background image

English (GB)

6

8. Motor protection

The booster module must be connected to an effective 
motor-protective circuit breaker which must protect the motor 
against damage from voltage drop, phase failure, overload and a 
locked rotor.
In power supply systems where undervoltage and variations in 
phase symmetry may occur, a phase failure relay should also be 
fitted. See section 

15. Checking of motor and cable

The control circuit must always be made in such a way that all 
modules are stopped if one module fails.

8.1 Setting of motor-protective circuit breaker

For cold motors, the tripping time for the motor-protective circuit 
breaker must be less than 10 seconds (Class 10) at 5 times the 
rated full-load current (I

1/1

/I

SFA

) of the module. See the module 

nameplate. 

In order to ensure the optimum protection of the submersible 
motor, the motor-protective circuit breaker should be set in 
accordance with the following guidelines: 
1. Set the motor-protective circuit breaker to the rated full-load 

current (I

1/1

/I

SFA

) of the module. 

2. Start the module, and let it run for half an hour at normal 

performance. See section 

9. Before starting the booster 

module(s)

3. Slowly grade down the scale indicator until the motor trip point 

is reached. 

4. Increase the overload setting by 5 %. 
The highest permissible setting is the rated full-load current (I

1/1

/

I

SFA

) of the module. 

For modules wound for star-delta starting, the motor-protective 
circuit breaker should be set as described above, but the 
maximum setting should be as follows: 
Motor-protective circuit breaker setting = rated full-load current x 
0.58. 
The highest permissible startup time for star-delta starting is 2 
seconds. 

9. Before starting the booster module(s)

The booster module(s) must be filled with water before startup.
Procedure:
1. Slacken the vent valve of the booster module, if any. 
2. Ensure an inlet pressure on the booster module.
3. Completely open the isolating valve.
4. Wait 3 to 5 minutes to ensure optimum venting.
5. Tighten and clean the vent valve.

Checking the direction of rotation

Procedure: 
1. Close the isolating valve on the discharge side of module 1 

(figures 

6

 to 

9

) to approx. 1/3 of maximum flow. 

2. Start module 1, and record discharge pressure and flow 

readings. 

3. Stop the module, and interchange two of the phases to the 

module. 

4. Restart the module, and re-record discharge pressure and 

flow readings. 

5. Stop the module. 
6. Compare the results taken under points 2 and 4. The 

connection which gave the larger pressure and flow is the 
correct direction of rotation. 

The check of the direction of rotation should last for the shortest 
possible time. 

If the booster system has several modules, starting and rotation 
checks must be made in the order 1-2-3-4 until all modules are 
running. When module 2 is checked, module 1 must be running. 
When module 3 is checked, modules 1 and 2 must be running, 
etc. 
If modules in series are also connected in parallel (fig

8

), the 

direction of rotation of each section connected in series should be 
checked. 
After having checked the direction of rotation, stop the modules in 
the order 4-3-2-1. 
The booster system is now ready for operation. 

10. Operation

Start

The booster modules must be started in the order 1-2-3-4 at 
intervals of 1 to 2 seconds. See section 

5.1 Booster modules 

connected in series and in parallel

. If other intervals are required, 

contact Grundfos.
Module 1 is always the first module on the suction side. During 
startup, we recommend to close the isolating valve 3/4 and open 
it slowly (2 to 3 seconds).
In systems involving the risk of water hammer in connection with 
start/stop, the necessary measures must be taken to minimise 
this risk, e.g. by installing a diaphragm tank.

Operation

During operation, the inlet pressure must be checked in 
accordance with section 

10.1 Limitations to operation

The total discharge pressure and flow of modules connected in 
series should never be changed by stopping one or more of the 
modules. If other pressures or flows are required, the following 
procedures are applicable:
• Bypass of module(s): Install a bypass between two modules. 

See fig. 

9

.

Stop the module(s) which is/are not required, and close the 
isolating valves on either side of the module. See section 

10.1.2 Flushing of the booster module

The module(s) to be bypassed is/are always the last 
module(s) in the flow direction.

• Fit a reducing valve to the discharge pipe.

The values stated in section 

10.1 Limitations to operation

 must 

be observed.

• Modules with three-phase motors: Install a frequency 

converter for speed control of the last booster module in the 
flow direction. See section 

7.1 Frequency converter operation

.

