GreenAire RAH-1000 series Installation And Operation Manual Download Page 4

CAUTION: For supply air locations there must be at least .075” static

pressure availabl
static pressure then a return air location may be required.

I.

If you have a return side installation no supply air feed is needed.

J. When installing the STS Box be sure to leave adequate service

must have ‘pull’ room for the tank to be removed if necessary. The cover for
the STS Box is a ‘Zero’ clearance cover. However standard space
requirements are at least 1.5x the width of the STS Box of space is needed in
front to service it.

II) RO System Location and Piping:

A. Now install the Reverse

mountable with simply two screws and can be hung as self supporting. Follow
the instructions outlined below
respective connections. All connections are simple quick connects. It is
recommended that a shut off valve be placed in line after tapping the domestic
water line for the RO System supply.

1) Locate and connect the

equipment. This will be the right side as you face the system. The
supply side will consist of Black ¼” tubing.

2) Locate the Yellow drain line, and place in an appropriate area for

drainage.

HUMIDIFICATION SEASON IS MONTHS AWAY.
CONDENSATE PUMP

3) Locate the b

humidifiers
system metal
storage tank.
proximity to the RO System.

4)

Make sure to open the valve at the top of the storage tank.

5) Once installed, allow the system to run for approximately 15

minutes to flush completely. Make sure there are no leaks, parts
can come loose in shipping. Hand tightening may be necessary.

6) The RO System will run until all the humidifier supply lines and

storage tank are filled and charged to the pressure of the building.
This may take several hours to happen.

7) PLEASE N

WATER SUPPLY TO THE RO SYSTEM.

if this is a problem)

B. Pipe supply piping from

Panel/Generator or STS Box

C. Open the inline water

the filling of water to the
filling the clear water filter housings on the RO System.

CAUTION: For supply air locations there must be at least .075” static

pressure available at the supply feed location. If there is not enough
static pressure then a return air location may be required.

If you have a return side installation no supply air feed is needed.
When installing the STS Box be sure to leave adequate service
must have ‘pull’ room for the tank to be removed if necessary. The cover for
the STS Box is a ‘Zero’ clearance cover. However standard space
requirements are at least 1.5x the width of the STS Box of space is needed in

) RO System Location and Piping:

everse Osmosis (RO) Water system. These systems are wall

mountable with simply two screws and can be hung as self supporting. Follow

outlined below for connecting the colored tubes to their

respective connections. All connections are simple quick connects. It is
recommended that a shut off valve be placed in line after tapping the domestic
water line for the RO System supply.

Locate and connect the domestic water supply side of the

quipment. This will be the right side as you face the system. The

supply side will consist of Black ¼” tubing.
Locate the Yellow drain line, and place in an appropriate area for
drainage.

NOTE: DRAIN MUST BE OPERABLE! EVEN IF THE

HUMIDIFICATION SEASON IS MONTHS AWAY.
CONDENSATE PUMP – IT MUST BE ON LINE!

Locate the blue product water line that will provide
humidifiers. Utilize a “t” connector (provided and taped to the RO
system metal frame) to hook up the product water (blue line) to the
storage tank. Locate the 2.5 gallon storage/bladder tank in close
proximity to the RO System.

Make sure to open the valve at the top of the storage tank.

Once installed, allow the system to run for approximately 15
minutes to flush completely. Make sure there are no leaks, parts
can come loose in shipping. Hand tightening may be necessary.
The RO System will run until all the humidifier supply lines and

torage tank are filled and charged to the pressure of the building.

This may take several hours to happen.

PLEASE NOTE: 35 PSI MINIMUM REQUIRED ON
WATER SUPPLY TO THE RO SYSTEM.

(Consult with the Factory

if this is a problem)

Pipe supply piping from the RO System to the fitting on the side of the

or STS Box labeled “

water in

”.

Open the inline water valve off of the building domestic water supply to begin

filling of water to the RO System. You should notice water immediately

filling the clear water filter housings on the RO System.

4

CAUTION: For supply air locations there must be at least .075” static

e at the supply feed location. If there is not enough

static pressure then a return air location may be required.

If you have a return side installation no supply air feed is needed.
When installing the STS Box be sure to leave adequate service room. You
must have ‘pull’ room for the tank to be removed if necessary. The cover for
the STS Box is a ‘Zero’ clearance cover. However standard space
requirements are at least 1.5x the width of the STS Box of space is needed in

Water system. These systems are wall

mountable with simply two screws and can be hung as self supporting. Follow

for connecting the colored tubes to their

respective connections. All connections are simple quick connects. It is
recommended that a shut off valve be placed in line after tapping the domestic

supply side of the

quipment. This will be the right side as you face the system. The

Locate the Yellow drain line, and place in an appropriate area for

! EVEN IF THE

IF PIPED TO A

e product water line that will provide RO water to the

(provided and taped to the RO

to hook up the product water (blue line) to the

Locate the 2.5 gallon storage/bladder tank in close

Make sure to open the valve at the top of the storage tank.

Once installed, allow the system to run for approximately 15
minutes to flush completely. Make sure there are no leaks, parts
can come loose in shipping. Hand tightening may be necessary.
The RO System will run until all the humidifier supply lines and

torage tank are filled and charged to the pressure of the building.

