background image

      

Wiring Instruction

The transmitter has standard screw block connectors. Use shielded twisted pair wiring of at least 22 AWG for all connections 

and do not run device wires in the same conduit with wiring used to supply inductive loads such as motors. Disconnect the 

power supply before making any connections to prevent electrical shock or equipment damage. Make all connections in 

accordance with national and local electrical codes.

This is a 3-wire sourcing device. Connect the positive dc or the ac voltage hot side (24 Vac/dc ± 10%) to the POWER terminal. 

The supply common is connected to the COMMON terminal. The device is reverse voltage protected and will not operate if 

connected backwards. It has a half-wave rectified power supply so the supply common is the same as the signal common. 

Several devices may be connected to one power supply and the output signals all share the same common. Use caution when 

grounding the secondary of a transformer or when wiring multiple devices to ensure the ground point is the same on all 

devices and the controller. 

The analog output is available on the PRES OUT terminal. This signal is switch selectable for either voltage or 4-20 mA active 

output. In voltage mode the output is 0-5 or 0-10 Vdc. These options are indicated on the circuit board. The current output 

operates in the Active mode and does not require a loop power supply. This means the signal current is generated by the 

transmitter and must not be connected to a powered input or device damage will result. Check the controller Analog Input to 

determine the proper connection before applying power. Both current and voltage signals are referenced to the COMMON 

terminal. The voltage output signal has a minimum load that it is able to drive, similarly the current signal has a maximum 

load. Follow the ratings in the Specification section or inaccurate readings may result. See figure 7.

The RELAY output is a normally open dry contact. This signal can be used to directly control an alarm, ventilation fan or may 

be connected to a digital input of the BAS for status monitoring. Ensure any loads connected to the relay is within the relay 

rating in the Specification section. See figure 8.

The remote zero feature may be used by wiring a dry-contact (relay only) digital output between the ZERO IN and COMMON 

terminals. Do not apply voltage to the ZERO IN terminal. See figure 9.

Hardware Setup

The analog output type must be set before the device is connected. 

Slide the switch labelled VOLT and mA to the correct 

position for the required output signal type, either 4-20 mA or 0-5/10 Vdc. See figure 5.  Other parameters may be set on the 

DIP switches before or after the device is connected. Any DIP switch change will have an immediate effect on the operation.

DIP Switch Configuration 

(See figure 6)

Figure 6

BL OFF / BL ON

   

 

Sets the LCD backlight on or off

"WC / Pa 

 

 

Sets the pressure units to “WC or Pascals

HI Range / LO Range*

   

Sets the pressure range (See chart below)

+/- Max / 0 - Max 

 

Sets bi- or uni-directional pressure range

LO Avg / HI Avg

   

 

Sets pressure averaging to 5 or 30 seconds

10V / 5V 

 

 

Sets the voltage output scale to 0-5 or 0-10 Vdc  (N/A when mA output is selected)

LO Delay / HI Delay

 

 

Sets the alarm delay to 10 or 60 seconds (N/A if no relay is ordered) 

Normal / Reverse

 

 

Sets the alarm action (N/A if no relay is ordered) 

*The effect of different DIP switch settings on the pressure range is shown in the following table.

Pressure 

        Pressure 

 

                     ULP*1  

 

 

                  ULP*2

Units   

        Range 

 

± Max   

      0 - Max 

              ± Max 

 

   0 - Max

"WC 

 

        HI Range 

                 ± 1 "wc   

     0-1 "wc 

          ± 0.25 "wc                     0-0.25 "wc

 

 

        LO Range                   ± 0.5 "wc 

     0-0.5 "wc 

          ± 0.125 "wc                    0-0.125 "wc

Pa 

 

        HI Range 

                 ± 250 Pa                        0-250 Pa 

          ± 60 Pa 

 

 0-60 Pa

 

 

        LO Range                   ± 125 Pa                        0-125 Pa 

          ± 30 Pa 

 

 0-30 Pa

Model

mA = 4-20 mA

(Factory  Default)

 Output Type Selection Switch 

VOLT = Vdc 

Figure 5

Greystone Energy Systems, Inc.  150 English Drive,   Moncton, NB  E1E 4G7  Canada  Tel: +1-506-853-3057  Tollfree (North America): +1-800-561-5611  Fax: +1-506-853-6014

Email: [email protected]    Web: www.greystoneenergy.com

Summary of Contents for ULP1

Page 1: ...it Leave enough space around the unit to connect the pressure tubing and avoid locations with severe vibrations excessive moisture or rapid temperature changes It should be mounted on a vertical surface with the pressure ports on the bottom and the cable entrance on the right The enclosure has a standard conduit opening and may be installed with either conduit and a conduit coupler or a cable glan...

Page 2: ...dings may result See figure 7 The RELAY output is a normally open dry contact This signal can be used to directly control an alarm ventilation fan or may be connected to a digital input of the BAS for status monitoring Ensure any loads connected to the relay is within the relay rating in the Specification section See figure 8 The remote zero feature may be used by wiring a dry contact relay only d...

Page 3: ...less than the Low pressure For bipolar ranges the output pressure can be calculated as follows 4 20 mA Pressure Output current 4 mA 16 mA x 2 x Range Offset 0 5 Vdc Pressure Output voltage 5 V x 2 x Range Offset 0 10 Vdc Pressure Output voltage 10 V x 2 x Range Offset Wiring Instruction con t Figure 7 Wiring all output signals and 24 Vdc power from controller Wiring for all output signals and exte...

Page 4: ...e then the relay contacts will close When the input pressure decreases below the setpoint for the delay time then the relay contacts will open again The alarm on off delay time can be set to either LO Delay 10 seconds or HI Delay 60 seconds via a DIP switch The operation described above is for the default Normal Alarm A DIP switch can be set to Reverse Alarm which will cause the alarm operation to...

Reviews: