Wired Controller XE70-33/H
49
(3) Medium pollution: Cleaning degree of current environment is “B”. When
clean cycle is “0”, the accumulative running time is 1400 hours. Every
increase of "1" indicates an increase of 400 hours in running time. When
clean cycle is "9", the accumulative running time is 5000 hours;
(4) Severe pollution: Cleaning degree of current environment is “C”. When clean
cycle is “0”, the accumulative running time is 100 hours. Every increase of
"1" indicates an increase of 100 hours in running time. When clean cycle is
"9", the accumulative running time is 1000 hours;
NOTE:
When cleaning time is up, icon “
” will be displayed on status bar and a
reminder box will pop up on homepage to remind user. Press "Done" or "Ignore" to
cancel the display. Meanwhile, the accumulative time for "Filter clean reminder" is
reset and starts counting again.
7.7 Gate-control Function
When there is Gate-control System, user can insert a card to turn on the unit or
pull off a card to turn off the unit. When the card is re-inserted, the unit will recover the
operation as state in memory. When the card is pulled off (or improperly inserted),
“ ” icon will show, neither remote control nor operation of wired controller will be
effective and icon “ ” will be flickering.
NOTE:
This model cannot be connected with gate control system on its own because
it cannot detect gate control signal directly. To realize gate control display and gate