Grundfos Dosing monitor Installation And Operating Instructions Manual Download Page 4

4

CONTENTS

Page

1.

Technical data

4

2.

General description

4

2.1

Definitions 5

2.2

Logic 5

2.3

Operation with vent valve

5

3.

Mounting and setting of dosing monitor

6

1. Technical data

Maximum pressure:

10 bar.

Maximum liquid temperature:

35°C.

Maximum liquid viscosity:

20 mPas.

Pulse transmitter 
(reed contact), maximum load: 48 VAC/VDC, 0.5 A.

Materials in contact with 
the pumped liquid:

PMMA/PVC/
PVDF/FKM.

2. General description

Fig. 1 

The dosing monitor is designed to monitor the dosing 
of liquids which may cause gas accumulation in the 
dosing head, thus stopping the dosing process even 
if the pump is still operating.

For every measured dosing stroke, the dosing moni-
tor gives a pulse signal to the level input so that the 
pump can compare performed dosing strokes (from 
internal stroke sensor) with externally measured 
physical strokes (from the dosing monitor). If an ex-
ternal dosing stroke is not measured together with 
the internal dosing stroke, this is considered a fault 
that may have been provoked by empty tank or gas 
in the dosing head. 

When used together with a 

DME pump

, the monitor 

will only operate if it is mounted on the suction side 
of the pump.

When used together with a 

DMS pump

, the monitor 

will operate if it is mounted on the suction or dis-
charge side of the pump.

The dosing monitor should be connected to the "low 
level" input (pins 2 and 3). This input must be config-
ured for dosing monitoring. Consequently, it cannot 
be used as a level input. 

Once the input has been set to dosing monitoring 
and a dosing monitor has been connected and set, 
the dosing monitoring function will be active.

Note:

 Make sure that the rubber gaskets supplied 

with the monitor are fitted as indicated by a * in fig. 1.

Before beginning installation procedures, 
these installation and operating instruc-
tions should be studied carefully. The in-
stallation and operation should also be in 
accordance with local regulations and ac-
cepted codes of good practice.

T

M

02

 20

29

 32

01

 / T

M

02

 20

30

 32

01

 / T

M

02

 2

0

3

1

 32

01

Dosing stroke 
measured

Dosing stroke 
measured

Dosing stroke 
measured

Monitor mounted on 
pump suction side 
(DME and DMS)

Monitor mounted on
pump discharge side
(DMS only)

Monitor mounted in dosing 
tube 
DMS: In dosing tube
DME and DMS: In suction tube

*

*

*

*