background image

Specification: 

Pressure Ranges: ULP*1     ± 1 "wc, 0-1 "wc, ± 0.5 "wc, 0-0.5 "wc,  

                                                   ± 250 Pa, 0-250 Pa, ± 125 Pa, 0-125 Pa

 

                         ULP*2    ± 0.25 "wc, 0-0.25 "wc, ± 0.125 "wc, 0-0.125 "wc,  

                                                  ± 60 Pa, 0-60 Pa, ± 30 Pa, 0-30 Pa

Accuracy . . . . . . . . . . . . . . . .± 1% FS of selected range

Stability . . . . . . . . . . . . . . . . .± 1% FS (1 year)

Thermal Effect . . . . . . . . . . .± 2% FS max , 10 - 40 ˚C  (50 - 104 ˚F)

Response Time . . . . . . . . . .5 or 30 Seconds (switch selectable)

Proof Pressure . . . . . . . . . . .100 "wc (24.9 kPa) for ULP*1, 

                                                  40 "wc (9.96 kPa) for ULP*2

Burst Pressure . . . . . . . . . . .200 "wc (49.8 kPa) for ULP*1, 

                                                  80 "wc (19.9 kPa) for ULP*2

Operating Conditions . . . .0 - 60 ˚C (32 - 140 ˚F), 

                                                  0 - 90 %RH non-condensing

Storage Temperature . . . .-40 - 95 ˚C (-40 - 203 ˚F)

Media Compatibility . . . . .Dry air or inert gas

Zero Adjust . . . . . . . . . . . . . .Pushbutton or digital input auto-zero

Power Supply . . . . . . . . . . . .24 Vac/dc ± 10%

Power Consumption . . . . .55 mA max with relay option

Output Signal . . . . . . . . . . . .4-20 mA (3-wire), 0-5 or 0-10 Vdc (3-wire), 

                                                  field selectable

Output Drive . . . . . . . . . . . .750 Ω max (4-20 mA), 2 KΩ min (voltage)

Optional Display . . . . . . . . .3 ½ digit LCD, 0.45" digit height, 

                                                  unit symbols and backlight

Optional Alarm Relay . . . .NO contact, 2 Amps @ 120 Vac or 30 Vdc

Alarm Trip Point . . . . . . . . . .Adjustable over the pressure range 

                                                  (forward or reverse acting)

Alarm Delay . . . . . . . . . . . . .10 or 60 Seconds (switch selectable)

Wiring Connections . . . . . .Screw terminal block (14 to 22 AWG)

Pressure Connections . . . .Barbed ports for 1/8" to 3/16" ID tubing

Conduit Connection . . . . .Access hole for ½” NPT conduit or cable gland

Enclosure . . . . . . . . . . . . . . . .Grey ABS with gasket, UL94-5VB. IP65 (NEMA 4X)

 

                                         145mmW x 101mmH x 63mmD (5.7" x 4.0" x 2.5")

Weight . . . . . . . . . . . . . . . . . .260 g (9.2 oz)

PRINTED IN C

ANAD

A

V. ULP 09/15

Dimensions: 

Alarm Operation

During normal operation the device also compares the output pressure value to the alarm setpoint and takes appropriate 

action. If the pressure value exceeds the setpoint then an alarm condition is set and the device will operate in alarm mode. 

Alarm mode activation is controlled by certain device settings.
The setpoint can be set using the Alarm Setpoint control on the pcb. Moving the control clockwise changes the setpoint from 

the minimum to the maximum pressure of the selected range, either 0-MAX or –MAX to +MAX, depending on the DIP switch 

position. The LCD will show the setpoint briefly while it is being adjusted and will revert back to the normal display when 

adjustment stops. 
When the input pressure exceeds the setpoint for the delay time, then the relay contacts will close. When the input pressure 

decreases below the setpoint for the delay time then the relay contacts will open again. The alarm on/off delay time can be 

set to either LO Delay (10 seconds) or HI Delay (60 seconds) via a DIP switch. The operation described above is for the default 

Normal Alarm. A DIP switch can be set to Reverse Alarm which will cause the alarm operation to reverse. In this case the alarm 

condition will be set when the pressure falls below the setpoint, instead of above the setpoint.

