Greystone Energy Systems CR3 Series Installation Instructions Manual Download Page 3

Page  3

WIRING 

•  Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent 

electrical shock or equipment damage.

•  Follow proper electrostatic discharge (ESD) handling procedures when installing the device or 

equipment damage may occur. 

•  Use 22 AWG wiring for all connections and do not locate the device wires in the same conduit with 

wiring used to supply inductive loads such as motors. 

•  Make all connections in accordance with national and local codes.

Connect the 24 Vac/dc power supply to the terminals labeled PWR +(power) and - (common) as 

shown in Figure 9.  This device has a half-wave type power supply so use caution when wiring multiple 

devices so that the circuit ground point is the same on all devices and the controller. Use caution if 

24 Vac power is used and one side of the transformer is earth-grounded. In general, the transformer 

should NOT be connected to earth ground when using devices with RS-485 network connections. 

The device is reverse voltage protected and will not operate if connected backwards. Figure 10 shows 

network connections. For end of Line (EOL) device place termination resister jumper in ON position, for 

all other devices, place jumper in OFF position. 

Figure 9

ALARM 

CO

NT

AC

TS

ANAL

OG OUTPUT

S

SENSO

R

BO

ARD   

 

ALARM 

CO

NT

AC

TS

RH-|RH+|TE-|TE+|DP

-|DP+   

 

RH-|RHV|RHI|TE-|TEV|TEI|DP

-|DPV|DPI   

 

VI

N

DIG IN

Pressure Analog Output (4-20mA)

Pressure Analog Output (0-5Vdc or 0-10Vdc)

Pressure Analog Output (Ground)

Temperature Analog Output (4-20mA)

Temperature Analog Output (0-5Vdc or 0-10Vdc)

Temperature Analog Output (Ground)

Humidity Analog Output (4-20mA)

Humidity Analog Output (0-5Vdc or 0-10Vdc)

Humidity Analog Output (Ground)
Pressure Relay (+)

Pressure Relay (-)

Temperature Relay (+)

Temperature Relay (-)

Humidity Relay (+)

Humidity Relay (-)

Digital Input (+)

Digital Input (-)

+24Vdc (24Vac)

Common (24Vac)

Pressure Analog Input (Input)

Pressure Analog Input (Ground)

Temperature Analog Input (Input)

Temperature Analog Input (Ground)

Humidity Analog Input (Input)

Humidity Analog Input (Ground)

Figure 10

G  I   S

-    +

G  I   S

G  I   S

PWR

-    +

DI +

DI -

24 

VDC / 24 

VA

C (+)

COMMON / 24 

VA

C (-)

20V POWER (S)

ANAL

OG IN (I)

GR

OUND (

G)

PWR

DIG IN

DP/TE/RH IN

Pr

essur

e (+)

Pr

essur

e (-)

TEMPER

ATURE (+)

TEMPER

ATURE (-)

HUMIDIT

Y (+)

HUMIDIT

Y (-)

ALARM CONTACTS

1

2

3

4

5

6

DP 4-20mA (DPI)

DP 0-5/10VDC (DPV

)

DP C

OMMON (DP

-)

TE 4-20mA (

TEI)

TE 0-5/10VDC (

TE

V

)

TE C

OMMON (

TE-)

ANALOG OUTPUTS

1

2

3

4

5

6

7

8

9

RH 4-20mA (RHI)

RH 0-5/10VDC (RHV

)

RH C

OMMON (RH-)

1

2

1

2

1

2

3

ANAL

OG OUTPUT

S

Humidity Analog Input (20V Power)

Temperature Analog Input (20V Power)

Pressure Analog Input (20V Power)

IN-CR3

CXXANA-01 04

/20

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for CR3 Series

Page 1: ... instructions may result in product damage Do not use in an explosive or hazardous environment with combustible or flammable gases as a safety or emergency stop device or in any other application where failure of the product could result in personal injury Take electrostatic discharge precautions during installation and do not exceed the device ratings MOUNTING STEP 1 As illustrated in Figure 1 un...

Page 2: ... Match wiring terminals to the labels on the back cover and re insert the wiring terminals into the unit As illustrated in figure 6 Figure 7 STEP 7 As illustrated in Figure 7 secure faceplate to mounting bracket with supplied screws Route wires to prevent pinching when installing unit into wall mounting bracket Figure 4 Figure 6 Figure 5 IN CR3CXXANA 01 04 20 Copyright Greystone Energy Systems Inc...

