9. Fault finding the product

9.1 Fault indication on the pump operating panel

Faults preventing the pump from operating properly are indicated 
on the operating panel with either a yellow or red LED. A warning 
is indicated with yellow and the LED is permanently on. An alarm 
is indicated with red and the LED flashes.
For more information about alarms and warnings, see section 

9.5 Fault finding tables

.

Fig. 36

Warning and alarm indication on the operating panel

9.2 Resetting an alarm or warning

When the pump experiences a fault, use Grundfos GO Remote to 
read out alarm codes and texts. Do as follows:
1. Connect the pump to Grundfos GO Remote, see section 

7.2 Connecting the pump to Grundfos GO Remote

. Grundfos 

Eye in the top center of the "Dashboard" menu will be either 
yellow or red, indicating either a warning or alarm.

2. Tap Grundfos Eye or choose the "Alarms and warnings" menu 

in the list.

3. The menu shows an error code and a short description of the 

error.

4. Correct the fault.
5. Tap the "Reset alarm" button.

9.3 Alarm and warning code logs

Grundfos GO Remote will save up to 40 alarms and warnings in 
total in the "Alarms and warnings" menu.

9.4 Automatic deblocking

In case of a blocked rotor, the pump will start vibrating 
automatically with a frequency of around 3 Hz during startup. Any 
dirt deposits that might prevent the impeller from rotating will be 
broken up swiftly, and the pump will resume normal operation.

DANGER
Electric shock

Death or serious personal injury
- Switch off the power supply before starting any 

work on the product. Make sure that the power 
supply cannot be accidentally switched on.

CAUTION
Pressurised system

Minor or moderate personal injury
- Before dismantling the pump, drain the system or 

close the isolating valves on either side of the 
pump. The pumped liquid may be scalding hot 
and under high pressure.

WARNING
Electric shock

Death or serious personal injury
- A damaged product must be repaired or replaced 

by Grundfos or a service workshop authorised by 
Grundfos.

WARNING
Hot surface

Minor or moderate personal injury
- The pump housing may be hot due to the pumped 

liquid being scalding hot. Close the isolating valves 
on both sides of the pump and wait for the pump 
housing to cool down.

T

M

0

7

 1

2

0

8

 111

8

ALPHA3

ALPHA3

Warning

Alarm

If the pump does not revert to normal duty, the fault is 
not corrected. Turning the power off and on again will 
not reset the alarm.

Recommendations on how to correct the fault can be 
found in the "Assist" menu under "Assisted fault 
advise".

Summary of Contents for 98091786

Page 1: ...ALPHA3 Model B Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Page 2: ...ng 17 7 6 Activating and deactivating Automatic night setback 17 7 7 Hydronic balancing 18 7 8 Firmware update 18 7 9 Resetting to factory settings 18 7 10 Setting the operating mode using the operati...

Page 3: ...ust be stopped If these instructions are not observed it may result in malfunction or damage to the equipment Tips and advice that make the work easier CAUTION Crushing of feet Minor or moderate perso...

Page 4: ...ings Fig 1 Mounting ALPHA3 3 2 Pump positions Always install the pump with a horizontal motor shaft within 5 Pump installed correctly in a vertical pipe See fig 2 A Pump installed correctly in a horiz...

Page 5: ...n 1 Remove the four screws TM05 5538 3812 2 Turn the pump head to the desired position You can turn the control box in steps of 90 TM05 5539 3812 3 Insert and cross tighten the screws TM05 5540 3812 C...

Page 6: ...ctric installation where an RCD is used as an additional protection this must be type A or better due to the nature of the pulsating DC leakage current The RCD must be marked with the symbol shown bel...

Page 7: ...ecause the pump is self venting through the system the noise ceases over a period of time Still we recommend venting the pump in new installations or when the pipes have been emptied and refilled with...

Page 8: ...ollowing liquids Thin clean non aggressive and non explosive liquids not containing solid particles or fibres Cooling liquids not containing mineral oil Softened water The kinematic viscosity of water...

