motor data plate, within the limits covered in Sections 3 and 4. 
Avoid pump exposure to sub-zero temperatures to prevent pump 
liquid from freezing. If freezing conditions exist during shutdown 
periods, see Sections 4.5 and 4.6 for specific recommendations.

2.5 Vertical mounting instructions

The Endgun booster is designed to be mounted vertically on a     
2 ½ ” NPT nipple. It may also be mounted with a nipple and 
companion flange on both the pump and the pivot. The majority of 
installations are threaded straight onto the nipple where the 
suction must be the same size (no decrease in pipe size at 
suction allowed). Discharge pipe size will be the same at the 
pump or may be one or two sizes larger depending on the length. 
Our pump unit is equipped of a wash down duty motor and may 
be used in a variety of outdoor applications.

2.6 Mechanical seals

All Grundfos Type EB pumps that are equipped with mechanical 
seals are matched to the conditions for which the pump was sold. 
Observe the following precautions to avoid seal damage and 
obtain maximum seal life. Do not exceed temperature or pressure 
limitations for the mechanical seal used. Do not run the pump dry 
or against a closed valve! Dry operation will cause seal failure 
within minutes. Purge all air from the seal chambers and 
recirculation lines prior to operating the pump. Clean and purge 
suction piping in new installations before installing and operating 
pump. Pipe scale, welding slag and other abrasives can cause 
rapid seal failure. 

3. Installation-electrical

3.1 Motors general

The motor control circuit must have the following components in 
order to comply with the National Electrical Code.

Motor Disconnecting Device: A motor disconnecting device 
must be installed that is capable of disconnecting both the 
controller (motor starter) and the motor from their source of 
power.

The disconnecting device must be located so that the 
controller (motor starter) can be seen from the disconnecting 
means. In all cases, the distance from the disconnecting 
device to the controller must be less than 50'.

In most installations the disconnecting device will be a circuit 
breaker or fusible disconnect switch.

Motor short circuit and ground fault protection: Short circuit 
and ground fault protection are usually provided by means of a 
circuit breaker or fusible disconnect switch. The selection of 
the size of the circuit breaker or fuse must be in accordance 
with Section 430-52 and Table 430-152 of the National 
Electrical Code.

Motor controller with running over current protection (magnetic 
starter): These components must be installed in accordance 
with applicable local and state electrical codes in addition to 
the National Electrical Code. 

3.2 Installation wiring

Mount the control panel or motor starter(s) in close proximity to 
the pump to provide convenient control and ease of installation. 
Wire panel or starter(s) to motor(s) and pilot device(s): Wires to 
each motor must be sized for at least 125% of the motor 
nameplate full load amps. AWG #16 Type THW stranded wire is 
recommended for wiring of pilot devices (float switches). Check 
incoming power source to ensure that it is the same as the 

TM

 05

 55

91

 37

12

Warning

Whenever powered equipment is being used in 
explosive surroundings, the rules and 
regulations generally or specifically imposed by 
the relevant responsible authorities or trade 
organizations must be observed.

Summary of Contents for EB 20501-5

Page 1: ...GRUNDFOS INSTRUCTIONS End gun booster Installation and operating instructions...

Page 2: ...2...

Page 3: ...ILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES LOSSES OR EXPENSES ARISING FROM INSTALLATION USE OR ANY OTHER CAUSES THERE ARE NO EXPRESS OR IMPLIED WARRANTIES INCLUDING MERCHANTABILITY...

Page 4: ...f installations are threaded straight onto the nipple where the suction must be the same size no decrease in pipe size at suction allowed Discharge pipe size will be the same at the pump or may be one...

Page 5: ...on performance curve 8 Check and record voltage amperage per phase and kilowatts if a wattmeter is available 4 5 Voltage regulation The motor will operate satisfactorily under the following conditions...

Page 6: ...ion normal or light loading clean air 100 F maximum ambient temperature Severe conditions Continuous 24 hour operation shock loading or vibration poor ventilation 100 150 F ambient temperature Extreme...

Page 7: ...ent items Specify pump serial or catalog number when ordering parts 3 Reassembly is the reverse of disassembly 4 Observe the following when reassembling the liquid end All mechanical seal components m...

Page 8: ...8...

Page 9: ...9...

Page 10: ...10...

Page 11: ...Grundfos companies U S A Grundfos CBS Inc 902 Koomey Road Brookshire TX 77423 USA Phone 281 994 2700 Toll Free 1 800 955 5847 Fax 1 800 945 4777...

Page 12: ...ing ahead makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S D...

Reviews: