Page 32 of 40
15.0 De-commissioning, Dismantling and Disposal
The building will be without the Fire protection that the FireSAFE at home unit gives once
decomissioned and an alternative measure to provide protection against fire should be
considered. The owner of the building, insurer and any inhabitants must be informed of this.
15.1 De-commissioning
De-commissioning is the process of taking out of service the FireSAFE unit.
Reasons for this could be:
Replacing with another unit
Upgrading the unit
Removing the system altogether
15.2 Dismantling
Always make sure that adequate provision is made to capture any water
drained from the system and FireSAFE unit when dismantling.
Always make sure that adequate water spill protection for flooring etc is in
place before Dismantling and Draining any part of the system or FireSAFE unit.
Appropriate PPE must be worn. (including eye protection and gloves)
Ensure any outgoing signals from the FireSAFE unit are not going to cause
activation of:
Fire Alarms/Beacons
Fire Alarm control panel
Fire service response or Fire monitoring service response
Any other warning/monitoring devices installed (eg. SMS to mobile device)
Consideration should be given to contacting any response services beforehand and
informing them of the De-commissioning and Dismantling of the FireSAFE device.
Isolate the electrical supply ensuring it cannot be turned back on
Disconnect the electrical supply from the FireSafe unit
Press the Test/Reset button on the Control panel to silence the internal buzzer
Close the system Isolating valve on the suction side of the FireSAFE unit
Remove the two bolts holding the front cover in place
Lift off the front cover and disconnect the earth bonding wire to the front cover and
place the cover in safe place out of the way
NOTE
NOTE
NOTE
NOTE
Summary of Contents for 97931710
Page 22: ...www grundfos co uk Page 22 of 40...
Page 37: ...www grundfos co uk Page 37 of 40...
Page 38: ...www grundfos co uk Page 38 of 40...