background image

Laboratory Exhaust System

3

®

occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. 
Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity 
of the surfaces. Wipe clean thoroughly with Tectyl

®

 506 (Ashland Inc.) or the equivalent. For hard to reach internal 

surfaces or for occasional use, consider using Tectyl

®

 511M Rust Preventive or WD-40

®

 or the equivalent.

REMOVING FROM STORAGE

As fans are removed from storage to be installed in their final location, they should be protected and maintained in a 
similar fashion, until the fan equipment goes into operation.
Prior to assembly and installation of the Vektor fan and system components, inspect the fan assembly to make sure 
it is in working order.
1.  Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base and accessories for tightness.
2.  Rotate the fan wheel(s) by hand and assure no parts are rubbing. Access to the wheel is obtained through a 

bolted panel located on the side of the fan housing.

General Information

To ensure a successful installation, the instructions in this manual should be read and adhered to. Failure to comply 
with proper installation procedures may void the warranty.

Unit and System Identification Tags

Each fan has a permanently affixed manufacturer’s engraved metal nameplate containing the model number and 
individual serial number.
The tag shown is an example of an identification nameplate on the fan. The 
information provides general details about the fan, as well as containing specific 
information unique to the unit. When contacting your local manufacturer’s 
representative with future needs or questions, please have the information on 
this label available. Tags are mounted in an area which is clearly visible, usually 
on the side of the fan cabinet.
Vektor fan systems may arrive in component pieces due to shipping restrictions. Individual components of a system 
have matching identification tags which should be used to identify and assemble the complete system. Assembling 
systems with different identification tags can cause reductions in the fan(s) performance.
Prior to fully assembling and installing the Vektor-H or Vektor-HS fans, inspect bypass air plenums and the fan 
assembly to make sure they are in working order.

Pre-Installation Information

Before installation, it is important to be certain the mounting surface will bear the operating weight of the unit. For 
proper unit operation, it is also important that it be operated in a completely level position.
For further details on safety practices involving industrial and commercial fans, please refer to AMCA 
Publication 410.

Electrical Disconnects

All fan motors should have disconnects located in close visual proximity to turn off electrical service. Service 
disconnects shall be locked-out when maintenance is being performed.

Moving Parts

All moving parts must have guards to protect personnel. Refer to local codes for requirements as to the number, 
type and design. Fully secure fan wheel before performing any maintenance. The fan wheel may start “free wheeling” 
even if all electrical power has been disconnected. Before the initial start-up or any restart, check the following items 
to make sure that they are installed and secure.
•  Do not spin fan wheel faster than the maximum cataloged fan rpm. 
•  Adjustments to fan speed significantly affects motor load. If the fan RPM is changed, the motor current should be 

checked to make sure it is not exceeding the motor nameplate amps.

Guards (Motor Cover, Weatherhoods)

Do not operate fans without proper protective devices in place. Failure to do so may result in serious bodily injury 
and property damage. Check local codes to ensure compliance for all protective devices.

Air Pressure and Suction

In addition to the usual hazards associated with rotating machinery, fans also create a dangerous suction at the inlet. 
Special caution needs to be used when moving around a fan, whether it is in operation or not. Before start-up, make 
sure the inlet area is clear of personnel and loose objects.

Summary of Contents for Vektor-HS

Page 1: ...instructions and should be aware of general safety precautions Improper installation can result in electric shock possible injury due to coming in contact with moving parts as well as other potential hazards Other considerations may be required if high winds or seismic activity are present If more information is needed contact a licensed professional engineer before moving forward 1 Follow all loc...

Page 2: ...eratures should be evenly maintained between 30 F and 110 F 1 C and 43 C Wide temperature swings may cause condensation and sweating of metal parts All accessories must be stored indoors in a clean dry atmosphere Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid sweating of metal parts allow cold parts to reach room temperature To dry parts an...

Page 3: ...ual components of a system have matching identification tags which should be used to identify and assemble the complete system Assembling systems with different identification tags can cause reductions in the fan s performance Prior to fully assembling and installing the Vektor H or Vektor HS fans inspect bypass air plenums and the fan assembly to make sure they are in working order Pre Installati...

Page 4: ...re lifting be sure that all shipping materials have been removed from the unit 2 Use standard lifting and rigging practices 3 All lifting brackets on each unit must be utilized at the same time 4 Fan to be kept level during lifting and installation 5 Spreader bars must span the unit to prevent damage to the unit by the lifting cables 6 Always test lift the unit to check for proper balance and rigg...

