background image

OPTIONAL

SECOND MOTOR

(PRIMARY)

L2

MOTOR

WHIT

E

MOTOR

SWITCHING DEVICE

  (BY OTHERS)

L1

(OVERRIDE)

BROW

N

BLACK

ORANGE

BLUE

BLACK

115 VAC

RED

TOR

15

5

12

11

2

1

14

13

3 4

18

8

16 17

6 7

19 20

9 10

C

A B

YELLO

W

YELLO

W

YELLO

W

YELLO

W

SWITCH #1

SWITCH #2

BLACK

WHIT

E

WHIT

E

MOTOR

BLACK

OPTIONAL

THIRD MOTOR

BLUE

RED

WHIT

E

24 VAC/VDC

WHIT

E

12

11

14

13

1 2 3 4 5

15

18

16 17

19 20

8

6 7

9 10

C

A B

1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.

2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" 

OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS 

MUST ALSO BE SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.

THE OCI WIRES MUST BE CHECKED TO VERIFY 

WHICH SET INDICATES THE CLOSED POSITION 

OF DAMPER. THIS SET OF WIRES SHOULD THEN 

BE LABELED WITH A BLUE WIRE MARKER 

(382169).

TOR

Wiring Diagrams

Figure 3: 

Label applied to 

dampers with factory mounted 
duct smoke detectors.

 

Smoke  detector  r equir es  100  fpm  minimum 

air velocity in duct. For damper activation 

r equir ements when system velocity is less 

than 100 fpm, the local authority having

jurisdiction should be consulted. 

Refer to smoke detector installation 

instructions and Gr eenheck IOM - Smoke 

Detector Supplement FS for dampers with 

factory mounted duct smoke detectors. 

458565 

482753 DUCTSD Smoke Detector

5

®

Summary of Contents for Duct SD

Page 1: ...nsulted prior to the installation of the damper and smoke detector 3 Holes on sampling tube must face into airstream 4 Smoke detector specifications are Operating temperature range 4 F to 158 F 20 C to 70 C Operating humidity range 10 to 95 R H Operation voltage 24 VAC DC or 120 VAC 50 60 Hz 5 Refer to System Sensor DUCTSD Installation and Maintenance Instructions for further installation details ...

Page 2: ...in 152mm 15 in 381mm 24 in 610mm Dampers Equal to or Greater Than 10 inches 254 mm But Less Than 25 Inches 635 mm in Height Height equal to or greater than 10 in 254mm 3 in 76mm 6 in 152mm 15 in 381mm 24 in 610mm 9 25 in 235mm 3 in 76mm Dampers Equal to or Greater Than 25 inches 635 mm in Height 9 25 in 235mm 3 in 76mm Height equal to or greater than 25 in 635mm 11 in 279mm 6 in 152mm 4 in 102mm 2...

Page 3: ...MOTOR L1 BLUE BLACK 115 VAC RED OCI 15 5 12 11 2 1 14 13 3 4 18 8 16 17 6 7 19 20 9 10 C A B YELLOW YELLOW YELLOW YELLOW SWITCH 1 SWITCH 2 BLACK WHITE WHITE MOTOR BLACK OPTIONAL THIRD MOTOR BLUE RED WHITE 24 VAC VDC WHITE 12 11 14 13 1 2 3 4 5 15 18 16 17 19 20 8 6 7 9 10 C A B 1 CONDUIT RUNS WHICH EXCEED 72 MUST HAVE GREEN GROUND WIRE 2 FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP 458296 WIT...

Page 4: ... AT A MAXIMUM OF 24 ON CENTER THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER 382169 RRL OCI OPTIONAL SECOND MOTOR L2 MOTOR WHITE MOTOR L1 BLACK ORANGE BLUE BLACK 115 VAC RED RRL 15 5 12 11 2 1 14 13 3 4 18 8 16 17 6 7 19 20 9 10 C A B BLACK WHITE WHITE MOTOR BLACK OPTIONAL THIRD MOTOR BLUE R...

Page 5: ...ANDI BOX OR ACTUATOR CONDUIT RUNS MUST ALSO BE SECURED ALONG SLEEVE AT A MAXIMUM OF 24 ON CENTER THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER 382169 TOR Wiring Diagrams Figure 3 Label applied to dampers with factory mounted duct smoke detectors Smokedetector requires100 fpm minimum air vel...