Greenheck XG-BP Installation, Operation And Maintenance Manual Download Page 6

XG-Fan Powered Air Terminals Rev 2

6

Troubleshooting

If the fan motor does not energize:

 

5

With the power off, verify for free rotation of fan blower wheel 

using standard safety precautions.

 

5

Check for proper supply voltage.

 

5

Disconnect switch (if supplied), should be in the ON position.

 

5

Check fan motor fusing (always use time delay fusing).

 

5

Check for proper control signal, 24 VAC at fan.

 

5

Verify contractor and fan relay energized.

 

5

If Parallel Variable Fan Air Terminal, verify there is a call  

for fan.

Excessive Noise When Fan Motor Runs

 

5

Check for clearance problems with fan motor and blower 

components.

 

5

Check that all components are properly assembled.

 

5

Verify the ductwork does not have any leaks or loose con-

nections and diffusers are not rattling or balancing dampers 

are not generating noise.

 

5

Verify maximum CFM is not too high or discharge static 

pressure too low.

Insufficient Air Flow

 

5

Check for restrictions in ductwork.

 

5

Check for dirty or clogged hot water coils (if supplied).

 

5

Verify intake filter is not clogged or dirty (if supplied).

 

5

Re-adjust SCR motor speed control.

 

5

Verify discharge static is not too high.

Note:

 

If repair or replacement of fan blower or motor is re-

quired, the fan motor and blower should be removed as 

an assembly.

 

Fan Motor/Blower Removal

1.  Disconnect power to XG-Fan Powered Air Terminal.

2.  Remove bottom fan motor/blower access panel.

3.  Disconnect motor wires for fan motor.

4.  Remove the two bottom screws holding motor/blower as-

sembly to XG-Fan Powered Air Terminal discharge end plate 

bracket.

5.  Loosen the top two screws holding motor/blower assem-

bly to XG-Fan Powered Air Terminal discharge end plate 

bracket.

6.  Lift the fan motor/blower

 

assembly upward to disengage the 

top two motor screws.

7.  Do not allow the fan motor/blower assembly to hang from 

the power leads.

Fan Motor Removal from Blower

1.  Loosen the blower wheel hub set screw to fan motor shaft.

2.  Remove the 3 screws holding motor leg brackets to blower 

housing.

3.  Slide the fan motor out of the fan blower wheel.

4.  Reverse steps 1-3 to re-install motor to blower wheel.

5.  Verify isolation grommets are in place on the fan motor legs.

6.  Verify the blower wheel set screw is properly torqued and 

LOCKTITE has been applied to threads.

7.  Do not over tighten the fan motor leg mounting screws.

Electric Duct Heater

Caution: Use extreme care if testing the electric 

heater with power on!

The control cabinet contains live electrical parts. Contact-

ing these parts with the power applied may cause serious 

injury or death.

Caution: This unit should be serviced by a licensed 

electrician or a similarly qualified electrical service 

technician!

If the electric heater does not operate:

 

5

Check electric power into the unit and verify the input power 

agrees with the label data.

 

5

Verify the Air Terminal is installed properly (according to the 

air flow orientation).

 

5

Review the wiring diagram attached to the inside of the 

control enclosure cover to verify the field wiring is correct 

with proper gauge wire, overcurrent protection and properly 

grounded.

If the electric heater cycles on and off:

 

5

Verify the air flow is uniformly distributed across the face of 

the heater elements.

 

5

Check for obstructions in the duct or insufficient air flow. (70 

CFM per kW required)

If conditioned space fails to warm up:

 

5

Verify the electric heater controls and thermostat are com-

patible and wired properly.

 

5

Relocate the room thermostat if it is located in position that 

is too warm.

If condition space overheats:

 

5

Verify the electric heater controls and room thermostat are 

compatible and wired properly.

 

5

Relocate the room thermostat if it is located in position that 

is too cold.

 

5

Verify the air distribution to the space is appropriate for the 

required thermal load.

Summary of Contents for XG-BP

Page 1: ...empting to assemble install operate or maintain the product described Protect yourself and others by observing all safety information Failure to comply with these instructions will result in voiding o...

Page 2: ...ts 5 The XG Fan Powered Air Terminal should be suspended from the building structure in a horizontal plane with the bottom access panel facing down 5 Do not obstruct the bottom access panels or side m...

Page 3: ...These clearances recommendations are not meant to preclude NEC requirements or local building codes that may be applicable which are the responsibility of the installing contractor Connecting Duct Wo...

Page 4: ...s with Hot Water Coils Always inspect the hot water coils for damage prior to install ing the XG Fan Powered Air Terminal Caution The copper tubing should not be used as lift points The hot water coil...

Page 5: ...ckwise to reduce the fan speed 8 Turn the SCR motor speed control clockwise to increase fan speed 9 Set the XG Fan Powered Air Terminal to full heating maxi mum induction 10 Adjust the downstream damp...

Page 6: ...er assembly to hang from the power leads Fan Motor Removal from Blower 1 Loosen the blower wheel hub set screw to fan motor shaft 2 Remove the 3 screws holding motor leg brackets to blower housing 3 S...

Page 7: ...ower supply wiring voltage are correct contact factory for further assistance Manual reset safety switch has tripped 1 Push the reset safety button on back of safety reset The manual safe ty reset is...

Page 8: ...ng coil 6 Use an ohmmeter to check continuity of the holding coil on the back up contractor 7 If bad contact factory for replacement backup contractor Insufficient air flow across the electric heat in...

Page 9: ...XG Fan Powered Air Terminals Rev 2 9 Figure 3...

Reviews: