18.04.16
Page 11 / 146
VARMAX -
Installation, Use and Maintenance
2.4.
Gas supply pressures
INFORMATION:
The pressures given below must be read at the gas valve inlet.
Natural gas H G20
G31 Propane gas
(for relevant models
and countries only)
20 mbar
Nominal pressure (mbar)
20
37
Minimum pressure (mbar)
17
25
Maximum pressure (mbar)
25
45