18.04.16
Page 19 / 146
VARMAX -
Installation, Use and Maintenance
fi
gure 4 - Peripheral clearance
4.2. Installing the boiler
VARMAX boilers must not be installed on an in
fl
ammable surface (wooden
fl
oor, plastic
fl
oor covering, etc.).
Recommended distances from walls and the
fl
oor:
Ensure there is suf
fi
cient clearance so that work may be carried out easily
on the boilers.
The
minimum
values (in mm) are indicated in
fi
gure 4 and in the table below.
A
B
C
D
H
MODELS
120
450
500
150
140
450
500
150
180
450
500
320
225
450
500
320
275
450
600
500
263
320
450
600
500
263
390
450
700
500
427
450
450
700
500
427
The hashed zone above the boiler must remain free of obstacles to
allow for inspections and cleaning of the burner.
!
WARNING:
A 2 cm free space must also be left above the side panels to allow for
their disassembly and reassembly.
These values cannot be replaced by speci
fi
c regulatory requirements.
!
WARNING:
The boiler must be positioned horizontally using a spirit level to
promote effective ventilation of the heat exchanger (use the base as
a reference surface).
To adjust the level, screw or unscrew the 4 adjustable feet as required using
a 17 mm wrench.
00BET9005-#
H
A
B
C
D