7.1.1 Setting the start levels with a controller
LC 220
Select a start level, either "LOW" or "HIGH", via the
DIP switches. The stop and alarm levels are set
automatically according to the selected start level.
See the installation and operating instructions of the
controller for more information about the DIP
switches.
You can change the values corresponding to "LOW"
and "HIGH" via PC Tool, which is available as an
accessory. Product number: 96705378.
LC 221
Go go [Setup], [L_01] and select one of the following
start levels. The stop and alarm levels are set
automatically according to the selected start level.
7.1.2 Setting the start levels with float switches
Set the start and stop levels by adjusting the free
cable length (L).
Fig. 25
Example of start and stop levels for
Unilift CC
We recommend start and stop levels corresponding
to a cable length between the minimum and
maximum values indicated below.
LOW
HIGH
Start level
[mm]
180
500
Stop level
[mm]
100
100
Alarm level
[mm]
350
600
1
2
3
4
5
Start level
[mm]
180
250
350
450
500
Stop level
[mm]
100
100
100
100
100
Alarm level
[mm]
350
400
550
600
600
TM
03
08
29
05
05
Start
Stop
L
Unilift KP
Cable length (L)
70 mm
(minimum)
150 mm
(maximum)
Start
Stop
Start
Stop
Unilift KP
150
290
140
335
100
Unilift KP
250
Unilift KP
350
300
150
345
110
Unilift CC
Cable length (L)
100 mm
(minimum)
200 mm
(maximum)
Start
Stop
Start
Stop
Unilift CC 5
350
115
400
55
Unilift CC 7
Unilift CC 9
350
150
435
90
Unilift
APB
Cable length (L)
100 mm
(minimum)
400 mm
(maximum)
Start
Stop
Start
Stop
Unilift
AP35/50B
430
320
460
140