Energy Recovery Ventilator
6
®
Duct Connections
Examples of good and poor fan-to-duct connections are
shown below. Airflow out of the fan should be directed
straight or curve the same direction as the fan wheel
rotates. Poor duct installation will result in low airflow,
loud noise and excessive vibrations.
4x Wheel Diameter
MiniVent
Less
than 4x Wheel Diameter
GOOD
GOOD
POOR
Recommended Discharge Duct Size and Length
MiniVent
ERV
Blower Size
Duct
Size
Straight Duct
Length
450
8
10 x 8
32
750
10
10 x 10
40
All dimensions are in inches.
Base Vibration Isolator Assembly
3/8-inch bolt
Factory-mounted
bracket
Lock washer
Flat washer
Isolator
Assembled and Mounted Isolator Detail
Base Mounting with Base Vibration
Isolation
• The base isolators kit includes four (4) isolators,
four (4) brackets and required hardware.
• Rotate the MiniVent 180 degrees, so the electrical
and fan component panel is accessible from the top.
The corners, where the brackets are fastened, are
now closest to the mounting surface.
• Assemble and mount the isolators as shown in the
figures below.
Note: The hanging and base mounting brackets are
fastened to the same unit corners.
Electrical
and
Fan Access Panel