Stop

The modules must be stopped in reverse order, i.e. 4-3-2-1, at 
intervals of 1 to 2 seconds. See section 

5.1 Booster modules 

connected in series and in parallel

If the booster system is taken out of operation for a long period, 
the modules should be flushed through with clean freshwater. 
See section 

10.1.2 Flushing of the booster module

. The modules 

are then left with freshwater until they are to be used again.

Note

If this requirement is not met, the motor warranty will 
be invalidated. 

Warning 
The booster modules are not allowed to run against a 
closed discharge valve for more than 5 seconds as 
this will cause an increase in temperature/formation 
of steam in the module which may cause damage to 
the pump and motor.
If there is any risk of the modules running against a 
closed discharge valve, a minimum liquid flow 
through the module should be ensured by connecting 
a bypass or a drain to the discharge side of the 
module. The drain can for instance be connected to a 
tank. 

Summary of Contents for BM 125

Page 1: ...BM BMhp Installation and operating instructions GRUNDFOS INSTRUCTIONS ...

Page 2: ...s to be stored it must be stored on a frost free location or it must be ensured that the motor liquid is frost proof 1 Symbols used in this document 2 2 General description 2 2 1 Pumped liquids 2 2 2 Sound pressure level 2 3 Delivery transportation and storage 2 3 1 Frost protection 2 4 Preparation 3 5 Installation 3 5 1 Booster modules connected in series and in parallel 4 6 Pipe connection 4 7 E...

Page 3: ...allation Grundfos booster modules are as standard supplied without a built in non return valve However a non return valve can be built in on request See fig 7 In systems involving the risk of water hammer in connection with start stop the necessary measures must be taken to minimise this risk The booster modules are suitable for both vertical and horizontal installation however the discharge port ...

Page 4: ...pass mounted above each other 6 Pipe connection The booster modules are fitted with clamp liners for Victaulic PJE clamp couplings on the suction and discharge sides See fig 10 Fig 10 Pipe connection using clamp couplings TM00 3760 1902 TM00 3761 1902 Air escape valve Closing valve Non return valve Pressure switch Flow switch Motor operated valve Diaphragm tank Pressure gauge Air escape valve Isol...

Page 5: ...y the speed to such a level that the necessary flow of cooling liquid past the motor is no longer ensured The permissible frequency ranges are 30 50 Hz and 30 60 Hz respectively During start the maximum acceleration time from 0 to 30 Hz is 3 seconds During stop the maximum deceleration time from 30 to 0 Hz is 3 seconds Depending on the frequency converter type it may expose the motor to detrimenta...

Page 6: ... 1 2 3 4 until all modules are running When module 2 is checked module 1 must be running When module 3 is checked modules 1 and 2 must be running etc If modules in series are also connected in parallel fig 8 the direction of rotation of each section connected in series should be checked After having checked the direction of rotation stop the modules in the order 4 3 2 1 The booster system is now r...

Page 7: ...nce with the estimated inlet pressure At a pressure lower than 0 5 bar for BM 4 and BM BMhp 6 and 1 bar for BM BMhp 8 an alarm is given and the module must be stopped without delay All discharge connections to the system should be fitted with a flow switch which will stop the system at the set minimum flows The above monitoring devices ensure a correct inlet pressure and a minimum flow of cooling ...

Page 8: ...rt circuited not cutting in Replace the coil Check the coil voltage d The control circuit has cut out or is defective Check the control circuit and the contacts in the monitoring devices pressure switch flow switch etc e The motor supply cable is defective Check motor and cable See also section 15 Checking of motor and cable 3 The booster system runs but gives no water or develops no pressure a No...

Page 9: ...ue and multiply by 100 The result is the current unbalance in For three phase motors the current unbalance must not exceed 5 If so or if the current exceeds the maximum operating current there are the following possible faults The contacts of the motor protective circuit breaker are burnt Replace the contacts Poor connection in leads possibly in terminal box Too high or too low supply voltage See ...

Page 10: ...endix 1 LOG BOOK for BM BMhp booster modules Product No Installation date Company your ref Country Type Start of operation City VFD Softstart Brand Date Amb temp Liquid temp Flow pressure Current A Voltage V Comments ...

Page 11: ...Appendix 11 System sketch ...

