3>Disconnect the wire connector of the fans with a flat head screw driver and remove the 

fans from the fan guards, it is shown as below. 

4>Clean fan, fan guards and heat sink or replace fan.

Clean the fan and fan guards with air pump, brush or a damp cloth.

Remove each fan separately for cleaning if necessary. 

Remove the fan that need to replace with a cross screwdriver, replace a new fan.

Tidy up the wire.

5>Install the fan, fan guard fixed and the inverter again.

Figure 9.1

Figure 9.2

9.2 Trouble Shooting

Work on the Growatt Max must be carried out by qualified personnel.

Normally grounded conductors may be ungrounded and energized 

when a PV isolation low is indicated

.

Risk of electric shock

DANGER

Warnings identify the current status of the inverter(Max), warnings do not related to a 

fault and it does not affect the normal running of the inverter. When a warning with a 

number after it appears in the display, it indicates a warning code and is usually cleared 

through an orderly shutdown/re-set or a self-corrective action performed by the inverter.

See the warning code in the following table;

9.2.1 Warning

Warning 

Message

Description

Suggestion

Warning 

200

String fault

1.After shutdown,Check the panel  is normal.

2.If error message still exists, contact manufacturer.

Warning 

202

DC SPD  function 

abnormal 

1.After shutdown,Check the DC SPD.

2.If error message still exists,contact manufacturer.

Warning 

203

PV Circuit short

1.Check the PV1 or PV2 wiring is short-circuited.

2.If error message still exists,contact manufacturer.

Warning 

206

AC SPD  function 

abnormal 

1.After shutdown,Check the AC SPD.

2.If error message still exists,contact manufacturer.

Warning 

207

U disk over-current 

protection

1.unplug the U disk

2.Re-access U disk after shutdown

3.If the error message still exists, contact manufacturer.

Warning 

400

Fan  function 

abnormal

1.After shutdown,Check the fan connection.

2.Replace the fan.

3. If the error message still exists, contact manufacturer.

Warning 

401

Meter abnormal

1.Check if the meter is on

2.Check the machine and the meter connection is normal

Warning 

402

Optimizer and 

inverter 

communication is 

abnormal

1. Check if the optimizer is on.

2. Check whether the connection between the optimizer 

and the inverter is normal

Warning 

404

EEPROM abnormal

1.Restart inverter.

2.If error message still exists,contact manufacturer.

Warning 

405

DSP and COM 

firmware version 

unmatch

1.Check  the firmware version.

2.If error message still exists,contact manufacturer.

Warning

408

NTCBroken

1.Restart inverter

2.If error message still exists, contact manufacturer.

If the above suggestions do not work, please contact Growatt.

Summary of Contents for MAC 15-20KTL3-XL

Page 1: ...75 A 00 SHENZHENGROWATTNEWENERGYTECHNOLOGYCO LTD No 28GuangmingRoad ShiyanStreet Bao anDistrict Shenzhen P R China T 86 755 27471942 E service ginverter com W www ginverter com Installation Operation...

Page 2: ...Description 3 1 Appearance 3 2 Size Dimensions 3 3 Nameplate 3 4 Working Principle 3 5 Inverter Storage 3 6 Grid Types 3 Product Introduction 4 Unpacking 5 Installation 5 1 Basic Installation Require...

Page 3: ...ounding 6 Electrical Connections 7 Debugging 7 1 Debug Inverter 7 2 Operating Mode 7 3 OLED Display and Touch Buttons 8 1 Remote Data Monitoring 8 2 Local Data Monitoring 9 1 Routine Maintenance 9 2 T...

Page 4: ...on Before installation please read through this manual any damage cause by improper installation Growatt reserve the right to disclaim any warranty Ensure that the MAC is not connected to a power supp...

Page 5: ...technician Burn Warning Do not touch a running inverter cause it generates high temperature on the case Protective Grounding Connect inverter to grounding bar Delay discharge Residual voltage exists...

Page 6: ...ce 3 2 Size Description Model Size unit mm Weight unit kg Width High Deep MAC series PV inverter 680 508 281 52 MAC series PV Inverter with packaging 730 650 350 60 Figure 3 1 6 5 Identification Descr...

Page 7: ...ircuit breaker F Grid 1 Do not unpack the Inverter and store it in a ventilation dry place 2 Keep the storage temperature at 25 60 and humidity at 0 95 3 A maximum of four inverters with package can b...

Page 8: ...he OLED display and maintenance work F To avoid inverter performance de rate due to the over heat please do not expose the inverter under direct sunlight G The installation humidity should be from 0 9...

Page 9: ...ury Do not place the inverter with its wiring and signal terminals at the bottom contacting with floor or any other object because the terminals are not designed to support the weight of inverter 1 2...

Page 10: ...not store inverter in area with flammable and explosive material Each inverter must install one AC breaker AC breaker is forbidden to share with other inverters It is forbidden to add load between inv...

Page 11: ...vent water ingress Notice Waterproof joints must be blocked with fireproof mud to prevent water ingress Before electrical connection please ensure the inverter DC switch is at OFF also disconnect AC s...

Page 12: ...5A 3 MAC 50KTL3 X LV 12 5A 4 12 5A 3 12 5A 3 MAC 60KTL3 X LV 12 5A 4 12 5A 4 12 5A 4 MAC 50KTL3 X MV 12 5A 4 12 5A 3 12 5A 3 MAC 50 70KTL3 X MV 12 5A 4 12 5A 4 12 5A 4 MAC 15 36KTL3 XL 12 5A 4 12 5A...

