5.7.1 Analog inputs
This display shows the status of the individual analog inputs.
Example
Analog input AI1 (CU 362) [51]:
The AI1 analog input on the CU 362 (designated terminal 51) is set
up as a current input.
The measured value of 14.9 mA corresponds to a level and a
pressure of 3.40 m.
Path:
Status > Electrical overview > Analog inputs
1-10-1_ANALOG_INPUTS_053
Analog inputs
If an ultrasonic sensor is used, this display only shows the
"raw" value without offset and not inverted.
5.7.2 Digital inputs
This display shows the status of the individual digital inputs.
Example
Digital input DI2 (IO351B-41) [12]:
Path:
Status > Electrical overview > Digital inputs
1-10-2_DIGIT
AL_INPUTS_054
Digital inputs
5.7.3 Analog outputs
This display shows the status of the individual analog outputs.
Example
Analog output AO1 (IO351B-41) [18]:
The AO1 analog output on IO 351B (designated terminal 18) is
linked to the function "VFD frequency, pump 1", and the analog
output signal is 10.0 V equal to 50.0 Hz.
Path:
Status > Electrical overview > Analog outputs
1-10-3_ANALOG_OUTPUTS_142
Analog outputs
5.7.4 Digital outputs
This display shows the status of the individual digital outputs.
Example
Digital output DO1 (CU 362) [71]:
The DO1 digital output on the CU 362 (designated terminal 71) is
linked to the function "High-level alarm", and the relay is active.
Path:
Status > Electrical overview > Digital outputs
1-10-4_DIGIT
AL_OUTPUTS_055
Digital outputs
Related information