TTFM 1.0 Transit Time Flow Meter
Possible Causes:
Corrective Action:
NO ECHO INDICATION Icon: No Echo
Sensor Connections
Check sensor connections at TTFM and at
sensor junction box.
Note: Refer to Sensor Cable Resistance Test to
test final connections.
Sensors not mounted to Pipe or mounted improperly
Apply coupling compound and mount sensors
to pipe with proper sensor spacing.
Empty pipe or partially filled
Pipe must be fluid filled and acoustically
transparent in order to obtain echoes.
Coupling compound washed out, or sensor loose on
pipe.
Remount sensor
Use Dow Corning Silicone #4
METER READING HIGHER THAN EXPECTED?
Calibration Error
Review calibration menu. Pipe dimensions and
fluid selection/fluid velocity.
Higher flow rate than expected
Investigate pump/valves. Compare velocity
with alternate instrument.
Erratic measurement (set damping to 0% to check) due
to electrical noise or poor signal quality.
Ensure all Flowmeter wiring is in METAL
conduit and sensor shield is properly grounded.
Ensure correct power input Ground connection
(<1 ohm resistance).
Ensure 4-20mA Shield connected to Instrument
Ground stud.
Try adjusting sensor spacing (+/- 10%) and
contact Greyline for further assistance.
Pipe not Full
Verify pipe is full by mounting sensors at top
of pipe and check echo icon.
No echo if pipe is not full.
High viscosity fluid
Laminar flow profile due to high viscosity fluid
requires an adjustment to Cal Const.
Summary of Contents for TTFM 1.0
Page 2: ...Note This page has been left blank intentionally ...
Page 4: ...Page 4 TTFM 1 0 Transit Time Flow Meter SENSOR INSTALLATION ...
Page 6: ...Page 6 TTFM 1 0 Transit Time Flow Meter CONNECTIONS ...
Page 9: ...Page 9 TTFM 1 0 Transit Time Flow Meter CALIBRATION MENU ...
Page 10: ...Page 10 TTFM 1 0 Transit Time Flow Meter ICONS ...
Page 24: ...Page 24 TTFM 1 0 Transit Time Flow Meter SENSOR MOUNTING COUPLING RECOMMENDATIONS BAD GOOD ...
Page 36: ...Page 36 TTFM 1 0 Transit Time Flow Meter SENSOR INTRINSIC SAFETY ...