Auto Zero Operation

A sensor auto zero can be initiated by pressing and holding the internal auto zero switch for at least 3 seconds. If both 

pressure ports are close to zero pressure (open to ambient), then the device will calibrate with a new zero point. The auto zero 

can also be initiated by holding the ZERO IN terminal low for 3 seconds.
Generally, it is not recommended that a span calibration be performed in the field unless a high quality calibrator with low 

differential pressure ranges is available and the temperature of the sensor can be maintained. Contact the factory for informa-

tion on this type of calibration.

Normal Operation con’t

In the case of 

 

±

 

1 "wc, 4 mA or 0 V = -1 "wc and 20 mA or 5 V or 10 V = +1 "wc. Since the transmitter is linear, 0 "wc would be 12 

mA or 2.5 V or 5 V.
During normal operation the device reads the pressure sensor and calculates the pressure value depending on the device 

model ranges and the selected pressure range. The pressure value is displayed on the LCD (if installed) and set as the value for 

the analog output.
The output signal may be affected by the pressure averaging time setting. The pressure averaging setting controls how many 

readings are averaged to form the output value. The pressure averaging value can be set to LO Avg for a 5 second average of 

the output signal or to HI Avg for a 30 second average to form the output value. This value effectively filters the output to 

prevent noise and false alarms.

114.3 mm

4.5 “ 

100 mm

3.95 “ 

Mounting Holes 

(X4)  Ø 0.200”

88.9 mm

3.5 “ 

145 mm

5.7 “ 

High Port

Low Port

1/8” Barbed for 3/16 ID tubing

63 mm

2.5 “ 

Greystone Energy Systems, Inc.  150 English Drive,   Moncton, NB  E1E 4G7  Canada  Tel: +1-506-853-3057  Tollfree (North America): +1-800-561-5611  Fax: +1-506-853-6014

Email: [email protected]    Web: www.greystoneenergy.com

Cop

yr

igh

t © Gr

ey

stone Ener

gy S

yst

ems I

nc

. A

ll R

igh

ts R

eser

ved

Summary of Contents for ULP1

Page 1: ...it Leave enough space around the unit to connect the pressure tubing and avoid locations with severe vibrations excessive moisture or rapid temperature changes It should be mounted on a vertical surface with the pressure ports on the bottom and the cable entrance on the right The enclosure has a standard conduit opening and may be installed with either conduit and a conduit coupler or a cable glan...

Page 2: ...dings may result See figure 7 The RELAY output is a normally open dry contact This signal can be used to directly control an alarm ventilation fan or may be connected to a digital input of the BAS for status monitoring Ensure any loads connected to the relay is within the relay rating in the Specification section See figure 8 The remote zero feature may be used by wiring a dry contact relay only d...

Page 3: ...less than the Low pressure For bipolar ranges the output pressure can be calculated as follows 4 20 mA Pressure Output current 4 mA 16 mA x 2 x Range Offset 0 5 Vdc Pressure Output voltage 5 V x 2 x Range Offset 0 10 Vdc Pressure Output voltage 10 V x 2 x Range Offset Wiring Instruction con t Figure 7 Wiring all output signals and 24 Vdc power from controller Wiring for all output signals and exte...

Page 4: ...e then the relay contacts will close When the input pressure decreases below the setpoint for the delay time then the relay contacts will open again The alarm on off delay time can be set to either LO Delay 10 seconds or HI Delay 60 seconds via a DIP switch The operation described above is for the default Normal Alarm A DIP switch can be set to Reverse Alarm which will cause the alarm operation to...

Reviews: