background image

4

2. SLEEVE LENGtH AND WALL/FLOOR tHICKNESS

  Insert the damper assembly into the prepared opening, to 

appropriate depth (see Page 3, 

Fig. 1

).

  Recommended maximum and minimum insertion depth 

can be exceeded if:

1)  the operation of the damper actuator is not 

impeded and

2)  the CL of the damper blade remains within the 

plane of the wall/floor 

 

IMPORtANt SAFEty DANGER! :

 To avoid 

causing death or serious bodily harm to building 
occupants, do not insert screws into the damper 
frame unless used for duct connection within 2 
in. of the frame end. 

  The sleeve may extend a maximum of 16 in. beyond the 

wall or floor on the actuator side of the damper and a 
maximum of 6 in. on the opposite side. 

3. DUCt tO SLEEVE CONNECtIONS

  Dampers are supplied with sleeves and actuators from 

the factory and can be installed without the need for 
additional field installed sleeves.

  Gauge of factory furnished sleeve determines the 

type of duct to sleeve connections required (see table 
below). Any duct connection other than the breakaway 
connections are considered rigid. 

 

 

 

type of Duct to

  Sleeve Gauge  Duct Dimension 

Sleeve Connection 

 

 

 

Permitted

10 ga. (0.138 in.)
14 ga. (0.075 in.) 

24 in. max. dia. 

Rigid or Breakaway

16 ga. (0.060 in.)   

 

 20 ga. (0.036 in.)  24 in. max. dia. 

Breakaway only 

 

 

 

Sleeve thickness must not be less than the gauge of the connecting 

duct.
UL Standard 555 requires all ducts to terminate at fire damper 

sleeves. 

4. SECURING tHE DAMPER/SLEEVE ASSEMBLy 

tO WALL AND FLOOR OPENINGS

 
  Damper assemblies must be installed in wall/floor 

openings using a single retaining plate on either 
side of the wall/floor or by using a retaining plate 
on both sides of the wall/floor. The use of a second 
retaining plate is allowed, but is not necessary. A 
single retaining plate is provided with the dampers. A 
second retaining plate can be ordered as an option. 
The outside dimension of the supplied retainer plate is 
nominal dia. + 4.50”.   

   

•  The retaining plate(s) will open up for easy  

 

  installation when the clamping screw is  

   

  loosened. If necessary, remove the clamping  

 

  screw and nut (see 

Fig. 2

).

   

  (IMPORTANT: The clamping mechanism should  

 

  face away from the wall/floor).

 Retainer plate(s)  

 

  are designed to mount flush to the wall/floor  

 

  and hold the damper in the wall/floor opening.

   

•  Place the damper and attached retainer plate  

 

  into the wall/floor opening. 

   

•  If a second retaining plate is being used, secure  

 

it on the opposite side of the wall/floor 

 
 

DO NOt POSItION REtAINER PLAtE(S) IN 
FRAME GROOVE

   

•   Verify position, blade orientation, and actuator 

clearance then tighten the retainer plate 
clamping screws. The retainer plate(s) must 
overlap the wall/floor opening a minimum 
of 1 inch.  Secure the retainer plate(s) to the 
wall using appropriate fasteners (minimum #8 
sheet metal screws) at the four corners of each 
retainer plate when two retainer plates are used 
and also within 

3

in. of the center of each plate 

when one retainer plate is used. 

0QFOJOHJO.JO

JO.JO5ZQ

'BTUFOFST

$MBNQJOH
4DSFX

/VU

3FUBJOJOH
1MBUF"TTFNCMZ

$MBNQJOH4DSFX

.JOJNVN8BMM'MPPS0QFOJOH

/PNJOBM%JBJO

Fig. 2

Summary of Contents for FSDR-XXX

Page 1: ... backcharges without prior written authorization Due to continuing research Greenheck reserves the right to change specifications without notice UL CLASSIFIED see complete marking on product UL CLASSIFIED to Canadian safety standards see complete marking on product UL Standard 555 555S Classification R13317 FSDR XXX SEFSDR XXX and SSFSDR XXX Model Dampers are intended for installation in accordanc...

Page 2: ...ve leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and after installation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be sufficiently covered as to pr...

Page 3: ...opening must be a minimum of 7 8 in larger than the outside diameter of the damper Refer to Section 4 for additional installation considerations SAFEty DANGER Electrical input may be needed for this equipment this work should be performed by a qualified electrician All wiring shall be done in accordance with the National Electrical Code ANSI NFPA 70 latest edition any local codes that may apply an...

Page 4: ...SLEEVE ASSEMBLY TO WALL AND FLOOR OPENINGS Damper assemblies must be installed in wall floor openings using a single retaining plate on either side of the wall floor or by using a retaining plate on both sides of the wall floor The use of a second retaining plate is allowed but is not necessary A single retaining plate is provided with the dampers A second retaining plate can be ordered as an opti...

Page 5: ...or with the higher temperature setting When the temperature of the secondary sensor is exceeded the damper closes and remains closed thereafter Fig 6 The TOR assembly also contains a single pole double throw switch used to indicate damper blade position The switch provides a positive open or closed signal when used in conjunction with remote indicator lights See page 6 Fig 6 for wiring of the TOR ...

Page 6: ... primary sensor 212 F optional primary sensor 250 F secondary sensor 350º F secondary sensor 8 Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown see Fig 7 Double vertical studs are not required for openings 36 in x 36 in or smaller Gypsum wall board must be fastened 12 in on center to all stud and runner flanges surrounding opening see Fig 8 All construc...

Page 7: ...led too far into wall Move out to line designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance Damper does not fully open and or fully close Damper does not operate Actuator runs hot or makes a humming noise Link separated Heat Replace link Actuator prohibited from reaching end of stroke Disconnect linkage from jackshaft open damper power actuato...

Reviews: