tOR Wiring

Fig. 6

FSDR-XXX and DFDR-XXX Blade Orientation

Normal

30° Off Horizontal

(Maximum)

30° Off Horizontal

(Maximum)

Axle

Axle

Axle

30°

30°

RAtINGS  (Fig. 6) 

 
 

Integral Switch type:

   Single Pole, double throw

 

         

 Electrical:

    10 Amps, 

1

/

3

 hp, 120 or 240 Vac

 

   

1

/

2

 Amp, 125 Vdc; 

1

/

4

 Amp 250 Vdc 

 

   5 Amps, 120 Vac “L” (lamp load)

 

   1.0 Amps, 24 Vac

 

   1.5 Amps, 24 Vdc

 

temperature Limit

:   165° F (standard primary sensor)

 

  212° F (optional primary sensor)

 

  250° F (secondary sensor)

 

  350º F ( secondary sensor)

8. Recommended Preparation of Openings in 

Wood and Metal Stud Walls

•  Frame wall openings as shown. (see 

Fig. 7

)

•  Double vertical studs are not required for openings 

36 in. x 36 in. or smaller.

•  Gypsum wall board must be fastened 12 in. on 

center to all stud and runner flanges surrounding 
opening. (see

 Fig. 8

)

•  All construction and fasteners must meet the 

requirements of the appropriate wall design (See UL 
Fire Resistance Directory) and/or local codes.

Fig. 7

*/5)*4(3007&

3&5"*/&31-"5&

%0/051-"$&

*/5)*4(3007&

%0/051-"$&
3&5"*/&31-"5&

%".1&3'3".&

%".1&3'3".&

800%
456%

.*/

456%

.&5"-


.*/

JO

JOPD

.BYJNVN

'MPPS3VOOFS

JO

$FJMJOH3VOOFS

1BOIFBE

4DSFXT

JOPD

.BYJNVN

 NFUBMTUVET

JOPD

.BYJNVN

 NFUBMTUVET

JOPD

.BYJNVN

 XPPETUVET

JOPD

.BYJNVN

 XPPETUVET

JO

Fig. 8

Summary of Contents for FSDR-XXX

Page 1: ... backcharges without prior written authorization Due to continuing research Greenheck reserves the right to change specifications without notice UL CLASSIFIED see complete marking on product UL CLASSIFIED to Canadian safety standards see complete marking on product UL Standard 555 555S Classification R13317 FSDR XXX SEFSDR XXX and SSFSDR XXX Model Dampers are intended for installation in accordanc...

Page 2: ...ve leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and after installation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be sufficiently covered as to pr...

Page 3: ...opening must be a minimum of 7 8 in larger than the outside diameter of the damper Refer to Section 4 for additional installation considerations SAFEty DANGER Electrical input may be needed for this equipment this work should be performed by a qualified electrician All wiring shall be done in accordance with the National Electrical Code ANSI NFPA 70 latest edition any local codes that may apply an...

Page 4: ...SLEEVE ASSEMBLY TO WALL AND FLOOR OPENINGS Damper assemblies must be installed in wall floor openings using a single retaining plate on either side of the wall floor or by using a retaining plate on both sides of the wall floor The use of a second retaining plate is allowed but is not necessary A single retaining plate is provided with the dampers A second retaining plate can be ordered as an opti...

Page 5: ...or with the higher temperature setting When the temperature of the secondary sensor is exceeded the damper closes and remains closed thereafter Fig 6 The TOR assembly also contains a single pole double throw switch used to indicate damper blade position The switch provides a positive open or closed signal when used in conjunction with remote indicator lights See page 6 Fig 6 for wiring of the TOR ...

Page 6: ... primary sensor 212 F optional primary sensor 250 F secondary sensor 350º F secondary sensor 8 Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown see Fig 7 Double vertical studs are not required for openings 36 in x 36 in or smaller Gypsum wall board must be fastened 12 in on center to all stud and runner flanges surrounding opening see Fig 8 All construc...

Page 7: ...led too far into wall Move out to line designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance Damper does not fully open and or fully close Damper does not operate Actuator runs hot or makes a humming noise Link separated Heat Replace link Actuator prohibited from reaching end of stroke Disconnect linkage from jackshaft open damper power actuato...