Page 13: ...Steps for installing the monitoring module Make sure is on the front side then insert the display and tighten the screws Figure 6 7 19 20 When multiple machines are connected in parallel two customers...

Page 14: ...ght Note2 3 The lightning down conductor and the equipment ground wire eventually sink at a total ground point but the two cannot share the wire That is the equipment grounding wire should be pulled s...

Page 15: ...2 Local Data Monitoring download the mobile app and log in to the monitoring interface to modify the communication address This operation is performed by a professional 1 Select Parameter Settings 2...

Page 16: ...enough power voltage 200VDC then the inverter will start automatically The intelligent control system of the inverter constantly monitors and adjusts the state of the system When the inverter detects...

Page 17: ...ed Set Date 2018 12 14 Set Time 12 30 30 Set Comaddr 1 Set Language English General Advanced Set Parameter Reset factory YES NO WideVolt Set WideVolt Set 1 2 3 Set OK The inverter is factory set to CQ...

Page 18: ...setting mode switch the language with a single touch and touch the setting twice to confirm the setting Set Language English English Chinese Set OK The default COM address is 1 continuous touch twice...

Page 19: ...inePhone Main interface 1 The center of the main interface shows the current power station name You can switch between different power stations in the account by clicking the invertedtriangle symbol 2...

Page 20: ...ve power set PF set inverter time set grid voltage high set grid voltage low The operation password is inverter date For example if the date of the day is April 18 2019 the password is inverter2019041...

Page 21: ...essary information then go back to login page input the registered username and password click login Figure 8 8 Figure 8 9 On the Plant page click on device list datalog add data logger enter the SN n...

Page 22: ...Figure 8 13 Figure 8 11 C View detailed data Click Plant device list MAX MID and the inverter list of the power station is displayed Double click on the inverter name in the list to display the detai...

Page 23: ...5678 If you have already connected you can click Skip to connect directly to the WIFI Figure 8 14 Figure 8 15 When viewing local monitoring you must keep the phone s wifi connected to the collector s...

Page 24: ...C Parameter configuration The parameter data of the equipment can be modified according to the usage D Intelligent detection Detailed and accurate view of the device s detailed data and status E Intel...

Page 25: ...me recording detection Inverter voltage and current quality can be observed in real time Figure 8 21 Figure 8 22 Figure 8 20 H One click diagnosis One button detection of power plant environment inclu...

Page 26: ...to be programming at last time Figure 8 23 Figure 8 25 Figure 8 24 Figure 8 26 2 Fault Recording Create a BCONFIG txt file under the root directory of the USB flash drive write down_fault insert the...

Page 27: ...ssible reasons or solutions Fan is blocked or the heat sink gathers too much dust it needs to clean the fan fan cover or heat sink Fan is damaged it need to replace the fan Poor ventilation of the ins...

Page 28: ...normal 2 If error message still exists contact manufacturer Warning 202 DC SPD function abnormal 1 After shutdown Check the DC SPD 2 If error message still exists contact manufacturer Warning 203 PV...

Page 29: ...ge still exisits contact Manufacturer Error 304 AC F Outrange 1 Restart inverter 2 If error message still exists contact manufacturer 9 2 2 Error Error 402 Output DC current too high 1 Restart inverte...

Page 30: ...50A 50A 50A 45A 45A 45A 45A 45A 45A 55A 55A 55A 55A 55A 55A 3 3 3 2 3 3 3 4 3 3 4 4 4 33300VA 44400VA 55500VA 66600VA 230V 400V 340 440VAC 50 60 Hz 45 55Hz 55 65 Hz 43 5A cos 1 48 3A cos 0 9 58 0A cos...

Page 31: ...APP USB YES Rs485 YES WIFI Option GPRS Option 4G Option General Data Dimensions W H D 680 508 281 mm Weight 52kg 0 99 0 8LG 0 8LD Efficiency Protection devices Interfaces Operating temperature range 2...

Page 32: ...kers Full load MPP voltage MPP voltage range Nominal voltage Start voltage Max DC voltage Max recommended PV PV power for module STC Input data Max output current AC grid frequency range Model Power f...

Page 33: ...0A 50A 55A 55A 55A 15000W 20000W 22000W 16600kVA 220VAC 22200kVA 220VAC 24400kVA 220VAC 127V 220V 101 6 139 7V 50 60 Hz 45 55Hz 55 65 Hz 39 4A 52 5A 57 7A 46 3A 58 3A 64 0A Nominal AC voltage range Ma...

Page 34: ...WIFI APP USB YES Rs485 YES WIFI Option GPRS Option 4G Option General Data Dimensions W H D 680 508 281 mm Weight 52kg 0 99 0 8LG 0 8LD Efficiency Protection devices Interfaces Operating temperature ra...

Page 35: ...tage Max DC voltage Max recommended PV PV power for module STC Input data Nominal output current AC grid frequency range Model MAC 36KTL3 XL MAC 25KTL3 XL MAC 30KTL3 XL Max output current Power factor...

Page 36: ...o OFF position 3 Wait at least 5 minutes until the internal capacitor discharge is completed 4 Disconnect the AC connector 5 Disconnect DC connector 6 Remove the inverter from the wall 7 Disposing of...

Reviews: