3.2 Mechanical installation
3.2.1 Tank inlets
We recommend that you connect the inlet pipes to
the top inlets of the tank. This prevents backflow and
deposits in the inlet pipe, and enables a high start
level of the pump. A high start level increases the
effective tank volume and reduces the number of
start/stops of the pumps.
3.2.2 Location
Install the lifting station in a properly lit and vented
room with 60 cm free space around all parts to be
serviced and operated.
The tank must not be exposed to direct sunlight. UV
light can affect the properties of its composite
material, resulting in a shorter life.
The product is designed for indoor operation. If
installed outside, the lifting station must be placed in
a closed pit.
The tank can be flooded and may be installed in a
basement with risk of penetrating groundwater.
Fig. 1
Installation example with a tank in a sump and with a controller. The diaphragm pump is not
shown.
Fig. 2
Installation example with a tank on the basement floor. The diaphragm pump is not shown.
T
M
06
57
89
02
16
Pos.
Designation
1
Isolating valve, inlet
2
Controller
3
Drainage pump
4
Non-return valve,
outlet
5
Isolating valve, outlet
6
Vent pipe
7
Backflow loop
TM
06
57
90
02
16
Pos.
Designation
1
Isolating valve, inlet
3
Drainage pump
4
Non-return valve,
outlet
5
Isolating valve, outlet
6
Vent pipe
7
Backflow loop
6
2
3
4
5
1
7
1
6
3
4
5
7
Summary of Contents for DUOLIFT APB Series
Page 1: ...UNOLIFT DUOLIFT Installation and operating instructions GRUNDFOS INSTRUCTIONS...
Page 11: ...English GB 11 TM05 9633 3913 TM05 9632 3913 Fig 13 Unilift AP35B AP50B Fig 14 SEG x4...
Page 22: ...Appendix 22 Appendix 1 Fig 1 Unolift 270 Duolift 270 TM06 1067 1514...