background image

Page  3

OPERATION

In normal operation the device reads the CO

2

, RH, and temperature sensors and updates the register 

values accordingly. The LCD displays the sensor values as determined by the display mode register.

If the device has the optional Up/Down set-point switches installed, pressing either the <UP> or 

<DOWN> keys will cause the LCD to change to show the set-point value. The first key press will display 

the current setting of the Up/Down control from 0 to 100% (default). The display will show "Setpoint 

- xx%" for about 5 seconds and then revert back to the sensor values again if neither the <UP> 

or<DOWN> keys are pressed again. To increase the set-point, press the <UP> key while the LCD is in 

set-point mode and each press will increase the set-point by 10% up to the 100% maximum value. To 

decrease the set-point, press the <DOWN> key while the LCD is in set-point mode and each press will 

decrease the set-point by 10% down to the 0% minimum value. After 5 seconds of no key activity, the 

display will revert back to normal and the new set-point value will be saved. The setpoint units may be 

changed as described in the menu section.

If the device has the optional Override switch installed, pressing the <OVERRIDE> key will cause the LCD 

to change to show the override status. The display will show "Override - ON" for about 5 seconds and 

then revert back to the sensor values again. The override cannot be turned OFF with the switch, it must 

be reset via the Modbus Overridde_Switch_Reset Register.

SET-UP MENU

The menu has several items as shown below. To enter the menu, press and release the <MENU> key 

while in normal operation. This will enter the Setup Menu, pressing the <MENU> key a second time 

advances to the next menu item. The <UP> and <DOWN> keys are used to make changes to program 

variables by scrolling through the available options. When a value is changed, use the <SAVE> key to 

save it to memory and advance to the next menu item. No values are saved using the <MENU> key.

Setup Menu operation is explained below, the factory default values are shown. Note that items that are 

not applicable to the hardware configuration are skipped on the device's setup.

Press and release the <MENU> key to enter the Setup Menu.

ModBus

Addr 01

Press the <UP> or <DOWN> keys to select a unique slave address from 1-255. Press 

the <SAVE> key to save the change.

<MENU> 

Press to advance to next menu item

1. MAC ADDRESS

BaudRate

9600

Use the <UP> or <DOWN> keys to select a baud rate of 300, 600, 1200, 2400, 

4800, 9600, 19200, 38400, 57600, 76800 or 115200.. Press <SAVE> key to save the 

change. 

<MENU> 

Press to advance to next menu item

2. BAUD RATE

Mod Mode

RTU

Use the <UP> or <DOWN> keys to toggle between RTU and ASCII modes. Press the 

<SAVE> key to save the change. The factory default Modbus transmission mode is 

RTU.

<MENU> 

Press to advance to next menu item

3. MOD MODE

ModBus

Parity N

Use the <UP> or <DOWN> keys to select a parity value of N (none), O (odd), or 

E (even). Press the save key to save the change.

<MENU> 

Press to advance to next menu item

4. PARITY VALUE

IN-GE-CDD3B1XXXMOD-01-03      11/19 Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for CDD3B1 Series

Page 1: ...tor is exposed to vibrations or rapid temperature changes Thecoverishookedtothebaseatthetopedgeandmustberemovedfromthebottomedgefirst Useasmall Phillips screwdriver to loosen the security screw as shown in Figure 1 Complete removal of the screw is not required Use the screwdriver to carefully pry each bottom corner if necessary Tip the cover away from the base and sit it aside as shown in Figure 2...

Page 2: ...tive loads such as contactors coils or motors A network segment is a single shielded wire loop run between several devices nodes in a daisy chain configuration The total segment length should be less than 4000 feet 1220 meters and the maximum number of nodes on one segment length is 64 Nodes are any device connected to the loop and include controllers but do not include the EOL terminators To inst...

Page 3: ...itch_Reset Register SET UP MENU The menu has several items as shown below To enter the menu press and release the MENU key while in normal operation This will enter the Setup Menu pressing the MENU key a second time advances to the next menu item The UP and DOWN keys are used to make changes to program variables by scrolling through the available options When a value is changed use the SAVE key to...

Page 4: ... if Relay option Installed Relay Test OFF Use the UP or DOWN keys to toggle the relay ON or OFF Press the MENU key to turn the relay off and advance to the next item 9 RELAY BackLite ENABLE Use the UP or DOWN keys to enable or disable the LCD backlight When enabled the backlight is always on when disabled it never lights Press the SAVE key to save the setting 10 BACKLIGHT Only if viewable LCD Inst...

Page 5: ...0 ppm CO2 gas a tank pressure regulator with flow restrictor and the necessary tubing to connect to the device Note that because of the Automatic Calibration Mode and other technology incorporated into the CDD series only a single point 1000 ppm calibration is required to meet specified accuracy Turn the regulator on off knob fully off and attach it to the 1000 ppm CO2 gas bottle and firmly tighte...

Page 6: ...acitive Accuracy 2 RH Range 0 100 RH non condensing Resolution 1 RH Hysteresis 3 RH Response Time 15 seconds typical Stability 1 2 RH typical 50 RH in 5 years OPTIONAL RELAY OUTPUT Contact Ratings Form A contact N O 2 Amps 140 Vac 2 Amps 30 Vdc Relay Trip Point Programmable 500 to 1500 ppm via Modbus Relay Hysteresis Programmable 25 to 200 ppm via Modbus GENERAL Power Supply 20 to 28 Vac dc non is...

Page 7: ...trol system programmers who may need to add support to their systmes to communicate with the device Modbus setup guide download is available online MODBUS PROTOCOL https downloads greystoneenergy com SG SG CDD3B1XXXMOD pdf IN GE CDD3B1XXXMOD 01 03 11 19 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...

Reviews: