7.3 Alarm and warning codes
Code
Description
Origin
Cause
Remedy
1
Leakage current
CUE
Leakage current detected
Check CUE local HMI for fault description.
2
Missing phase
MP
204/CUE
Phase disconnected
Check pre-fuses and circuit breakers.
3
External fault
MP 204/IO
351/IO
113/CUE
Fault in external module
Check all external modules connected via GENIbus.
4
Too many pump auto-
restarts per 24 h
MP 204
Overcurrent
Check pump, valves and pipes for blockages.
6
Mains supply fault
MP
204/CUE
Phase missing or drifted
Check voltages between phases, pre-fuses and circuit
breakers.
9
Motor-phase sequence
reversal
MP 204
Phases interchanged
Check phase sequence.
10
Pump (power line)
communication fault
IO 113
Communication to SM 113 Check cables between IO 113 and SM 113.
11
Water-in-oil content too
high
IO 113
Water-in-oil compartment
Water-in-oil content has passed threshold. Lower shaft-
seal and oil needs replacement.
12
Motor operating-time
service interval limit
exceeded
CU 362
Service interval
User-defined service interval has been reached.
Arrange for preventive maintenance.
15
SCADA callback fault
CU 362
SCADA failed to respond
Check cellular network connection. Check if SCADA
phone number is correct. Check status of external
SCADA system.
16
Other fault
CUE
Fault reported by CUE
Check fault locally on CUE drive.
17
Capacity too low
(Performance
requirements not met)
Dosing
pump
Dosing volume not met
Check status of dosing pump. Perform calibration
of dosing pump.
18
Motor protector
commanded (test) trip
MP 204
Test trip activated
Test trip activated on MP 204.
19
Diaphragm break - dosing
pump
Dosing
pump
Diaphragm break detected Replace diaphragm in dosing pump.
20
Motor insulation resistance
low
IO 113/MP
204
Insulation resistance
too low
Check setting. Motor may need replacement.
21
Motor max. starts per hour
limit exceeded
CU 362
Max. starts exceeded
User setting of max. number of starts exceeded.
Evaluate setting. Evaluate stop and start levels to
increase pump runtime.
22
Motor moisture switch
IO 113
Moisture switch activated
Moisture or water detected inside motor. Overhaul of
pump or motor is needed.
24
Motor/pump vibration high IO 113
Vibration threshold
exceeded
Check pump, valves and pipes for blockages. Pump
may need overhaul.
25
Setup conflict
IO 113
Setup conflict in IO 113
Check settings of DIP switches of IO 113. Check
warning and alarm threshold in IO 113 by using PC Tool
Water Utility.
26
Load continues despite
motor relay is off
MP 204
Current drawn when it
should not be
Check motor relay (possibility of contact welding).
27
Motor protector activated
via DI
CU 362
Motor protection tripped
Check possible causes for tripping. Check pump,
valves and pipes for blockages.
30
Change bearings (specific
service information)
CUE
Change bearings reported
by CUE
Check local alarms and instructions on CUE.
32
Motor high voltage
MP
204/CUE
Voltage too high
Voltage on one or multiple phases is too high. Check
incoming voltage.
33
Soon time for service
Dosing
pump
Service interval is close
User-defined service interval is close. Arrange for
preventive maintenance on dosing pump.
35
Gas in pump head,
deaerating problem
Dosing
pump
Gas in pump head
Check the installation and operating instructions of
the dosing pump for remedy.
36
Pressure valve leakage
Dosing
Pump
Pressure valve leakage
Check the installation and operating instructions of
the dosing pump for remedy.
37
Suction valve leakage
Dosing
pump
Suction valve leakage
Check the installation and operating instructions of
the dosing pump for remedy.
38
Venting valve defect
Dosing
pump
Venting valve defect
Check the installation and operating instructions of
the dosing pump for remedy.
18