Wired Controller XE70-13/E
4
2.2 Installing Position and Requirements of Wired
Controller
(
1
)
Please do not install the wired controller in the position where is wet or is
likely to be splashed with water;
(
2
)
Please do not install the wired controller near high-temperature objects or
under direct sunlight;
(
3
)
Before installation, please cut off the power supply of strong current wire
inside the wall, it is not allowed to install under electrified status;
(
4
)
In order to avoid malfunction due to electromagnetic interference and
other causes, please pay attention to the following notices:
1) Make sure that the interface of communication wire is correct, otherwise
the communication cannot work;
2) Signal wire of wired controller should be separated from the power cord
and indoor and outdoor connecting wire, the shortest distance should
be over 20cm, otherwise the communication cannot work normally;
3) If the unit is installed in the position where is likely to be impacted by
electromagnetic interface, signal wire of wired controller should be
made of STP (shielded twisted pair).
(
5
)
The wired controller should only be installed indoors, and its working