background image

Page  2

WIRING

Deactivate the 24 Vac/dc power supply until all connections are made 

to the device to prevent electrical shock or equipment damage. 

Follow proper electrostatic discharge (ESD) handling procedures 

when installing the device or equipment damage may occur.

Use 22 AWG shielded wiring for all connections and do not locate the 

device wires in the same conduit with wiring used to supply inductive 

loads such as motors. Connect the cable shield to ground at the 

controller only. Make all connections in accordance with national and 

local codes.

Connect the 24 Vac/dc power supply to the terminals labeled POWER 

and COMMON. Use caution if 24 Vac power is used and one side of 

the transformer is earth grounded. In general, the transformer should 

NOT be connected to earth ground when using devices with RS-485 network connections. The device is 

reverse voltage protected and will not operate if connected backwards.

Connect the RS-485 network with twisted shielded pair to the terminals marked A(-), B(+) and SHIELD. 

The positive wire connects to B(+) and the negative wire connects to A(-) and the cable shield must be 

connected to the SHIELD terminal on each device. If the device is installed at either end of an RS-485 

network, and end-of-line (EOL) termination resistor (121 Ω) should be installed in parallel to the A(-) and 

B(+) terminals. This device includes a network termination jumper and will connect the (121 Ω) resistor 

correctly on the PCB. Simply move the jumper to the EOL position and no external resistor is required. The 

ground wire of the shielded pair should be connected to earth ground at the end of the network and the 

master is not grounded. Do not run bus wiring in the same conduit as line voltage wiring or other wiring 

that switches power to highly inductive loads such as contactors, coils, or motors.

A network segment is a single shielded wire loop run between several devices (nodes) in a daisy chain 

configuration. The total segment length should be less than 4000 feet (1220 meters) and the maximum 

number of nodes on one segment length is 64. Nodes are any device connected to the loop and include 

controllers but do not include the EOL terminators. To install more than 64 devices, or to increase network 

length, repeaters will be required for proper communication. The maximum daisy chain length (segment) 

depends on transmission speed (baud rate), wire size and number of nodes. If communication is slow or 

unreliable, it may be necessary to wire two daisy chains to the controller with a repeater for each segment.

An optional signal is the relay output available on the N. OPEN and RELAY COM terminals. The RELAY COM 

terminal is NOT connected to the power supply COMMON terminal. The relay output is completely isolated 

and has a Normally Open (NO) signal. This signal can be used to directly control an alarm or ventilation fan.

START-UP

Verify that the transmitter is properly wired and connections are tight. Apply power and note that the 

CO

2

 sensor chamber light flashes on and off. The LCD will indicate the software version number, the Auto 

Cal status, the Modbus address, and the Baud Rate. Then the device will begin reading the sensor values 

and display them on the LCD. The sensor operates on a 4 second interval and will update the output and 

display every 4 seconds.

Figure 5

Figure 6

Building Controller

Device 01

Device 02

Device 03

Set EOL Jumper

Connect Shield

One End Only

Power

COMMON

Power

COMMON

Power

COMMON

A(-)

B(+)

SHLD

A(-)

B(+)

SHLD

A(-)

B(+)

SHLD

Modbus Master

24 Vac / dc

Common

A(-)

B(+)

Shield

EOL

DOWN

A-

B+

SHIELD

COMMON

POWER

UP

SAVE

MENU

N. OPEN

RELAY COM

RELAY

CO2 SENSOR

0001246

EOL

IN-GE-CDD3B1XXXMOD-01-03      11/19 Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for CDD3B1 Series

Page 1: ...tor is exposed to vibrations or rapid temperature changes Thecoverishookedtothebaseatthetopedgeandmustberemovedfromthebottomedgefirst Useasmall Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal of the screw is not required Use the screwdriver to carefully pry each bottom corner if necessary Tip the cover away from the base and sit it aside as shown in Figure 2...

Page 2: ...tive loads such as contactors coils or motors A network segment is a single shielded wire loop run between several devices nodes in a daisy chain configuration The total segment length should be less than 4000 feet 1220 meters and the maximum number of nodes on one segment length is 64 Nodes are any device connected to the loop and include controllers but do not include the EOL terminators To inst...

Page 3: ...itch_Reset Register SET UP MENU The menu has several items as shown below To enter the menu press and release the MENU key while in normal operation This will enter the Setup Menu pressing the MENU key a second time advances to the next menu item The UP and DOWN keys are used to make changes to program variables by scrolling through the available options When a value is changed use the SAVE key to...

Page 4: ... if Relay option Installed Relay Test OFF Use the UP or DOWN keys to toggle the relay ON or OFF Press the MENU key to turn the relay off and advance to the next item 9 RELAY BackLite ENABLE Use the UP or DOWN keys to enable or disable the LCD backlight When enabled the backlight is always on when disabled it never lights Press the SAVE key to save the setting 10 BACKLIGHT Only if viewable LCD Inst...

Page 5: ...0 ppm CO2 gas a tank pressure regulator with flow restrictor and the necessary tubing to connect to the device Note that because of the Automatic Calibration Mode and other technology incorporated into the CDD series only a single point 1000 ppm calibration is required to meet specified accuracy Turn the regulator on off knob fully off and attach it to the 1000 ppm CO2 gas bottle and firmly tighte...

Page 6: ...acitive Accuracy 2 RH Range 0 100 RH non condensing Resolution 1 RH Hysteresis 3 RH Response Time 15 seconds typical Stability 1 2 RH typical 50 RH in 5 years OPTIONAL RELAY OUTPUT Contact Ratings Form A contact N O 2 Amps 140 Vac 2 Amps 30 Vdc Relay Trip Point Programmable 500 to 1500 ppm via Modbus Relay Hysteresis Programmable 25 to 200 ppm via Modbus GENERAL Power Supply 20 to 28 Vac dc non is...

Page 7: ...trol system programmers who may need to add support to their systmes to communicate with the device Modbus setup guide download is available online MODBUS PROTOCOL https downloads greystoneenergy com SG SG CDD3B1XXXMOD pdf IN GE CDD3B1XXXMOD 01 03 11 19 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...

Reviews: