7.4 RS-485 interface
7.5 Dimensions
Fig. 2
Control panel enclosure Conex DIS-2Q
Fig. 3
Conex DIS-2Q in wall mounting housing
8. Installation
8.1 Transport and storage
•
Transport the device carefully.
•
Do not drop the device!
•
Store at a dry and cool location.
8.2 Unpacking
1. Check the device for damage.
2. Install the device as soon as possible after
unpacking.
3. Do not install or connect damaged devices!
8.3 Installation requirements
•
Dry room
•
room temperature: 0-50 °C
•
vibration-free location.
8.4 Installation in control panel
Fig. 4
Control panel enclosure Conex DIS-2Q
1. Make an opening 92 + 0.8 mm x 92 + 0.8 mm in
the control panel.
2. Slip on the supplied gasket.
3. Insert the Conex DIS-2Q into the opening from
the front.
1. Hook the clamps into the tightening cones on the
sides at the top and bottom.
2. Secure the device from the rear using a
screwdriver.
Data transfer rate
9,600 baud
Data format
• 8 bits
• 1 start bit
• 1 stop bit
• no parity.
Maximum cable
length
2-wire cable up to 1,200 m
Note
.
TM
03
70
56
12
13
TM
03
70
55
12
13
96
138
96
198
212,5
163
Note
Retain packing material or dispose of it
according to local regulations.
Caution
If you do not observe the installation
requirements, the device may be
damaged! The measurements may not
be correct!
TM
03
7
057
12
13
Caution
Do not damage the gasket!
The gasket must be fitted exactly!
92
+0.8
92
+0.8
> 10.5
> 30.5