4. Starting up the product
4.1 Before startup
Do not start the pump until the system has been filled with liquid
and vented. Make sure that the required minimum inlet pressure
is available at the pump inlet. See section
4.2 First startup
After installing the product, turn on the power supply. The light in
the operating panel shows that the power supply has been
switched on. See fig.
.
Factory setting
The pump is factory set to radiator mode with AUTO
ADAPT
.
Fig. 6
Starting up the pump
4.2.1 Dry-running protection
The dry-running protection protects the pump against dry running
during startup and normal operation. See section
During first startup and in case of dry-run, the pump will show a
warning. See section
4.3 Venting the pump
Fig. 7
Venting the pump
Small air pockets trapped inside the pump may cause noise when
starting up the pump. However, because the pump is self-venting
through the system, the noise ceases over a period of time. Still,
we recommend venting the pump in new installations or when the
pipes have been emptied and refilled with water.
Venting the pump at the first startup
When the pump is connected to Grundfos GO Remote, the app
takes you through a setup wizard. See section
.
When the setup is completed, a "Pump venting" dialogue box
appears after approximately two seconds, which guides you
through the pump venting process.
The venting process lasts 30 minutes.
Venting the pump via the "Assist" menu
You access the "Pump venting" menu in the "Assist" menu. Do as
follows:
1. Connect the pump to Grundfos GO Remote. See section
7.2 Connecting the pump to Grundfos GO Remote
2. Go to the "Assist" menu and choose "Pump venting". Follow
the instructions given in Grundfos GO Remote. The venting
process lasts 30 minutes.
Fig. 8
Operating panel during venting process
TM
07 1
1
26
02
18
T
M
0
7
11
9
2
11
1
8
30 min
T
M
07
12
10
1
11
8
The pump automatically returns to its initial settings
after venting.
The pump must not run dry.
You cannot vent the system through the pump.
ALPHA3