8
Technical Information
Service Manual
Outdoor Unit
Model of Outdoor Unit
VIRU36HP230V1AO
VIRU30HP230V1AO
Outdoor Unit Product Code
CB432W10100
CB432W10000
Compressor Manufacturer/Trademark
ZHUHAI LANDA COMPRESSOR
CO., LTD
ZHUHAI LANDA COMPRESSOR
CO., LTD
Compressor Model
QXAW-F518zX440C
QXFW-D318ZX035
Compressor Oil
FV50S or equivalent
FW68DA or equivalent
Compressor Type
Rotary
Rotary
Compressor Locked Rotor Amp (L.R.A)
36
30
Compressor RLA
A
24±10%
23
Compressor Power Input
W
5830±3%
3350±3%
Overload Protector
/
/
Throttling Method
Electron expansion valve
Electron expansion valve
Operation temp
ºF
61~86
61~86
Ambient temp (cooling)
ºF
0~109
0~109
Ambient temp (heating)
ºF
-31~75
-31~75
Condenser Form
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube
Pipe Diameter
inch
Φ5/16
Φ5/16
Rows-fin Gap
inch
2-1/16
2-1/16
Coil Length (LXDXW)
inch
41 37/64X1 1/2×38 13/64
41 37/64X1 1/2×38 13/64
Fan Motor Speed
rpm
940
850
Output of Fan Motor
W
170
170
Fan Motor RLA
A
0.73
0.73
Fan Motor Capacitor
μF
/
0
Air Flow Volume of Outdoor Unit
CFM
3119
5300
Fan Type
Axial-flow
Axial-flow
Fan Diameter
inch
Φ21 21/32
Φ21 21/32
Defrosting Method
Automatic Defrosting
Automatic Defrosting
Climate Type
T1
T1
Isolation
I
I
Moisture Protection
IPX4
IPX4
Design Pressure(High)
PSIG
550
550
Design Pressure(Low)
PSIG
240
240
Sound Pressure Level (H/M/L)
dB (A)
63/-/-
61/-/-
Sound Power Level (H/M/L)
dB (A)
73/-/-
73/-/-
Dimension (WXHXD)
inch
43 37/64X43 1/2X16 9/64
43 37/64X43 1/2X16 9/64
Dimension of Carton Box (LXWXH)
inch
45 1/2X18 57/64X45 39/64
45 1/2X18 57/64X45 39/64
Dimension of Package (LXWXH)
inch
45 39/64X19 X44 9/32
45 39/64X19 X44 9/32
Net Weight
Ib
253.53
229.3
Gross Weight
Ib
271.17
240.3
Refrigerant
R410A
R410A
Refrigerant Charge
oz
123.5
123.5
Connection
Pipe
Length
ft
24.6
24.6
Gas Additional Charge
oz/ft
0.3
0.3
Outer Diameter Liquid Pipe
inch
Φ1/4
Φ1/4
Outer Diameter Gas Pipe
inch
Φ5/8
Φ5/8
Max Distance Height
ft
98.4
98.4
Max Distance Length
ft
164
164
Note:The connection pipe applies metric diameter.
The above data is subject to change without notice; please refer to the nameplate of the unit.