8.1.8
Digital inputs
Available inputs depending on the functional module fitted in the
pump:
To set up a digital input, make the settings below.
Function
Select one of these functions:
•
Not active
When set to "
Not active
", the input has no function.
•
External stop
When the input is deactivated (open circuit), the pump will
stop.
•
Min.
(min. speed)
When the input is activated, the pump will run at the set min.
speed.
•
Max.
(max. speed)
When the input is activated, the pump will run at the set max.
speed.
•
External fault
When the input is activated, a timer will be started. If the input
is activated for more than 5 seconds, the pump will be stopped
and a fault will be indicated.
•
Alarm resetting
When the input is activated, a possible fault indication will be
reset.
The priority of the selected functions in relation to each other
appears from section .
A stop command will always have the highest priority.
8.1.9
Digital inputs/outputs
Available inputs/outputs depending on the functional module
fitted in the pump:
To set up a digital input/output, make the settings below.
Mode
The digital input/output 3 and 4 can be set to act as digital input
or digital output:
•
Digital input
•
Digital output
.
Function
The digital input/output 3 and 4 can be set to these functions:
Possible functions, digital input/output 3
Possible functions, digital input/output 4
Function (terminal)
FM 300
(advanced)
Digital input 1, setup
(2 and 6)
●
Digital input 2, setup
(1 and 9)
●
Function (terminal)
FM 300
(advanced)
Digital input/output 3, setup
(10 and 16)
●
Digital input/output 4, setup
(11 and 18)
●
Function if input
Function if output
•
Not active
•
External stop
•
Min.
•
Max.
•
External fault
•
Alarm resetting
•
Not active
•
Ready
•
Alarm
•
Operation
•
Pump running
•
Warning
Function if input
Function if output
•
Not active
•
External stop
•
Min.
•
Max.
•
External fault
•
Alarm resetting
•
Not active
•
Ready
•
Alarm
•
Operation
•
Pump running
•
Warning