ON INCOMING

(Consult with the Factory

the RO System to the fitting on the side of the Control

valve off of the building domestic water supply to begin

System. You should notice water immediately

Summary of Contents for RAH-1000 series

Page 1: ...o Wet Switch Parts List More Components VS 10 13 INSTALLATION AND OPERATION RAH 1000 1500 Series Table of Contents Initial items 1 Humidifier basics 2 Installing humidifier 3 Sequence of Operation 6 T...

Page 2: ...gs The following guidelines should be adhered to The DTA should be placed in a straight section of duct work with at feet up stream and downstream with no obstructions branch take offs or If a vertica...

Page 3: ...r downstream of the DTA for at least 3 ft in either direction Sealant can be used on the flange if desired for complete seal Once you have located the Generator in a clear and accessible location use...

Page 4: ...tem The supply side will consist of Black tubing Locate the Yellow drain line and place in an appropriate area for drainage NOTE DRAIN MUST BE OPERABLE EVEN IF THE HUMIDIFICATION SEASON IS MONTHS AWAY...

Page 5: ...domestic water supply and the humidifier supply lines If there are any questions or issues please contact your Factory Representative If the system was provided with a controlling humidity sensor then...

Page 6: ...m If your model has a timer delay relay go to that section in this Manual for more info In this configuration the Digital Controller governs the humidifier The electronic humidity sensor is wired back...

Page 7: ...H 10 00 G E N E R AT O R Install Generator at angle so door can swing completely open REDUCE TO 3 AT PANEL FAN FRONT VIEW FROM CLOSET DOOR SIDE VIEW W ATER PURIFICATION STATION STORAGE TANK Note water...

Page 8: ...GURE 1 TYPICAL LAYOUT 10 RETURN DUCT ELECTRONIC AIR FILTER SUPPLY AIR REENSAIR CONTROL PANEL 15 Amp Cir 20 x20 x12 WATER PURIFICATION STATION STORAGE TANK TO DRAIN DRAIN ALL LOW POINTS COLD WATER 3 L...

Page 9: ...1030 1050 STS HL Supply Hi Limit Switch AFS Air Flow Switch low voltage multi conductor cable RO WATER STATION 3 GAL STORAGE RETURN SIDE APPLICATION 3 8 OD water drain 3 8 Main to Humidifiers B C E H...

Page 10: ...Flow Switch RAH 1090 STS low voltage multi conductor cable RO WATER STATION 3 GAL STORAGE TANK 1 4 OD water drain SUPPLY SIDE APPLICATION Please Note One 1 RO Water Station can serve FOG ON ON OFF 00...

Page 11: ...DUCT STS UNIT STS UNIT STS UNIT POSSIBLE LOCATIONS SUPPLY AIR FEED SUPPLY DUCT AC UNIT DUCT EXT STS UNIT STS UNIT STS UNIT DTA DTA DTA SUPPLY AIR FEED 11 PLAN VIEW...

Page 12: ...SWITCH HI LIMIT 12B CR3 FLOAT SWITCH SAFETY HHLS FLS CR2 11 12 12A 12C 13 17 16 18 13 TIMER RELAY FCR STS WIRING with CONTROLLER DENOTES ITEM LOCATION OUTSIDE OF CONTROL PANEL GENERATOR 7 CR4 RH SENS...

Page 13: ...11 12 12A 12C 13 17 16 18 13 TIMER RELAY FCR CR1 STS WIRING for REMOTE CONTROL DENOTES ITEM LOCATION OUTSIDE OF CONTROL PANEL GENERATOR 120VAC 7 CR4 2 10 N 2 Power On R 500 VA 7 6 STS BOX 2 WET SWITCH...

Page 14: ...HI LIMIT 12B CR3 FLOAT SWITCH SAFETY HHLS FLS CR2 11 12 12A 12C 13 17 16 18 13 TIMER RELAY FCR STANDARD RAH WIRING WITH CONTROLLER DENOTES ITEM LOCATION OUTSIDE OF CONTROL PANEL GENERATOR CR4 RH SENSO...

Page 15: ...has closed after properly sensing that air is moving in the duct Verify that the HiLimit switch circuit is closed Check the Wet Switch and verify that the green LED on the switch is lit If it is red...

Page 16: ...here is a call for heat There is a dry contact relay in the panel for exactly this purpose Contact the Installer to verify that he utilized this relay and that the control sequence on the blower syste...

Page 17: ...and making sure all the UPC discs that should be running are indeed doing so You may do this by observing the operation with a flash light and peering through the plastic lid or taking the lid off see...

Page 18: ...DIGITAL CONTROLLER DIGITAL CONTROLLER 18...

Page 19: ...19...

Page 20: ...ir humidifiers have their controllers pre programmed in the Factory but if it is somehow lost here is the access and settings A To Access the Initial Setting Mode press button for 3 seconds Here are t...

Page 21: ...21...

Page 22: ...Socket 6047 Idec Single Pole Relay 6048 Idec Single Pole Socket PARTS LIST Item Description 2 4 MHz Nebulizer Board Model 579R3 304SS with welds stand brackets top flange w PEMS and bottom hole Model...

Page 23: ...y or Factory Representative for current pricing Plastic Fan Guard for 4 69 Fan Bulkhead Conn 1 4T x 1 8MPT Brass Part B 400 11 2 clear w paper back in square ft units 10 Amp fuse 12 32 dia time delay...

Reviews: