Controller Configuration
I) Initial Programming:
their controllers pre
is somehow lost, here is the access and settings:
A. To Access the “Initial Setting Mode” press
button for 3 seconds.
page 13:
inPT = u10
(this sets the input type, which is 0
tP-H = 100
(this sets the high of the process, RH)
tP-L = 0
(this sets the low of the process, RH)
Ctrl = on/off
(this sets the control type your using)
S-HC= heat
(control mode, use
ALA1= 0
(this feature not used)
SALA= off
(this feature not used)
CoSH= off
(this feature not used)
C-SL = ASCII
(this feature not used)
C-no = 1
(this feature not used)
bPS = 9600
(baud rate if data transfer was used)
LEN = 7
(this feature not
Prty = even
Parity
Stop = 1
Stop bit setting
Configuration:
I) Initial Programming:
All ReenAir humidifiers have
their controllers pre-programmed in the Factory but if it
is somehow lost, here is the access and settings:
A. To Access the “Initial Setting Mode” press
button for 3 seconds. Here are the settings as shown
(this sets the input type, which is 0
(this sets the high of the process, RH)
(this sets the low of the process, RH)
(this sets the control type your using)
(control mode, use heat)
(this feature not used)
(this feature not used)
(this feature not used)
(this feature not used)
(this feature not used)
(baud rate if data transfer was used)
(this feature not used)
Parity
Stop bit setting
20
humidifiers have
programmed in the Factory but if it
is somehow lost, here is the access and settings:
Here are the settings as shown on
(this sets the input type, which is 0-10v)
(this sets the high of the process, RH)
(this sets the low of the process, RH)
(this sets the control type your using)
(baud rate if data transfer was used)