background image

Notes for wiring units

For all units:

1. The units nameplate states the voltage and total amperage required. 

The main feeder supplying power to the unit should be sized for the name plate voltage and 
amperage.

2. The main power line should be connected to the disconnect switch. 

Make sure that the disconnect lugs are securely tightened.

3. Connect control panel wiring to terminal strip in the control center. 

Greenheck’s standard control voltage is 120/60/1.

4. Wire any remote temperature selectors (optional) at this time. These wires

should be shielded cable if they are to be run with other power wires.

5. When an optional convenience outlet is provided, a separate power supply must be provided to 

the receptacle. This circuit must be on a ground fault breaker.

For power vent units:

1. Power vent units require an additional field supplied 115 Volt power source for the power vent 

motor.

2. The power vent unit is factory interlocked with the power to the furnace so the furnace will not 

function unless the power vent motor is running.

3. The power vent motor will not run unless the furnace is turned on and the gas controls are calling 

for heat.

For units with combination extension:

1. Wire power lead for CUBE through side breather tube.
2. The power lead should be of sufficient length as to allow the CUBE fan to hinge open and to 

allow service of the burner controls.

DANGER !

High voltage electrical input is needed for this
equipment. This work should be performed by a
qualified electrician.

Control Center Door

Unit Name Plate

CUBE Exhaust
Fan

Electrical Knockouts

Field Wiring
to CUBE

Before connecting power to the unit, read and
understand the following instructions and wiring
diagrams. Complete wiring diagrams are
attached inside the door(s) of the unit.

All wiring should be done in accordance with the
National Electrical Code ANSI/NFPA-70 latest
edition and any local codes that may apply. In
Canada, wiring should be done in accordance
with the Canadian Electrical Code. The
equipment must be properly grounded.

NOTE

: Any wiring running through the unit in the airstream must be protected by 

flexible metal conduit, metal clad cable or raceways. 

Electrical Instructions

CAUTION !

Any wiring deviations may result in personal injury or property damage. Greenheck is not

responsible for any damage to, or failure of the unit caused by incorrect field wiring.

8

Summary of Contents for IG-100

Page 1: ...t exchanger failure do not locate any gas fired units in areas where chlorinated halogenated or acid vapors are present in the atmosphere This manual is the property of the owner and is required for f...

Page 2: ...for both obvious and hidden damage If damage is found record all necessary information on the bill of lading and file a claim with the final carrier Check to be sure that all parts of the shipment in...

Page 3: ...apter is only a guide and is not intended to be used as support for the ductwork 3 Before beginning this installation Make sure that there is room to access the unit from all sides The inlet must be l...

Page 4: ...d down stream where there is good air mixture and where it is away from dead spots in the ductwork Sometimes this can only be done through trial and error Too far from the unit may cause delay problem...

Page 5: ...to lag in place Prepunched holes are provided Locate extension so the tall louvered side is over the exhaust opening as shown in illustration Step 4 Install Ductwork Exhaust Exhaust ductwork must be...

Page 6: ...xhaust fan prior to the supply unit will allow for easier installation of options Step 7 Install Supply Unit Use a crane and a spreader bar hooked to the factory lifting lugs as shown in the diagram t...

Page 7: ...used as support for the ductwork Before beginning this installation Make sure that there is room to access the unit from all sides The inlet must be located at least 10 feet away from any exhaust ven...

Page 8: ...furnace is turned on and the gas controls are calling for heat For units with combination extension 1 Wire power lead for CUBE through side breather tube 2 The power lead should be of sufficient lengt...

Page 9: ...Provides proper fusing for supply and exhaust fan motor 4 Motor Starters 120 Volt magnetic contacts for starting motors comes standard with electronic overload Can be provided with auxiliary contacts...

Page 10: ...e method in the ductwork away from the blower Other methods can be used but should be proven and accurate To adjust the air volume change the fan rpm or the system static See Trouble Shooting section...

Page 11: ...ace damper motor System static pressure too high Improve ductwork to eliminate losses using good duct practices Blower speed too low Check for correct drives and rpm with catalog data Dampers or regis...