Page 5: ...OTHERS SEE NOTE ABOVE Continuous weld or stitch weld Minimum 6 inch 152 4 mm stitch weld by 3 25 inch 82 5 mm spacing minimum Minimum 6 inch 152 4 mm weld on each corner OR Install 5 16 inch 7 9375 mm 24 Dril Flex Self Drilling Tapping Screws 3 16 inch 4 7625 mm minimum thread engagement into A36 steel centered in flange 4 5 inch 114 3 mm spacing 5 8 inch 15 875 mm minimum edge distance ALL HARDWA...

Page 6: ...r is present in the roof curb the duct is located between the roof curb and the damper adapter tray Duct Connection to Curb Side or End Duct Connection Vektor H or Vektor HS With bypass air plenum NOTE Plenum is provided with removable side or end panels allowing the proper duct connection Duct to Bypass Air Plenum Bypass Air Plenum Weatherhood Duct flange and gasketing by others Roof Curb Option ...

Page 7: ...ozzle subassemblies as shown in the submittal drawing Align flange bolt holes and fasten sections using the 3 8 inch 316 stainless steel bolts washers and lock washers provided 6 Follow electrical connection and pre start up checks as listed on pages 10 and 11 System Assembly NOTE When installing each section be certain to rig each section separately using the lifting lugs provided Stack Extension...

Page 8: ... of air velocity through the fan is maintained per NFPA 96 clause 8 2 1 1 2008 edition and UL 762 Issue 5 December 19 2003 clause 6 2 Grease Trap A grease trap is an aluminum trap designed to collect grease residue to avoid drainage onto roof surface It contains a built in water separating baffle Instructions 1 Apply cover to grease trap Install clip nuts to trap over holes provided Attach cover w...

Page 9: ...y occur Drain connections are 1 2 inch NPT Installed piping to have a downward angle to allow for drainage Fill traps to recommended level before start up Note A conservative method of trap design is to set N total static pressure Fan Drain Connection Plenum Drain Connection H 1 in for each inch of maximum negative static pressure plus 1 in J 1 2 of H L H J Pipe diameter L H J Connect this end to ...

Page 10: ...ed to fan housing Optional transformer and isolation damper refer to CAPS file selection SINGLE PHASE LAYOUT THREE PHASE LAYOUT THREE PHASE WITH VFD LAYOUT Field Wiring Factory Wiring Field Wiring Factory Wiring Field Wiring Factory Wiring Three Phase with Variable Frequency Drives Layout LINE IN 115 208 230 277 volt single phase MOTOR DISCONNECT 115 208 230 277 volt Single phase TRANSFORMER 208 2...

Page 11: ... inlet For 3 phase installations fan rotation can be reversed by simply interchanging any two of the three electrical leads For single phase installations follow the wiring diagram located on the motor Radial Gap Overlap A Inlet Cone Wheel Vektor H Applications with Variable Frequency Drive VFD For Vektor systems with single point three phase wiring per blower the isolation damper actuator will be...

Page 12: ...rive Motor bearings are lubed for life with no maintenance required If motor or wheel needs to be serviced or replaced use the lifting lugs to pull assembly cartridge out Removal of Dust and Dirt Dirt clogs cooling openings on the motor housing contaminates bearing lubricant and collects on the impeller causing severe imbalance if left unchecked The exterior surface of the motor and impeller shoul...

Page 13: ... a gravity isolation damper remove the panel opposite the weatherhood on the bypass air plenum section and slide the damper straight out toward you When performing maintenance on an isolation damper with an actuator remove the bolted weatherhood and disconnect the actuator from damper Then remove the panel opposite the weatherhood on the bypass air plenum section and slide the isolation damper out...

Page 14: ...P PAINT REPAIR KIT CONTENTS One Zinc Clad Aerosol Can One pint recoat epoxy primer grey with one pint recoat epoxy primer catalyst One quart H S Polyurethane One Scotch Brite scratch pad Two 1 1 2 inch wide paint brushes Four pint sized empty cans for mixing One quart sized empty can for mixing Zinc repair instructions MSDS sheets NOTE While the manufacturer provides heavy duty quality products fo...

Page 15: ...RAME BOTTOM BAR 2 5 FRAME TOP BAR 2 6 FRAME WELD 2 7 BLADE WELD 2 8 ACTUATOR MOUNT 2 9 LIFT LUG 4 10 ACTUATOR COVER 2 11 BLADE SEAL RIGHT 2 12 BLADE SEAL LEFT 6 13 FLEX BACKING 4 14 VEKTOR BACKING 2 15 ACTUATOR 2 16 ELECTRICAL BOX 1 17 BEARING 4 18 BLADE SEAL 4 19 FLEX SEAL 2 20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Quantity 1 for sizes 9 thru 13 Quantity 2 for sizes 16 thru 36 Item Q...

Page 16: ...AM PM Notes ____________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ____________________________________________ ___________________________________________...

Reviews: