23
Air to Water Heat Pump
Service Manual- Versati II Series
CONTROL
Full Name
Displayed Name
Range
Default
Set Mode
Mode
Cool/Heat
Heat
Period 1 running time
Period 1
00:00-23:59
08:30
Water out temperature for cooling /
Room temperature for cooling /
Water out temperature for heating /
Room temperature for heating
WT-heat 1/
RT-heat 1/
WT-cool 1/
RT-cool 1
Refer to the temperature
setting range of
“Weekly Timer”.
35
℃
/95
℉
Period 1 running time
Period 2
00:00-23:59
17:30
Water out temperature for cooling /
Room temperature for cooling /
Water out temperature for heating /
Room temperature for heating
WT-heat 2/
RT-heat 2/
WT-cool 2/
RT-cool 2
Refer to the temperature
setting range of
“Weekly Timer”.
35
℃
/95
℉
3�3�2�15 Floor Debug
1) At the homepage, by pressing the Function key access to the
FUNCTION
page, and then locate where
“
Floor debug
” is, after that, press OK key to go to the
FLOOR DEBUG
setting page.
2) At the
FLOOR DEBUG
setting page, by the Left/Right key select the desired parameter and then by
the Up/Down key configure it. The configurable parameters include “
Segments
”, “
Period 1
temp
”, “
ΔT of
segment
”, and “
Segment time
”, as listed in the following table..
No�
Full Name
Displayed Name
Range
Default
Accuracy
1
Segments for floor debug
Segments
1~10
1
1
2
First temperature for floor debug
Period 1 temp
25~35
℃
/
77~95
℉
25
℃
/77
℉
1
℃
/1
℉
3
Segment temperature
difference for floor debug
ΔT of segment
0~72H
0
12H
4
Segments duration for floor debug
Segment time
2~10
℃
/
36~50
℉
5
℃
/41
℉
1
℃
/1
℉
3) After the above setting is finished, by pressing the function key no. 2 activate this function and a dialog
box will pop up, reminding “
Start the Floor Debug Mode now?
”. If so, press the “OK” key. Once “
Floor debug
”
has been activated, by pressing the function key no. 2, a dialog box also will pop up, reminding “
Stop the Floor
Debug Mode now?
” If so, press the OK key; if not, press “
Cancel
” to go on.
[Notes]
①
This function can be activated only when the unit is OFF. When it is intended to activate this function
with the unit being ON, a dialog box will pop up, warning “
Please turn off the system first!
”.
②
When this function has been activated, it is unable to turn on or off the unit. In this case, when pressing
the ON/OFF key, a dialog will pop up, warning “
Please disable the Floor Debug Mode!
”.
③
When this function has been set successfully, “
Timer week
”, “
Clock timer
” and “
Temp timer
” will be
deactivated.
④
“When “
Floor debug
” mode has been activated, “
Emergen�mode
”, “
Sanitize
”, “
Holiday mode
” is not
Summary of Contents for Versati II
Page 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL Versati T1 R410A 50Hz GC201308 II ...
Page 4: ...1 Air to Water Heat Pump Service Manual Versati II Series PRODUCT PRODUCT ...
Page 13: ...10 Air to Water Heat Pump Service Manual Versati II Series CONTROL CONTROL ...
Page 37: ...34 Air to Water Heat Pump Service Manual Versati II Series INSTALLATION INSTALLATION ...
Page 62: ...59 Air to Water Heat Pump Service Manual Versati II Series MAINTENANCE MAINTENANCE ...
Page 81: ...78 Air to Water Heat Pump Service Manual Versati II Series MAINTENANCE Fig 14 ...
Page 97: ...JF00301971 ...