Page 12: ...out of either side of the unit If washable filters are installed they can be washed in warm soapy water An adhesive spray can be applied to increase filter efficiency If disposable filters are install...

Page 13: ...commendations Furnace Maintenance The following procedure should be completed before every heating season by a qualified service person 1 Remove and inspect burner Check burner ports and burner mixing...

Page 14: ...Replace transformer Check wiring to transformer Is combination gas control on Is limit control tripped Is gas supply valve open Is there sparking at pilot Is there gas to pilot Is the spark gap corre...

Page 15: ...lve closed and no spark and restart the ignition sequence again After going through this trial wait sequence 3 times the control will wait an additional 1 hour and repeat the process again if necessar...

Page 16: ...ssure regulator safety shut off valves pilot regulator and manual shut off knob For staged control this valve also controls 50 and or 100 fire 6 Modulating Valve Modulates gas to main burner for prope...

Page 17: ...setting If the outside air is below 55 F place a jumper wire from terminal 3 to terminal 4 on the amplifier If there is a room override stat remove the wire from terminal 14 on the amplifier and isol...

Page 18: ...Uses Housing 3 See CUBE literature for complete dimensions and weights of CUBE fan Minimum Distances Required per NFPA 96 FPE Model CUBE Sizes A B C D E 102 98 100 120 130 41 5 20 0 26 5 23 63 24 12 1...

Page 19: ...Optional V Bank Filters Optional Motorized Intake Damper Optional Recirc Damper Recommended Roof Opening Roof Curb O D Supply Duct H Roof Curb O D w Recirc M Optional Return Duct Furnace Supply Return...

Page 20: ...Height 2 Optional Recirc Damper Roof Curb O D w Recirc M Optional Return Duct Furnace Supply Return Duct Locations Roof Roof Curb Rec Supply Rec Return Input Duct Duct H M Curb O D O D w Recirc Roof...

Page 21: ...ly Duct H Lifting Lugs Unit Dimensions F Curb Height 2 1 2 G Curb Height 2 Optional Recirc Damper Roof Curb O D w Recirc Optional Return Duct Furnace Supply Return Duct Locations Roof Roof Curb Supply...

Page 22: ...Optional Motorized Intake Damper E Gas Connection G Lifting Lugs Lifting Lugs F D Optional V Bank Filters Optional Recirc Damper Roof Curb O D Recommended Roof Opening Roof Curb O D w Recirc M Option...

Page 23: ...ting Lugs 18 F 48 1 2 Gas Connections Lifting Lugs Lifting Lugs For IG 500 5 Dim IG 500 IG 600 IG 800 J 24 24 24 K 13 11 1 2 8 1 4 L 27 1 2 32 1 2 38 3 4 F Curb Height 2 1 2 G Curb Height 2 Unit Dimen...

Page 24: ...k Filters Optional Motorized Intake Damper Lifting Lugs 18 F 48 1 2 3 Gas Connections Lifting Lugs Lifting Lugs Unit Dimensions F Curb Height 2 1 2 G Curb Height 2 Optional Recirc Damper Furnace Roof...

Page 25: ...gs Lifting Lugs Optional Motorized Intake Damper E F 10 Foot Min Recommended Roof Opening Roof Curb O D Supply Duct H Exhaust Duct J K L Furnace Supply Roof Recommended Input Duct H J K L Curb O D Roo...

Page 26: ...imensions meet minimums required by NFPA 96 8 minimum curb height must be used G Curb Height 6 Gas Connections Lifting Lugs Lifting Lugs 60 1 2 24 Min 53 Min See CUBE literature for recommended exhaus...

Page 27: ...recommended exhaust duct sizes Furnace Supply Roof Recommended Input Duct Curb O D Roof Opening 500 800 24 x 40 50 1 2 x 108 1 2 47 x 105 Roof Curb Dimensions Roof Curb O D Supply Duct 26 Exhaust Duct...

Page 28: ...late Information Model ___________________________________________ Volts ___________ Hertz __________ Phase __________ Amps __________________ Mark ___________________ Supply hp _____________ Exhaust...

Reviews: