background image

COIL MAINTENANCE

1. Coils must be clean to obtain maximum performance. Check once a year under normal operating

conditions and, if dirty, brush or vacuum clean. Soiled fins reduce the capacity of the coil, demand more
energy from the fan, and create an environment for odor and bacteria to grow and spread through the
conditioned zone. High pressure water (400 psi or less) may be used to clean coils with fin thickness over
0.006 inches thick. 

TEST THE SPRAY PRESSURE

over a small corner of the coil to determine if the fins

will withstand the spray pressure. 

For coils with fragile fins or high fin density, foaming chemical sprays and washes are available. Many coil
cleaners contain harsh chemicals, so they must be used with caution by qualified personnel only. Care
must be taken not to damage the coils, including fins, while cleaning.

CAUTION: Fin edges are sharp.

2. Drain pans in any air conditioning unit will have some moisture in them, therefore, algae and other

organisms will grow due to airborne spores and bacteria. Periodic cleaning is necessary to prevent this
build-up from plugging the drain and causing the drain pan to overflow. Inspect twice a year to avoid the
possibility of overflow. Also, drain pans should be kept clean to prevent the spread of disease. Cleaning
should be performed by qualified personnel.

WINTERIZING COILS

Coil freeze-up can be caused by such things as air stratification and failure of outdoor air dampers and/or
preheat coils. Routine draining of water cooling coils for winter shutdown cannot be depended upon as
insurance against freeze-up. Severe coil damage may result. It is recommended that all coils be drained as
thoroughly as possible and then treated in the following manner.

Fill each coil independently with an antifreeze solution using a small circulating pump and again thoroughly
drain. Check freezing point of antifreeze before proceeding to next coil. Due to a small amount of water always
remaining in each coil, there will be diluting effect. The small amount of antifreeze solution remaining in the coil
must always be concentrated enough to prevent freeze-up.

NOTE:

Carefully read instructions for mixing antifreeze solution used. Some products will have a higher freezing

point in their natural state than when mixed with water.

Maintenance Instructions:

Optional Cooling Coils

11

Summary of Contents for MSCF

Page 1: ...items are stored inside the unit during shipping Care must be taken during installation to prevent damage to units MODEL MSCF Modular Small Cabinet Fan Installation Operation and Maintenance Manual W...

Page 2: ...ows panels removed 9 1 1 4 in knockout for recommended electrical wiring penetration or disconnect switch 8 8 8 8 8 7 9 Table of Contents Unit Layout Table of Parts Lifting Hanging Instructions Modula...

Page 3: ...to avoid damage see figure 1 Figure 1 3 Frame Rails By others Spreader bar Lifting lugs The MSCF should be hung by the factory supplied lifting lugs or field supplied frame rails as shown respectivel...

Page 4: ...26 38 2 5 3 5 43 45 6 75 26 18 5 6 75 6 75 26 6 6 75 26 50 2 5 3 5 55 50 6 75 26 18 5 6 75 6 75 26 6 6 75 32 50 2 5 3 5 55 65 6 75 32 18 5 6 75 6 75 28 6 6 75 36 50 2 5 3 5 55 85 6 75 32 18 5 6 75 6...

Page 5: ...nit A B C D E F Size w o Filter w Filter 12 in 24 in Vertical Sloped Hot Water CW DX Fan Motor Total 15 80 107 31 57 34 61 61 145 94 50 144 20 95 126 36 68 41 72 72 171 111 50 161 25 105 140 40 75 45...

Page 6: ...same as 4 row chilled water coil data see below Fluid enters the coil from the bottom connection In and exits from the top Out In Out Out In NOTE With airflow from left to right the fluid enters the...

Page 7: ...nnection between the scroll and the discharge of the fan If noise is an issue we recommend using heavy canvas connections on the inlet of the fan Refer to the Troubleshooting section of this manual if...

Page 8: ...g good duct practices Blower speed too low Check for correct drives and RPMs with catalog data Mixing box dampers closed Open and adjust Dirty or clogged filters Clean or replace Leaks in ductwork Rep...

Page 9: ...n of water coils with low entering air conditions CONTINUOUS WATER CIRCULATION THROUGH THE COIL AT ALL TIMES IS HIGHLY RECOMMENDED 5 Pipe sizes for the system must be selected on the basis of the head...

Page 10: ...ilters are installed check by holding up to a light source If light cannot pass through the filter it should be replaced Replacement filters should be of the same manufacturer and size When reinstalli...

Page 11: ...build up from plugging the drain and causing the drain pan to overflow Inspect twice a year to avoid the possibility of overflow Also drain pans should be kept clean to prevent the spread of disease C...

Page 12: ...Up Documentation Actual Voltage Hertz Phase Actual Amperage Blower Rotation Correct Air Volume Design cfm Actual cfm Drive Level of fan L or H Fan RPM Range min max 462888 MSCF IOM APRIL 2003 Warrant...

Reviews: