Multi Variable Air Conditioners Ducted Type Indoor Unit
7
Below are dimensions of A, B, C, etc. for different models:
Unit: mm(in.)
Model
A
B
C
D
E
F
G
H
I
GMV-ND07
PLS/A-T(U)
742
(29-1/4)
491
(19-3/8)
700
(27-1/2)
615
(24-1/4)
200
(7-7/8)
121
(4-3/4)
528
(20-3/4)
161
(6-3/8)
580
(22-7/8)
GMV-ND09
PLS/A-T(U)
GMV-ND12
PLS/A-T(U)
GMV-ND14
PLS/A-T(U)
942
(37-1/8)
491
(19-3/8)
900
(39-3/8)
615
(24-1/4)
200
(7-7/8)
121
(4-3/4)
728
(28-5/8)
161
(6-3/8)
780
(30-3/4)
GMV-ND18
PLS/A-T(U)
1142
(45)
491
(19-3/8)
1100
(43-1/4)
615
(24-1/4)
200
(7-7/8)
121
(4-3/4)
928
(36-1/2)
161
(6-3/8)
980
(38-5/8)
GMV-ND22
PLS/A-T(U)
4.1.2 Suspend the indoor unit
(1) Drill bolt holes and install bolts
1) Stick the reference cardboard on the installation position; drill 4 holes according to
the hole site on the cardboard as shown in fig 4.1.2; diameter of drilling hole is
according to the diameter of expansion bolt and the depth is 60-70mm(2-3/8~2-3/4
in.), as shown in fig 4.1.3.
Unit: mm(in.)
Fig 4.1.2 Fig 4.1.3
2) Insert the M10 expansion bolt into the hole and then knock the nail into the bolt, as
shown in fig 4.1.4.
Note:
The length of bolt depends on the installation height of the unit, bolts are field supplied.
Fig 4.1.4