Page 12: ... tanács alábbi előírásainak IT Dichiarazione di conformità CE Grundfos dichiara sotto la sua esclusiva responsabilità che i prodotti BM e BMhp ai quali si riferisce questa dichiarazione sono conformi alle seguenti direttive del Consiglio riguardanti il riavvicinamento delle legislazioni degli Stati membri CE LT EB atitikties deklaracija Mes Grundfos su visa atsakomybe pareiškiame kad gaminiai BM i...

Page 13: ...nly to water pumps marked with the minimum efficiency index MEI See pump nameplate This EC declaration of conformity is only valid when published as part of the Grundfos installation and operating instructions publication number 150095 1116 Bjerringbro 9th November 2016 Carsten Høybye Pedersen Senior Manager Grundfos Holding A S Poul Due Jensens Vej 7 8850 Bjerringbro Denmark Person authorised to ...

Page 14: ...ɩɥɭɚɬɚɰɢɢ ˀ ˋ 1 ˀ ˋ 2 ʿ ˀ ʧ ʿ ˋ 3 ˁ ʻ BM BMh ˀ ˁ 004 2011 ʽ ˀ ˁ 010 2011 ʽ ˀ ˁ 020 2011 ˑ KAZ BM BMh ɉɚɣɞɚɥɚɧɭ ɛɨɣɵɧɲɚ ɧԝɫԕɚɭɥɵԕ ʤ ಢ ಱ ದ ದ ದಱ ಱ 1 ʿ ಱ ದ ದ 2 ʧ ಪ ದ ದಱ ౢಱ ಱ ದ ದ ౢಱ ಪ ದ ಪ 3 ಪ ದ ದ ದ ಢ ಢ ದ ˁ ದ BM BMh ಢ ದ ಪ ದ ˀ ˁ 004 2011 ʺ ದ ದ ˀ ˁ 010 2011 ದ ಪ ˀ ˁ 020 2011 ʶ ʽ ಢ ಪ ದ ಪ ...

Page 15: ...ʇɸɺʏʗʅʋɸʍ ʈɼʓʍɸʗʆ ʖɼʉɸɻʗʕɸʅ Ɍʗʏʙʍɻʝʏʔ Ɋʍʘɼʛ ʚɸʔʖɸʀʉʀʂ ʕɼʗʒʏʙʋ ʍʎʕɸʅ ʇʉʏʙʋʏʕ ɝɸʔ 3 ʖɼʉɼʆʏʙʀʌʏʙʍ ɸʗʖɸɻʗʋɸʍ ɸʋʔɸʀʕʂ ʕɼʗɸɹɼʗʌɸʃɵ ʍʎʕɸʅ ʔɸʗʛɸʕʏʗʋɸʍ ʑʂʖɸʆʂ ʕʗɸ ɨɼʉɼʆʏʙʀʌʏʙʍʍɼʗ ʇɸʕɸʔʖɸɺʗʋɸʍ ʋɸʔʂʍɵ BM BMh ʖʂʑʂ ʑʏʋʑɼʗɿ ʔɼʗʖʂʝʂʆɸʘʕɸʅ ɼʍ ʇɸʋɸʈɸʌʍ ɝɸʛʔɸʌʂʍ ɝʂʏʙʀʌɸʍ ʖɼʄʍʂʆɸʆɸʍ ʆɸʍʏʍɸʆɸʗɺʂ ʑɸʇɸʍʒʍɼʗʂɵ ǺǸ Ǻǹ 004 2011 ɪɸʅʗɸʕʏʃʖ ʔɸʗʛɸʕʏʗʏʙʋʍɼʗʂ ʕɼʗɸɹɼʗʌɸʃ ǺǸ Ǻǹ 010 2011 ɝɼʛɼʍɸʍɼʗʂ ʞ ʔɸʗʛɸʕʏʗʏʙʋʍɼʗʂ ɸʍʕʖɸʍɺʏʙʀʌɸʍ ʕ...

Page 16: ...16 ...

Page 17: ...ea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tālr 371 714 9640 7 149 641 Fakss 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilnius Tel 370 52 395 430 Fax 370 52 395 431 Malaysia GRUNDFOS Pumps Sdn Bhd 7 Jalan Peguam U1 25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone 60 3 55...

Page 18: ...7085 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S www grundfos com ...

Reviews: