Page 16 of 40
8.10 Operating Conditions
Electrical Supply: 1Ph: 230 V +6 / -10% 3Ph: 176Vac – 264 Vac
Electrical Load: see Product Range – Electrical Requirement
Pollution Degree: 3
Noise Level: <65 dB(A) at full speed
Liquid temperature range: +3°C to +60°C
Ambient temperature: From +3°C - 40°C
Relative Humidity: up to 95 % non condensing
Altitude: use up to 2 km above sea level
Usage: Indoor (Outdoor, subject to restrictions found under 8.8 – Location)
Type of protection: Class 1 (earthed) equipment
Equipment type: Stationary, fixed equipment
Construction type: Fixed construction, no moveable parts
EMC Environment: B (light industrial, commercial and residential)
Pressure switch Range: -02 to 8 bar / 4 to 12 bar / 1 to 16 bar (depending on model)
Pressure gauge Range: 0 to 10 bar / 0 to 16 bar (depending on model)
Casing pressure rating: 10 bar / 16 bar (depending on model)
Inlet pressure Max: Casting pressure minus max head of pump
Pump generated pressure: see Product Range – Pressures and Flows
9.0 Installation and Commissioning
The Firesafe unit has been designed to minimize and simplify the number of Installation and
Commission activities required to bring the system on line.
All electrical connections should be carried out by a qualified and authorised electrician
in accordance with the wiring diagram supplied within the Control panel/this manual,
the latest I.E.E. regulations and in accordance with BS9251 latest revision.
All mechanical connections should be carried out by a by a qualified and authorised
person in accordance with BS9251 latest revision and the relevant codes of practice
The FireSAFE unit must be earthed.
Do not attempt to start the pump even to check the direction of rotation until the
system has been filled with water and both the pump and the system have been
primed/vented.
Do not remove the controller enclosures, controller components, motor terminal box
cover, electrical cables or any other electrical protective covering without first ensuring
that the electrical supply is suitably isolated and cannot be switched back on.
Do not attempt to supply electricity to the controller/unit and run the pump electric
motor without ensuring that all electrical fittings, cables and enclosures are intact and
suitably electrically isolated from human touch during operation.
Do not attempt to supply electricity to the electric motor or re-pressure the pipe work
system without first ensuring that all protective coverings are held securely in their
correct positions.
Summary of Contents for 97931710
Page 22: ...www grundfos co uk Page 22 of 40...
Page 37: ...www grundfos co uk Page 37 of 40...
Page 38: ...www grundfos co uk Page 38 of 40...