Wired Controller XE70-33/H
35
Item
Settable range
Default
Remarks
Outdoor Air
Pollution Degree
01: very good
02: good
03: light pollution
04: medium
pollution
05: high pollution
06: severe
pollution
02
Set the outdoor pollution level
according to the pollution degree of
different regions. It is used for
calculating the time for reminding
washing and replacing filter.
Indoor Air Quality
Target
01
、
02
02
When in auto control mode, this setting
is used for controlling the ON/OFF and
standby of ERV+DX Coil unit; for
specific value please the master control
logic;
Auto Control
Sensor
PM2.5, CO
2
,
Common
CO
2
Make sure to conduct auto control
according to target of which sensor
Linkage Method
CAN
、
HBS
CAN
CAN1 linkage: activation of IDU of
anyone of air conditioner or ERV+DX
Coil unit in CAN1 network; turning off
IDU of all the air conditioners and
ERV+DX Coil units;
HBS linkage: activation of IDU of
anyone of air conditioner or ERV+DX
Coil unit under the same wired
controller; turning off IDU of all the air
conditioners and ERV+DX Coil units.