Page 3: ...on Figure 9 ALARM CONTACTS ANALOG OUTPUTS SENSOR BOARD ALARM CONTACTS RH RH TE TE DP DP RH RHV RHI TE TEV TEI DP DPV DPI VIN DIG IN Pressure Analog Output 4 20mA Pressure Analog Output 0 5Vdc or 0 10Vdc Pressure Analog Output Ground Temperature Analog Output 4 20mA Temperature Analog Output 0 5Vdc or 0 10Vdc Temperature Analog Output Ground Humidity Analog Output 4 20mA Humidity Analog Output 0 5V...

Page 4: ...ctual alarm will not get set until the ALARM ON DELAY time has expired If the alarm condition gets reset before the time expires then no alarm is generated All three alarm relays operate as self resetting and non latching The input signal must return to non alarm condition before the alarm relay returns to the NO state ALARM SETPOINTS Each process variable TEMP RH and DP has both a high and low al...

Page 5: ...mote sensors or from remote transmitters connected to the analog inputs The actual hardware analog inputs will accept either 0 5Vdc 0 10Vdc or 4 20 mA input signal types from remote transmitters The input type is field selectable via the Installer Menu or over the network and the input signals are calibrated digitally for 0 25 span error during factory calibration BothTEMP and RH have network vari...

Page 6: ...ettings NOTE To change a previous setting return to the initial install menu 1 Analog OutputType curr volt Default curr Current orVoltage 2 Volt Output Scale Only if voltage selected 5 or 10 Default 5 Start up When power is first applied to the device a specific sequence of events occurs to test the displays plus indicate certain parameters The sequence is as follows Test all LEDs all LEDs light f...

Page 7: ...fault 0 10 DP Auto Zero only if DP within 10 range 11 TEMP Sensor ResponseTime Default FASt 12 RH Sensor ResponseTime Default FASt 13 dP Sensor ResponseTime Default FASt d i s p t e o n c u r r i n V o l t i n 5 d i s p r h o n d i s p d p o n t E o f f 0 0 r h o F F 0 0 d p 0 C a l r e s p t e f a s r e s p r h f a s r e s p d p f a s IN CR3CXXANA 01 04 20 Copyright Greystone Energy Systems Inc A...

Page 8: ...uto reset Default AUt 21 Buzzer Auto ResetTime Resolution 1 sec Default 15 sec 22 Digital Input Function disable freeze or silence Default disable 23 TEMP Alarm Operation low high both disable Default disable 24 RH Alarm Operation low high both disable Default disable o u t t e d i r o u t r h d i r o u t d p d i r a i n t e 5 0 a i n d p 2 5 0 b u z z a s s d p b u z z r s t a u t b u z z 1 5 s e...

Page 9: ...hanged If SETPOINT LOCK is set then the setpoints can be viewed but not changed 1 Temperature Units C F Default C 2 Pressure Units Pascal or mmWc PA StA Default PA 3 TEMP Alarm Low Setpoint Resolution 1 Default 15C or 59F 4 TEMP Alarm High Setpoint Resolution 1 Default 25C or 77F 5 TEMP Alarm Hysteresis Resolution 0 1 Default 0 2 C or 0 4 F 6 TEMP Alarm On Delay Resolution 1 sec Default 5 sec u s ...

Page 10: ... or 1 mmWc Default 5 Pa 14 DP Alarm On Delay Resolutionis 10 Pa or 1 mmWc Default 200 Pa r h s p l o 3 0 r h s p h i 6 5 r h h y 2 r h r h d l 1 5 s e c d p s p L o 0 d p s p h i 2 0 d p h y 5 p a d p d l 1 0 s e c When Pa units selected setpoint value displayed has been divided by 10 When Pa units selected setpoint value displayed has been divided by 10 Not available if STEP 24 in Installer Menu ...

Page 11: ...rential pressure 21 Min Max Reset Pressing SILENCE resets the min max values Pressing Menu to exit user menu 22 Display Brightness Default Hi Note that only the setpoints that are configured will be shown For example ifTEMP ALARM OPERATION is set for High Alarm only then theTEMP Alarm Low Setpoint will not be shown Note that the setpoint resolution is limited when setting with the menu but higher ...

Page 12: ...0 32 mm high Alarm Indication Low High alarm red LED for each USER INPUT Programming Menu Up Downfrontpanel tactilebuttons Alarm Silence Silence front panel tactile buttons ANALOG OUTPUTS SignalType 4 20 mA sourcing and 0 5 Vdc 0 10 Vdc selectable Number of Outputs 3 Temp RH DP Output Drive 500 Ω max for 4 20 mA 10 KΩ min for voltage Output Scales 0 50 C 0 100 RH 500 Pa ALARM OUTPUTS Number of Out...

Reviews: