7
English (US)
4. Starting up the product
4.1 LED diagnostics
Fig. 4
The indicator lights located on the control plate
4.2 DIP switch settings
TM
06
55
84
49
15
UPZCP-6 6 Pump Zone Rela
y
Part Number:
98863566
Input:
120VAC 50/60Hz 20A MAX
CAUTION,
RISK OF ELECTRICAL SHOCK -
DISCONNECT POWER PRIOR TO SERVICING
ATTENTION,
RISQUE DE CHOC ÉLÉCTRIQUE -
DÉCONNECTEZ LA PUISSANCE AVANT D’ENTRETENIR
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
Certified to CSA C22.2 No 24
Conforms to UL Standard 873
Listed
The power indicator light "Grundfos" is lit
when you power the unit on.
The red LED is lit
when there is a call
for heat.
Caution
CAUTION
Disconnect the power supply before
changing any DIP switch settings.
T
M
06
55
85
05
16
Master/Slave
Allows expansion to additional Grundfos UPZC
units.
Priority ON
Zone 1 operates as priority and the other
zones are switched off for a selectable 30- or
60-minute timeout.
Post purge ON
The boiler pump will continue to run for two
minutes after priority ends to remove residual
heat from the boiler.
Pump Exercise ON
Pumps will operate for 30 seconds every 72
hours or every 14 days.
Primary pump ON
During the PRIORITY demand, select whether
the PRIMARY PUMP is ON or OFF.
OFF
Post Purge ON
OFF
Primary ON
OFF
Priority 30 min.
Priority ON
60 minutes
Pump Exercise ON
OFF
Exercise 30 sec./72 hrs.
30 sec./14 days
Master
Slave