Page 9: ...on site code 3rd and 4th figures year 5th and 6th figures week 14 Temperature class 15 Enclosure class 16 Part according to EEI 17 Crossed out wheeled bin according to EN 50419 18 Maximum system press...

Page 10: ...s in accordance with the EN 10226 1 standard Rc or Rp threads are internal threads with either tapered or cylindrical parallel threads You can screw male R threads conical into female Rc or Rp threads...

Page 11: ...Reader can be used as an extender The ALPHA Reader is the receiver and transmitter of pump real time performance data The unit uses a CR2032 lithium battery The unit is together with the Grundfos GO...

Page 12: ...at the pump operates in Underfloor mode The underfloor mode uses the AUTOADAPT function to automatically adjust the pump performance to the actual heat demand in the system The pump performance follow...

Page 13: ...tem and the actual heat demand The curve s setpoint is user defined in the Grundfos GO Remote app The setpoint can be chosen anywhere between the minimum and maximum proportional curve in intervals of...

Page 14: ...pump changes back to the curve for automatic night setback when the condition for automatic night setback is fulfilled again If there is insufficient heat in the heating system check whether automati...

Page 15: ...rts to flash blue See fig 29 A When Grundfos GO Remote is connected to the pump the symbol on the operating panel is permanently on See fig 29 B Fig 29 Operating panel when connecting the pump to Grun...

Page 16: ...Application Hydronic balancing optional In this step Grundfos GO Remote opens up the Grundfos GO Balance app from which the balancing is done If you to skip this step in the setup wizard balancing is...

Page 17: ...work week or Stop at night only The 9 to 5 work week template inserts an adjustable template for a typical work week Summer mode This setting allows you to preset the pump to stop operation in a spec...

Page 18: ...d to the pump Your smart device stays within the Bluetooth communication range Fig 33 Operating panel when updating the firmware 7 9 Resetting to factory settings The pump can be reset to its factory...

Page 19: ...Electric shock Death or serious personal injury Switch off the power supply before starting any work on the product Make sure that the power supply cannot be accidentally switched on WARNING Electric...

Page 20: ...4 Automatic deblocking In case of a blocked rotor the pump will start vibrating automatically with a frequency of around 3 Hz during startup Any dirt deposits that might prevent the impeller from rota...

Page 21: ...play is on the pump is running in forced pumping mode Check the system for defective non return valves and replace the valves if necessary Check the system for correct position of non return valves In...

Page 22: ...imum surface temperature will not exceed 125 C Liquid temperature 2 110 C Electrical data Supply voltage 1 x 230 V 10 50 60 Hz PE Insulation class F Power consumption when the pump is stopped that is...

Page 23: ...36 104 47 G 1 ALPHA3 15 80 130 130 54 54 44 44 36 104 47 G 1 ALPHA3 25 40 130 130 54 54 44 44 36 104 47 G 1 1 2 ALPHA3 25 60 130 130 54 54 44 44 36 104 47 G 1 1 2 ALPHA3 25 80 130 130 54 54 44 44 36...

Page 24: ...mm2 s 0 474 cSt The conversion between head H m and pressure p kPa has been made for water with a density of 1000 kg m3 For liquids with other densities for example hot water the outlet pressure is pr...

Page 25: ...2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 Q m h 0 5 10 15 20 W P1 60 44 72 83 93 100 3 m 1 6 m 2 4 m 3 m 1 m 2 1 m 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 Q m h 0 1 2 3 4 m H 0 10 20 3...

Page 26: ...2 8 3 0 3 2 0 5 10 15 20 25 30 35 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 0 1 2 3 4 5 6 0 10 20 30 40 50 60 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 0 0 2 0 4 0 6 0 8 1 0...

Page 27: ...3 0 3 2 3 4 3 6 0 1 2 3 4 5 6 7 8 0 10 20 30 40 50 60 70 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 3 6 0 10 20 30 40 50 0 0 0...

Page 28: ...28...

Page 29: ...53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava...

Page 30: ...splayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2019 Grundfos Holding A...

Reviews: