FACTORY CONFIGURATIONS 

The device preset is as follows:

• 

Range is 0-15 Vdc

• 

R1 is set to 6 Vdc

• 

R2 is set to 12 Vdc

• 

Deadband is set to 3%

CALIBRATION AND SETUP

• 

Set the INPUT RANGE jumper to the correct position for the signal to 

be used. For example, if the input signal is 2-10 Vdc, select the 0-15 Vdc 

range.

• 

Set the deadband jumper to the desired value. This can be changed at 

any time with the power on.

• 

Connect the power supply and the input signal to the correct terminals.

• 

Turn the power on and the POWER LED will light.

• 

Apply an input signal equal to the R1 set-point.

• 

Adjust the R1 pot clockwise until the RELAY1 LED goes out, then slowly 

adjust the R1 pot counter-clockwise until the LED lights.

• 

Apply an input signal equal to the R2 set-point and adjust the R2 pot the 

same as for R1, watching the RELAY2 LED.

• 

Test the operation by increasing the input signal and watch as R1 and R2 

turn on at the selected set-points. Then decrease the signal and watch as 

the relays turn off at the selected set-points minus the deadband.

SPECIFICATIONS

POWER OUTPUT

Regulated Power Output ........20 Vdc ±10% @ 30 mA max to 

 

power an external sensor

INPUT SIGNAL

Input Voltage Range .................0 to 7.5 or 0 to 15 Vdc

Input Voltage Impedance .......>15 KΩ

Input Current Range .................0 to 20 mA

Input Current Impedance .......250 Ω

OUTPUT RELAYS

Type ................................................SPDT Form C

Contact Rating ............................10 Amps at 125 Vac

Contact Resistance....................100 mΩ maximum

Electrical Life ...............................100,000 operations

Mechanical Life ..........................10,000,000 operations

GENERAL

Power Supply ..............................23 to 30 Vdc, 22 to 27 Vac

Consumption ..............................80 mA maximum at 24 Vdc

Protection Circuitry ...................Reverse voltage protected, overvoltage protected

Operating Conditions ..............0 to 50°C (32 to 122°F),

 

5 to 95 %RH non-condensing

Storage Conditions ...................-30 to 70°C (-22 to 158°F),

 

5 to 95 %RH non-condensing

Wiring Connections ..................Screw terminal block (12 to 24 AWG)

Enclosure ......................................Snap track mounting standard,

 

99mm L x 82.5mm W 32mm H (3.9" x 3.25" x 1.25")

Weight ...........................................110gm (3.88oz)

Country of Origin .......................Canada

DIMENSIONS

99mm

3.9"

82.5mm

3.25"

0001259

R2

R1

R1

R2

RELAY 1

RELAY 1

RELAY 2

RELAY 2

POWER

PWR COM 20V IN

DEADBAND

INPUT RANGE

1%
3%
5%

0-7.5V

0-15V

0-20mA

Figure 4

+

-

PWR

COM

20V

IN

24 Vac/dc Power Supply

+

-

Loop Powered Sensor

PWR

COM

20V

IN

+

-

24 Vac/dc Power Supply

R1

R2

0001259

R2

R1

R1

R2

RELAY 1

RELAY 1

RELAY 2

RELAY 2

POWER

PWR COM20V IN

DEADBAND

INPUT RANGE

1%
3%
5%

0-7.5V

0-15V

0-20mA

Input Range

1%

2%

3%

0- 7.5 Vdc

0.075 Vdc

0.225 Vdc

0.375 Vdc

0 - 15 Vdc

0.15 Vdc

0.45 Vdc

0.75 Vdc

0 - 20 mA

0.2 mA

0.6 mA

1 mA

Deadband Values

Figure 6