10.3.7 Settings for switching point SP 1
•
Display and set switching point SP 1.
Fig. 15
Setting switching point 1
Setting control direction for switching point 1
•
Select code function 1:
– OFF: The relay is activated when the actual
value exceeds the setpoint.
– ON: The relay is activated when the actual
value falls below the setpoint.
Setting dosing time monitoring for switching
point 1
•
Select code function 3:
– OFF: Alarm when maximum dosing time is
overrun.
– ON: No alarm when maximum dosing time is
overrun.
Selecting proportional action control for
switching point 1
•
Select code function 6:
– OFF: Switching point 1 with integral action
control.
– ON: Switching point 1 without integral action
control.
Selecting integral action control for switching
point 1
•
Select code function 8:
– OFF: Switching point 1 with integral action
control.
– ON: Switching point 1 without integral action
control.
Selecting differential action control for switching
point 1
•
Select code function 10:
– OFF: Switching point 1 with differential action
control.
– ON: Switching point 1 without differential action
control.
Displaying and setting pulse frequency for
switching point 1
Range of adjustment: 0.1 (correlates with 10 pulses/
hour) to 72 (correlates with 7,200 pulses/hour).
Fig. 16
Setting setpoint for switching point 1
10.3.8 Settings for switching point 2
•
Display and set switching point 2.
Fig. 17
Setting switching point 2
Setting control direction for switching point 2
•
Select code function 2:
– OFF: The relay is activated when the actual
value falls below the setpoint.
– ON: The relay is activated when the actual
value exceeds the setpoint.
Setting dosing time monitoring for switching
point 2
•
Select code function 4:
– OFF: Alarm when maximum dosing time is
runover.
– ON: No alarm when maximum dosing time is
runover.
TM
0
3
7
071
1
213
31.0
%
-
+
XX.X
%
Current setpoint
Set setpoint.
Setpoint is saved.
Note
If 0 is set as the pulse frequency, the
device operates as an interpulse
controller.
T
M
03
70
72
12
13
TM
03 707
3 121
3
03
-
+
XX
n+1
31.0
%
Set setpoint.
Setpoint is saved.
Current setpoint
-
+
18.0
%
XX.X
%
Current
setpoint
Set setpoint.
Setpoint is saved.