background image

7

Airflow System Start-Up

For proper unit function and safety, follow everything in this start-up procedure in the order presented. This is to
be done after the electrical connections are complete.

1. Check Voltage

Before starting the unit compare the supplied
voltage with the units nameplate voltage and the
motor voltage.

2. Check Blower Rotation

If the blower is rotating in the wrong direction, the
unit will move some air but not perform properly. To
check the rotation, open the blower access door
and run the blower momentarily to determine the
rotation.

To reverse the rotation, turn the power off and use
the following procedure:

• For single phase units, rewire the motor per the

instructions on the motor.

• For three phase units, interchange any two

power leads. This can be done at the motor
starter.

3. Check for Vibration

Check for unusual noise, vibration or overheating
of bearings. Excessive vibration maybe
experienced during initial start-up.  Left
unchecked, excessive vibration can cause a
multitude of problems, including structural and/or
component failure. Many conditions can be
discovered by careful observation.  If the problem
is wheel unbalance, in-place balancing can be

done providing there is access to the fan wheel.
Generally, fan vibration and noise is transmitted to
other parts of the building by the ductwork. To
eliminate this undesirable effect, Greenheck has
used a  heavy canvas connection between the
scroll and the discharge of the fan. If noise is an
issue, we recommend using heavy canvas
connections on the inlet of the fan. Refer to the
“Troubleshooting” section of this manual if a
problem develops.

4. Air Volume Check and Measurement

Along with the building balance, the units air
volume (cfm) should be measured and compared
with its rated air volume. This unit is flexible for
varying air volume, but the actual air volume 
should be known for making final adjustments. The
most accurate way to measure the air volume is by
using the pitot traverse method in the ductwork
away from the blower. Other methods can be used
but should be proven and accurate. To adjust the
air volume, change the fan rpm or the system
losses. 

See Troubleshooting section in this guide.

5. Measure Motor Voltage, Amperage and

Fan rpm

All access doors must be installed. Measure and
record the input voltage and motor amperage(s).

To measure the fan rpm, the blower door will need
to be removed. Minimize measurement time
because the motor may over amp with the door
removed.

Compare measured amps to the motor nameplate
full load amps and correct if over amping. See the
Troubleshooting section in this guide.

Pre-Start Check List

1. Disconnect and lock-out all power switches to

fan.

2. Check all fasteners, set screws and locking

collars on the fan, bearings, drive, motor base
and accessories for tightness.

3. Rotate the fan wheel by hand and assure no

parts are rubbing.

4. Check the V-belt drive for proper alignment and

tension.

Special Tools Required

• Voltage meter
• Tachometer
• Amperage meter

AIRFLOW

R

O

TA

T O

I N

Summary of Contents for MSCF

Page 1: ...items are stored inside the unit during shipping Care must be taken during installation to prevent damage to units MODEL MSCF Modular Small Cabinet Fan Installation Operation and Maintenance Manual W...

Page 2: ...ows panels removed 9 1 1 4 in knockout for recommended electrical wiring penetration or disconnect switch 8 8 8 8 8 7 9 Table of Contents Unit Layout Table of Parts Lifting Hanging Instructions Modula...

Page 3: ...to avoid damage see figure 1 Figure 1 3 Frame Rails By others Spreader bar Lifting lugs The MSCF should be hung by the factory supplied lifting lugs or field supplied frame rails as shown respectivel...

Page 4: ...26 38 2 5 3 5 43 45 6 75 26 18 5 6 75 6 75 26 6 6 75 26 50 2 5 3 5 55 50 6 75 26 18 5 6 75 6 75 26 6 6 75 32 50 2 5 3 5 55 65 6 75 32 18 5 6 75 6 75 28 6 6 75 36 50 2 5 3 5 55 85 6 75 32 18 5 6 75 6...

Page 5: ...nit A B C D E F Size w o Filter w Filter 12 in 24 in Vertical Sloped Hot Water CW DX Fan Motor Total 15 80 107 31 57 34 61 61 145 94 50 144 20 95 126 36 68 41 72 72 171 111 50 161 25 105 140 40 75 45...

Page 6: ...same as 4 row chilled water coil data see below Fluid enters the coil from the bottom connection In and exits from the top Out In Out Out In NOTE With airflow from left to right the fluid enters the...

Page 7: ...nnection between the scroll and the discharge of the fan If noise is an issue we recommend using heavy canvas connections on the inlet of the fan Refer to the Troubleshooting section of this manual if...

Page 8: ...g good duct practices Blower speed too low Check for correct drives and RPMs with catalog data Mixing box dampers closed Open and adjust Dirty or clogged filters Clean or replace Leaks in ductwork Rep...

Page 9: ...n of water coils with low entering air conditions CONTINUOUS WATER CIRCULATION THROUGH THE COIL AT ALL TIMES IS HIGHLY RECOMMENDED 5 Pipe sizes for the system must be selected on the basis of the head...

Page 10: ...ilters are installed check by holding up to a light source If light cannot pass through the filter it should be replaced Replacement filters should be of the same manufacturer and size When reinstalli...

Page 11: ...build up from plugging the drain and causing the drain pan to overflow Inspect twice a year to avoid the possibility of overflow Also drain pans should be kept clean to prevent the spread of disease C...

Page 12: ...Up Documentation Actual Voltage Hertz Phase Actual Amperage Blower Rotation Correct Air Volume Design cfm Actual cfm Drive Level of fan L or H Fan RPM Range min max 462888 MSCF IOM APRIL 2003 Warrant...

Reviews: