46
Air to Water Heat Pump
Service Manual- Versati II Series
INSTALLATION
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Oil trap
A
B
A
B
A
B
model
Pipe size
(Diameter:Φ)
Length B
Elevation A
Additional
refrigerant
gas
Liquid
Standard
Max.
Standard
Max.
GRS-CQ12Pd/NaB-K
5/8"
3/8"
7.5m
30m
0m
15m
50g/m
GRS-CQ14Pd/NaB-K
5/8"
3/8"
7.5m
30m
0m
15m
50g/m
GRS-CQ16Pd/NaB-K
5/8"
3/8"
7.5m
30m
0m
15m
50g/m
Note:
①
No additional charge of the refrigerant is need when the pipe length is less than 10 m, if the pipe length
is longer than 10m,additional charge of the refrigerant is needed according to the table.
Example:
If 16kw model is installed at a distance of 25m, (25-10)*50=750g refrigerant should be added;
②
Rated capacity is based on standard pipe length and maximum allowable length is base on the product
reliability in the operation;
③
Oil trap should be installed every 5-7 meters when the location of outdoor unit is higher than indoor unit.
Summary of Contents for Versati II
Page 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL Versati T1 R410A 50Hz GC201308 II ...
Page 4: ...1 Air to Water Heat Pump Service Manual Versati II Series PRODUCT PRODUCT ...
Page 13: ...10 Air to Water Heat Pump Service Manual Versati II Series CONTROL CONTROL ...
Page 37: ...34 Air to Water Heat Pump Service Manual Versati II Series INSTALLATION INSTALLATION ...
Page 62: ...59 Air to Water Heat Pump Service Manual Versati II Series MAINTENANCE MAINTENANCE ...
Page 81: ...78 Air to Water Heat Pump Service Manual Versati II Series MAINTENANCE Fig 14 ...
Page 97: ...JF00301971 ...