Mounting Orientation and Space Envelopes

Dampers Equal to or Greater Than 7 inches (178 mm) But Less Than 10 Inches (254 mm) in Height

0.875 in.

(22mm)

1.4 in.

(36mm)

3 in.

(76mm)

9.25 in.

(235mm)

Height equal to or 

greater than 7 

inches (178mm)

3 in.

(76mm)

6 in.

(152mm)

15 in.

(381mm)

24 in.

(610mm)

Dampers Equal to or Greater Than 10 inches (254 mm) But Less Than 25 Inches (635 mm) in Height

Height equal to or 

greater than 10 in. 

(254mm)

3 in. 

(76mm)

6 in.

(152mm)

15 in. 

(381mm)

24 in.

(610mm)

9.25 in.

(235mm)

3 in.

(76mm)

Dampers Equal to or Greater Than 25 inches (635 mm) in Height

9.25 in.

(235mm)

3 in.

(76mm)

Height equal to 

or greater than 

25 in. (635mm)

11 in. 

(279mm)

6 in.

(152mm)

4 in.

(102mm)

21 in.

(533mm)

482753 DUCTSD Smoke Detector

2

®

Summary of Contents for Duct SD

Page 1: ...nsulted prior to the installation of the damper and smoke detector 3 Holes on sampling tube must face into airstream 4 Smoke detector specifications are Operating temperature range 4 F to 158 F 20 C to 70 C Operating humidity range 10 to 95 R H Operation voltage 24 VAC DC or 120 VAC 50 60 Hz 5 Refer to System Sensor DUCTSD Installation and Maintenance Instructions for further installation details ...

Page 2: ...in 152mm 15 in 381mm 24 in 610mm Dampers Equal to or Greater Than 10 inches 254 mm But Less Than 25 Inches 635 mm in Height Height equal to or greater than 10 in 254mm 3 in 76mm 6 in 152mm 15 in 381mm 24 in 610mm 9 25 in 235mm 3 in 76mm Dampers Equal to or Greater Than 25 inches 635 mm in Height 9 25 in 235mm 3 in 76mm Height equal to or greater than 25 in 635mm 11 in 279mm 6 in 152mm 4 in 102mm 2...

Page 3: ...MOTOR L1 BLUE BLACK 115 VAC RED OCI 15 5 12 11 2 1 14 13 3 4 18 8 16 17 6 7 19 20 9 10 C A B YELLOW YELLOW YELLOW YELLOW SWITCH 1 SWITCH 2 BLACK WHITE WHITE MOTOR BLACK OPTIONAL THIRD MOTOR BLUE RED WHITE 24 VAC VDC WHITE 12 11 14 13 1 2 3 4 5 15 18 16 17 19 20 8 6 7 9 10 C A B 1 CONDUIT RUNS WHICH EXCEED 72 MUST HAVE GREEN GROUND WIRE 2 FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP 458296 WIT...

Page 4: ... AT A MAXIMUM OF 24 ON CENTER THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER 382169 RRL OCI OPTIONAL SECOND MOTOR L2 MOTOR WHITE MOTOR L1 BLACK ORANGE BLUE BLACK 115 VAC RED RRL 15 5 12 11 2 1 14 13 3 4 18 8 16 17 6 7 19 20 9 10 C A B BLACK WHITE WHITE MOTOR BLACK OPTIONAL THIRD MOTOR BLUE R...

Page 5: ...ANDI BOX OR ACTUATOR CONDUIT RUNS MUST ALSO BE SECURED ALONG SLEEVE AT A MAXIMUM OF 24 ON CENTER THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER 382169 TOR Wiring Diagrams Figure 3 Label applied to dampers with factory mounted duct smoke detectors Smokedetector requires100 fpm minimum air vel...

Page 6: ...Notes 482753 DUCTSD Smoke Detector 6 ...

Page 7: ...Notes 482753 DUCTSD Smoke Detector 7 ...

Page 8: ...tes 482753 DUCTSD Smoke Detector Rev 3 January 2022 Copyright 2022 Greenheck Fan Corporation 8 Phone 715 359 6171 Fax 715 355 2399 Parts 800 355 5354 E mail gfcinfo greenheck com Website www greenheck com ...