If the unit has the LCD option then the scale can be set to either °C 

or °F via the Scale jumper. See Figure 10. If he unit is also equipped 

with the backlight option it can be enabled or disabled via the 

Backlight jumper. The LCD display can be calibrated by adjusting 

the LCD ADJ pot.

MANUAL OVERRIDE/OCC IN 

The optional override switch output is a dry-contact and is available 

on the and SWITCH - terminals. It is typically connected 

to a low-voltage digital input on the controller to indicate room occupancy or override when the button 

is activated.

If the override switch is ordered with the optional LCD, also included is the OCC IN. The OCC IN terminal 

is a digital input that controls the OCC segment on the LCD to indicate an occupied condition. It can be 

connected to a 0-5V digital signal or a dry contact signal. This is usually an active low input signal and 

requires that the OCC IN terminal be shorted to COMMON to activate the input.

LED

The LED is typically used as indication as when manual override has been selected.  It is available on the 

LED+ and LED- terminals and requires 5 Vdc to power.  The LED option is not available when LCD installed

FAN SPEED SWITCH 

The 5 position speed fan speed has a resistance output signal on the FAN + and FAN - terminals and has 

different resistances for each position 5 positions (Auto, Off, Low, Mid, High).

EXTERNAL JACK

The external jack is internally connected to a 4-pin terminal block labeled 1, 2, 3, 4 and excepts a 4 pin 

molex connector for remote communication with the controller. The HHTA-XXX adapter converts the 4-pin 

Moles to a 4 pin phone jack connection.

Figure 9

Analog Input
COMMON

Controller

SETPNT -

Analog Input
COMMON

Controller

FAN +

FAN -

Analog Input
COMMON

Controller

SENSOR -

Digital Output (+5 Vdc)
COMMON

Controller

OCC IN

COMMON

Digital Output (+5 Vdc)
COMMON

Controller

LED +

LED -

Digital Input
COMMON

Controller

SWITCH -

Wiring for PCB

Backlight

Figure 10

On

Off

Scale

Fahrenheit

Celsius

IN-GE-TSRCXXX-01 04/20

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for TSRC Series

Page 1: ... at the top edge and must be removed from the bottom edge first Use a small Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal is not required Use a screw driver to carefully pry each bottom corner if necessary Tip the cover away from the base and sit it aside as shown in Figure 2 SENSOR ONLY Feed at least 6 inches of wire through the wall and out of the juncti...

Page 2: ...s mounted on the wall For added protection place the PCB in the supplied anti static bag Mount the base by screwing it to an electrical box or directly to the wall as shown in Figure 5 After the base is screwed to an electrical box or the wall using the appropriate holes remove the PCB from the anti static bag feed connection wires through center hole and place the top of the PCB into the PCB hold...

Page 3: ... LED The LED is typically used as indication as when manual override has been selected It is available on the LED and LED terminals and requires 5 Vdc to power The LED option is not available when LCD installed FAN SPEED SWITCH The 5 position speed fan speed has a resistance output signal on the FAN and FAN terminals and has different resistances for each position 5 positions Auto Off Low Mid High...

Page 4: ...ot as resistive output 20 to 20K Ω Custom Spans Available 1K 2K 5K 10K or 20K Ω OCCUPIED INPUT Signal Type Digital input 0 5 Vdc active low Action Causes OCC segment to light on LCD LED INPUT Signal Type Active high low or 2 wire 5 V current limit standard LED Colors Red Green or Yellow Power Supply 5 Vdc standard 10 Vdc or 24 Vdc optional LCD DISPLAY Power Supply 12 24 Vdc 24 Vac 10 Consumption 2...

Reviews: