IN-GE-GTAR2XXX-01-02 02/19
Page 2
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com
PRINTED IN C
ANAD
A
FACTORY CONFIGURATIONS
The device preset is as follows:
•
Range is 0-15 Vdc
•
R1 is set to 6 Vdc
•
R2 is set to 12 Vdc
•
Deadband is set to 3%
CALIBRATION AND SETUP
•
Set the INPUT RANGE jumper to the correct position for the signal to
be used. For example, if the input signal is 2-10 Vdc, select the 0-15 Vdc
range.
•
Set the deadband jumper to the desired value. This can be changed at
any time with the power on.
•
Connect the power supply and the input signal to the correct terminals.
•
Turn the power on and the POWER LED will light.
•
Apply an input signal equal to the R1 set-point.
•
Adjust the R1 pot clockwise until the RELAY1 LED goes out, then slowly
adjust the R1 pot counter-clockwise until the LED lights.
•
Apply an input signal equal to the R2 set-point and adjust the R2 pot the
same as for R1, watching the RELAY2 LED.
•
Test the operation by increasing the input signal and watch as R1 and R2
turn on at the selected set-points. Then decrease the signal and watch as
the relays turn off at the selected set-points minus the deadband.
SPECIFICATIONS
POWER OUTPUT
Regulated Power Output ........20 Vdc ±10% @ 30 mA max to
power an external sensor
INPUT SIGNAL
Input Voltage Range .................0 to 7.5 or 0 to 15 Vdc
Input Voltage Impedance .......>15 KΩ
Input Current Range .................0 to 20 mA
Input Current Impedance .......250 Ω
OUTPUT RELAYS
Type ................................................SPDT Form C
Contact Rating ............................10 Amps at 125 Vac
Contact Resistance....................100 mΩ maximum
Electrical Life ...............................100,000 operations
Mechanical Life ..........................10,000,000 operations
GENERAL
Power Supply ..............................23 to 30 Vdc, 22 to 27 Vac
Consumption ..............................80 mA maximum at 24 Vdc
Protection Circuitry ...................Reverse voltage protected, overvoltage protected
Operating Conditions ..............0 to 50°C (32 to 122°F),
5 to 95 %RH non-condensing
Storage Conditions ...................-30 to 70°C (-22 to 158°F),
5 to 95 %RH non-condensing
Wiring Connections ..................Screw terminal block (12 to 24 AWG)
Enclosure ......................................Snap track mounting standard,
99mm L x 82.5mm W 32mm H (3.9" x 3.25" x 1.25")
Weight ...........................................110gm (3.88oz)
Country of Origin .......................Canada
DIMENSIONS
99mm
3.9"
82.5mm
3.25"
0001259
R2
R1
R1
R2
RELAY 1
RELAY 1
RELAY 2
RELAY 2
POWER
PWR COM 20V IN
DEADBAND
INPUT RANGE
1%
3%
5%
0-7.5V
0-15V
0-20mA
Figure 4
+
-
PWR
COM
20V
IN
24 Vac/dc Power Supply
+
-
Loop Powered Sensor
PWR
COM
20V
IN
+
-
24 Vac/dc Power Supply
R1
R2
0001259
R2
R1
R1
R2
RELAY 1
RELAY 1
RELAY 2
RELAY 2
POWER
PWR COM20V IN
DEADBAND
INPUT RANGE
1%
3%
5%
0-7.5V
0-15V
0-20mA
Input Range
1%
2%
3%
0- 7.5 Vdc
0.075 Vdc
0.225 Vdc
0.375 Vdc
0 - 15 Vdc
0.15 Vdc
0.45 Vdc
0.75 Vdc
0 - 20 mA
0.2 mA
0.6 mA
1 mA
Deadband Values
Figure 6