Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust

Duct Connections

Plenum Bottom Inlet Opening

Plenum Side Inlet Duct Dimension

Cabinet 

Size

Length 

(inches)

Width 

(inches)

020

86

25

030

120

25

040

172

25

060

236

25

Cabinet 

Size

Length 

(inches)

Height 

(inches)

020

86

30

030

120

30

040

172

30

060

236

30

Length

Gasket or Sealant

(by others)

Gasket or Sealant

(by others)

Screws

(by others)

Contractor

Installed

Ductwork

Height

Length

Width

Service

Door

Service

Door

Service

Door

Bottom Inlet

Plenum Side Inlet

Length

Gasket or Sealant

(by others)

Gasket or Sealant

(by others)

Screws

(by others)

Contractor

Installed

Ductwork

Height

Energy Recovery Cabinet

Energy Recovery Cabinet

Roof Deck

Curb

Curb

Roof Deck

RECOMMENDED DUCT INSTALLATION FOR VEKTOR ENERGY RECOVERY VERTICAL INLETS

NOTE:

-ALL DUCT WORK AND HARDWARE SUPPLIED BY OTHERS

-CAULK AND/OR GASKETING MATERIAL SHOULD BE USED TO SEAL DUCT TO VEKTOR ERS CABINET 

Contractor

Installed

Ductwork

Contr actor

Installed

Ductwork

Energy Recovery Cabinet

Energy Recovery Cabinet

Roof Deck

Curb

Curb

Roof Deck

RECOMMENDED DUCT INSTALLATION FOR VEKTOR ENERGY RECOVERY VERTICAL INLETS

NOTE:

-ALL DUCT WORK AND HARDWARE SUPPLIED BY OTHERS

-CAULK AND/OR GASKETING MATERIAL SHOULD BE USED TO SEAL DUCT TO VEKTOR ERS CABINET 

Contractor

Installed

Ductwork

Contr actor

Installed

Ductwork

Duct Connections

Installation of all ducts should be done in accordance 
with SMACNA and AMCA guidelines.
Connect primary exhaust air ducts to unit using 
flanged connections. Screw ducts directly to unit 
using stainless steel self-tapping sheet metal screws. 
Contractor is responsible for providing transitions 
to accommodate difference in sizing between unit 
and building ducts. Duct connections to collar-type 
openings can be made with S-cleats or overlapping 
joints. Apply caulking around the duct connection. 
Failure to ensure a tight fit and properly seal duct 
connections can cause air leakage and system 
performance problems from the contaminated 
airstream.

Summary of Contents for ERS-MD

Page 1: ...oving parts as well as other potential hazards Other considerations may be required if high winds or seismic activity are present If more information is needed contact a licensed professional engineer before moving forward 1 Follow all local electrical and safety codes as well as the National Electrical Code NEC the National Fire Protection Agency NFPA where applicable Follow the Canadian Electric...

Page 2: ...For hard to reach internal surfaces or for occasional use consider using Tectyl 511M Rust Preventive or WD 40 or the equivalent Receiving Upon receiving the product check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received Inspect each crate for shipping damage before accepting delivery Notify the carrier if any damage is noticed The carrier...

Page 3: ...d be used to identify and assemble the complete system Assembling systems with different identification tags can cause reductions in the fan s performance General Information To ensure a successful installation the instructions in this manual should be read and adhered to Failure to comply with proper installation procedures may void the warranty Pre Installation Checks Prior to fully assembling a...

Page 4: ...g to desired location 7 Never lift units in windy conditions 8 Preparation of curb and roof openings should be completed prior to lifting unit to the roof Verify the curb has the gasket seal on the top surface 9 Do not use fork lifts for handling unit Cabinet Size Cabinet Height Weight lbs 020 075 3700 090 4500 030 075 4300 090 4900 040 075 5400 090 6100 060 075 6900 090 7800 110 8300 Weights show...

Page 5: ...5 DRAIN LIFT LUG QTY 8 S S ISOLATION DAMPER Coil Coil Optional External Piping by others Service Doors Internal Pipe Chase Side or Bottom Intake Opening Lift Bracket Optional Internal Piping by others under Vektor fans Bypass Weatherhood s Vektor bypass air plenum optional mounting locations shown Filters Coil Coil Coil Service Doors Coil Service Clearance Coil Service Clearance Clearance Clearanc...

Page 6: ...the hardware kit attach the unit sections by bolting together frame extrusion from the inside Tighten the bolt washer assemblies to the top and both sides of the joining sections Start on the lower sides and work towards the top As the bolts are tightened the plenum sections will draw together Use anti seize gel to prevent galling welding of all stainless steel fasteners If necessary pull the unit...

Page 7: ...Contractor Installed Ductwork Energy Recovery Cabinet Energy Recovery Cabinet Roof Deck Curb Curb Roof Deck RECOMMENDED DUCT INSTALLATION FOR VEKTOR ENERGY RECOVERY VERTICAL INLETS NOTE ALL DUCT WORK AND HARDWARE SUPPLIED BY OTHERS CAULK AND OR GASKETING MATERIAL SHOULD BE USED TO SEAL DUCT TO VEKTOR ERS CABINET Contractor Installed Ductwork Contr actor Installed Ductwork Duct Connections Installa...

Page 8: ...ses steel toe boots and gloves are recommended during the installation and maintenance of the coil All field piping must be self supporting System piping should be flexible enough to allow for the thermal expansion and contraction of the coil Water Coil Installation Recommendations 1 Piping should be in accordance with accepted industry standards Always use a back up wrench on the coil connections...

Page 9: ... are located only in the coil plenum section Access is needed from both sides of the plenum to change all the filters Unit may have either 2 inch MERV 8 filters or 4 inch MERV 11 filters depending on the application requirements Use equivalent MERV rating filters when replacing Change the filters regularly Pressure drop readings can be used to determine when a filter should be replaced Prefilters ...

Page 10: ...es the pressure across the filter section Periodic inspection is necessary to determine whether filters need to be replaced Vapor Tight Lights Vapor tight lights provide light to each of the compartments in the energy recovery plenum The lights are wired to a junction box mounted on the outside of the unit The switch requires a separate power source to allow for power to the lights when the unit m...

Page 11: ...en working with coils Fin Straightening Coil fins may have been bent during shipping or servicing and should be straightened to maintain maximum heat transfer Reduction of the effective coil surface will correspondingly reduce coil capacity Always check fin appearance after any handling of the coil and after any servicing is done near the coils Fin combs are sized according to number of fins per i...

Page 12: ...over of Part 474118 Service Coil Change Out Procedure Coils can only be pulled out through the side of the plenum cabinet Side panels which are nearest to the coil can be removed if the coil needs to be replaced Size 020 ERS plenums only have a single coil and do not require coil removal clearances on both sides If necessary both coils can be removed through the same side of the plenum housing Thi...